Items where Subject is "B2: Internal fire spread (linings)"
![]() | Up a level |
- Library of Congress Subject Areas (24)
- K Law (24)
- The Building Regulations 2010 (24)
- B2: Internal fire spread (linings) (24)
- The Building Regulations 2010 (24)
- K Law (24)
absorption coefficient
NOTES:
1. Upper and lower surfaces of suspended ceiling, between plastic panels, to comply with paragraph 4.1.
2. No restriction on class D-s3, d2 diffusers or rooflights in small rooms.
3. See note 4 to Table 4.2. 5m²
See Table 4.2
absorptive material
Thermoplastic materials that do not meet the classifications in Table 4.1 can be used as described in paragraphs 4.13 to 4.17. No guidance for European fire test performance is currently available, because there is no generally accepted test and classification procedure.
Thermoplastic materials are defined in Appendix B, paragraph B11. Classifications used here are explained in paragraph B13.
Materials within this zone – at plane of ceiling – should comply with Table 4.1
Rooflights
See Table 4.2
access room
Parts of walls in rooms may be of lower performance than stated in Table 4.1, but no worse than class D-s3, d2. In any one room, the total area of lower performance wall lining should be less than an area equivalent to half of the room’s floor area, up to a maximum of 20m2 of wall lining.
air path
Any flexible membrane covering a structure, other than an air-supported structure, should comply with Appendix A of BS 7157.
air permeability
Internal fire spread (linings)
B2.(1) To inhibit the spread of fire within the building, the internal linings shall —
(a) adequately resist the spread of flame over their surfaces; and
(b) have, if ignited, either a rate of heat release or a rate of fire growth, which is reasonable in the circumstances.
(2) In this paragraph “internal linings” means the materials or products used in lining any partition, wall, ceiling or other internal structure.
The surface linings of walls and ceilings should meet the classifications in Table 4.1.
a. DIFFUSER FORMING PART OF CEILING
b. DIFFUSER IN FITTING BELOW AND NOT FORMING PART OF CEILING
See para 4.15
The following paragraphs apply to lighting diffusers forming part of a ceiling. Diffusers may be part of a luminaire or used below sources of light. The following paragraphs do not apply to diffusers of light fittings attached to the soffit of a ceiling or suspended beneath a ceiling (Diagram 4.1).
Diffusers constructed of thermoplastic material may be incorporated in ceilings to rooms and circulation spaces, but not to protected stairways, if both the following conditions are met.
a. Except for the upper surfaces of the thermoplastic panels, wall and ceiling surfaces exposed in the space above the suspended ceiling should comply with paragraph 4.1.
b. Diffusers should be classified as one of the following.
i. TP(a) rigid – no restrictions on their extent.
ii. TP(b) – limited in their extent (see Table 4.2 and Diagram 4.2).
A ceiling constructed from TP(a) flexible panels should meet the following conditions.
a. Have a maximum area of 5m2.
b. Be supported on all sides.
For the purposes of this requirement, a wall includes both of the following.
a. The internal surface of internal and external glazing (except glazing in doors).
b. Any part of a ceiling which slopes at an angle greater than 70 degrees to the horizontal.
Parts of walls in rooms may be of lower performance than stated in Table 4.1, but no worse than class D-s3, d2. In any one room, the total area of lower performance wall lining should be less than an area equivalent to half of the room’s floor area, up to a maximum of 20m2 of wall lining.
For the purposes of this requirement, a ceiling includes all of the following.
a. Glazed surfaces.
b. Any part of a wall at 70 degrees or less to the horizontal.
c. The underside of a gallery.
d. The underside of a roof exposed to the room below.
approved document
Guidance on the control of flame spread is given in the following sections.
a. Stairs and landings: Sections 2 and 3 (escape stairs) and Section 15 (firefighting shafts).
b. Exposed surfaces above fire-protecting suspended ceilings: Section 8.
c. Enclosures to above-ground drainage system pipes: Section 9.
Guidance on the use of PTFE-based materials for tension-membrane roofs and structures is given in the BRE report BR 274.
b2 internal fire spread linings
Internal fire spread (linings)
B2.(1) To inhibit the spread of fire within the building, the internal linings shall —
(a) adequately resist the spread of flame over their surfaces; and
(b) have, if ignited, either a rate of heat release or a rate of fire growth, which is reasonable in the circumstances.
(2) In this paragraph “internal linings” means the materials or products used in lining any partition, wall, ceiling or other internal structure.
In the Secretary of State’s view, requirement B2 is met by achieving a restricted spread of flame
over internal linings. The building fabric should make a limited contribution to fire growth,
including a low rate of heat release.
It is particularly important in circulation spaces, where linings may offer the main means by which
fire spreads and where rapid spread is most likely to prevent occupants from escaping.
Requirement B2 does not include guidance on the following.
a. Generation of smoke and fumes.
b. The upper surfaces of floors and stairs.
c. Furniture and fittings.
The surface linings of walls and ceilings should meet the classifications in Table 4.1.
For the purposes of this requirement, a wall includes both of the following.
a. The internal surface of internal and external glazing (except glazing in doors).
b. Any part of a ceiling which slopes at an angle greater than 70 degrees to the horizontal.
b3 internal fire spread structure
Internal fire spread (linings)
B2.(1) To inhibit the spread of fire within the building, the internal linings shall —
(a) adequately resist the spread of flame over their surfaces; and
(b) have, if ignited, either a rate of heat release or a rate of fire growth, which is reasonable in the circumstances.
(2) In this paragraph “internal linings” means the materials or products used in lining any partition, wall, ceiling or other internal structure.
In the Secretary of State’s view, requirement B2 is met by achieving a restricted spread of flame
over internal linings. The building fabric should make a limited contribution to fire growth,
including a low rate of heat release.
It is particularly important in circulation spaces, where linings may offer the main means by which
fire spreads and where rapid spread is most likely to prevent occupants from escaping.
Requirement B2 does not include guidance on the following.
a. Generation of smoke and fumes.
b. The upper surfaces of floors and stairs.
c. Furniture and fittings.
Insulating core panels consist of an inner core of insulation sandwiched between, and bonded to, a membrane, such as galvanised steel or aluminium.
Where they are used internally they can present particular problems with regard to fire spread and should meet all of the following conditions.
a. Panels should be sealed to prevent exposure of the core to a fire. This includes at joints and where services penetrate the panel.
b. In high fire risk areas, such as kitchens, places of special fire hazard, or in proximity to where hot works occur, only class A1 cored panels should be used.
c. Fixing systems for all panels should be designed to take account of the potential for the panel to delaminate. For instance, where panels are used to form a suspended ceiling, the fixing should pass through the panel and support it from the lower face.
b4 external fire spread
Internal fire spread (linings)
B2.(1) To inhibit the spread of fire within the building, the internal linings shall —
(a) adequately resist the spread of flame over their surfaces; and
(b) have, if ignited, either a rate of heat release or a rate of fire growth, which is reasonable in the circumstances.
(2) In this paragraph “internal linings” means the materials or products used in lining any partition, wall, ceiling or other internal structure.
In the Secretary of State’s view, requirement B2 is met by achieving a restricted spread of flame
over internal linings. The building fabric should make a limited contribution to fire growth,
including a low rate of heat release.
It is particularly important in circulation spaces, where linings may offer the main means by which
fire spreads and where rapid spread is most likely to prevent occupants from escaping.
Requirement B2 does not include guidance on the following.
a. Generation of smoke and fumes.
b. The upper surfaces of floors and stairs.
c. Furniture and fittings.
Insulating core panels consist of an inner core of insulation sandwiched between, and bonded to, a membrane, such as galvanised steel or aluminium.
Where they are used internally they can present particular problems with regard to fire spread and should meet all of the following conditions.
a. Panels should be sealed to prevent exposure of the core to a fire. This includes at joints and where services penetrate the panel.
b. In high fire risk areas, such as kitchens, places of special fire hazard, or in proximity to where hot works occur, only class A1 cored panels should be used.
c. Fixing systems for all panels should be designed to take account of the potential for the panel to delaminate. For instance, where panels are used to form a suspended ceiling, the fixing should pass through the panel and support it from the lower face.
For the purposes of this requirement, a ceiling includes all of the following.
a. Glazed surfaces.
b. Any part of a wall at 70 degrees or less to the horizontal.
c. The underside of a gallery.
d. The underside of a roof exposed to the room below.
Guidance on the use of PTFE-based materials for tension-membrane roofs and structures is given in the BRE report BR 274.
background ventilator
NOTES:
1. Upper and lower surfaces of suspended ceiling, between plastic panels, to comply with paragraph 4.1.
2. No restriction on class D-s3, d2 diffusers or rooflights in small rooms.
3. See note 4 to Table 4.2. 5m²
See Table 4.2
boundary
NOTES:
1. This table does not apply to products that meet the provisions in Table 4.1.
2. Smaller rooflights and diffusers can be grouped together provided that both of the following satisfy the dimensions in Diagram 4.2 or 4.3.
a. The overall size of the group.
b. The space between one group and any others.
3. Lighting diffusers of TP(a) flexible rating should be used only in panels of a maximum of 5m2 each. See paragraph 4.17.
4. There are no limits on the use of class D-s3, d2 materials in small rooms. See Table 4.1.
5. The minimum 3m separation given in Diagram 4.2 between each 5m2 group must be maintained. Therefore, in some cases, it may not be possible to use the maximum percentage quoted.
building
Any flexible membrane covering a structure, other than an air-supported structure, should comply with Appendix A of BS 7157.
building contract
Insulating core panels consist of an inner core of insulation sandwiched between, and bonded to, a membrane, such as galvanised steel or aluminium.
Where they are used internally they can present particular problems with regard to fire spread and should meet all of the following conditions.
a. Panels should be sealed to prevent exposure of the core to a fire. This includes at joints and where services penetrate the panel.
b. In high fire risk areas, such as kitchens, places of special fire hazard, or in proximity to where hot works occur, only class A1 cored panels should be used.
c. Fixing systems for all panels should be designed to take account of the potential for the panel to delaminate. For instance, where panels are used to form a suspended ceiling, the fixing should pass through the panel and support it from the lower face.
building control bodies
NOTE:
1.Wallcoverings which conform to BS EN 15102, achieving at least class C-s3, d2 and bonded to a class A2-s3, d2 substrate, will also be acceptable.
cavity
Diffusers constructed of thermoplastic material may be incorporated in ceilings to rooms and circulation spaces, but not to protected stairways, if both the following conditions are met.
a. Except for the upper surfaces of the thermoplastic panels, wall and ceiling surfaces exposed in the space above the suspended ceiling should comply with paragraph 4.1.
b. Diffusers should be classified as one of the following.
i. TP(a) rigid – no restrictions on their extent.
ii. TP(b) – limited in their extent (see Table 4.2 and Diagram 4.2).
ceiling
a. DIFFUSER FORMING PART OF CEILING
b. DIFFUSER IN FITTING BELOW AND NOT FORMING PART OF CEILING
See para 4.15
Guidance on the control of flame spread is given in the following sections.
a. Stairs and landings: Sections 2 and 3 (escape stairs) and Section 15 (firefighting shafts).
b. Exposed surfaces above fire-protecting suspended ceilings: Section 8.
c. Enclosures to above-ground drainage system pipes: Section 9.
Diffusers constructed of thermoplastic material may be incorporated in ceilings to rooms and circulation spaces, but not to protected stairways, if both the following conditions are met.
a. Except for the upper surfaces of the thermoplastic panels, wall and ceiling surfaces exposed in the space above the suspended ceiling should comply with paragraph 4.1.
b. Diffusers should be classified as one of the following.
i. TP(a) rigid – no restrictions on their extent.
ii. TP(b) – limited in their extent (see Table 4.2 and Diagram 4.2).
circulation space
Thermoplastic material classified as a TP(a) rigid product may be used to glaze external windows to rooms, but not external windows to circulation spaces. Approved Document K includes guidance on the safety of glazing.
In rooms and circulation spaces other than protected stairways, rooflights may be constructed of thermoplastic material if they comply with both of the following.
a. The lower surface is classified as TP(a) rigid or TP(b).
b. The size and location of the rooflights follow the limits in Table 4.2, Table 12.2 and Table 12.3.
Diffusers constructed of thermoplastic material may be incorporated in ceilings to rooms and circulation spaces, but not to protected stairways, if both the following conditions are met.
a. Except for the upper surfaces of the thermoplastic panels, wall and ceiling surfaces exposed in the space above the suspended ceiling should comply with paragraph 4.1.
b. Diffusers should be classified as one of the following.
i. TP(a) rigid – no restrictions on their extent.
ii. TP(b) – limited in their extent (see Table 4.2 and Diagram 4.2).
commissioning
NOTE:
1.Wallcoverings which conform to BS EN 15102, achieving at least class C-s3, d2 and bonded to a class A2-s3, d2 substrate, will also be acceptable.
Thermoplastic materials that do not meet the classifications in Table 4.1 can be used as described in paragraphs 4.13 to 4.17. No guidance for European fire test performance is currently available, because there is no generally accepted test and classification procedure.
Thermoplastic materials are defined in Appendix B, paragraph B11. Classifications used here are explained in paragraph B13.
In rooms and circulation spaces other than protected stairways, rooflights may be constructed of thermoplastic material if they comply with both of the following.
a. The lower surface is classified as TP(a) rigid or TP(b).
b. The size and location of the rooflights follow the limits in Table 4.2, Table 12.2 and Table 12.3.
Rooflights should meet the following classifications, according to material. No guidance for European fire test performance is currently available, because there is no generally accepted test and classification procedure.
a. Non-plastic rooflights should meet the relevant classification in Table 4.1.
b. Plastic rooflights, if the limitations in Table 4.2 and Table 12.2 are observed, should be a minimum class D-s3, d2 rating. Otherwise they should meet the relevant classification in Table 4.1.
communal or common (area facilities or entrances)
Parts of walls in rooms may be of lower performance than stated in Table 4.1, but no worse than class D-s3, d2. In any one room, the total area of lower performance wall lining should be less than an area equivalent to half of the room’s floor area, up to a maximum of 20m2 of wall lining.
communication strategy
NOTE:
1.Wallcoverings which conform to BS EN 15102, achieving at least class C-s3, d2 and bonded to a class A2-s3, d2 substrate, will also be acceptable.
compartment (fire)
In the Secretary of State’s view, requirement B2 is met by achieving a restricted spread of flame
over internal linings. The building fabric should make a limited contribution to fire growth,
including a low rate of heat release.
It is particularly important in circulation spaces, where linings may offer the main means by which
fire spreads and where rapid spread is most likely to prevent occupants from escaping.
Requirement B2 does not include guidance on the following.
a. Generation of smoke and fumes.
b. The upper surfaces of floors and stairs.
c. Furniture and fittings.
compartment wall
The surface linings of walls and ceilings should meet the classifications in Table 4.1.
compartmentation
Internal fire spread (linings)
B2.(1) To inhibit the spread of fire within the building, the internal linings shall —
(a) adequately resist the spread of flame over their surfaces; and
(b) have, if ignited, either a rate of heat release or a rate of fire growth, which is reasonable in the circumstances.
(2) In this paragraph “internal linings” means the materials or products used in lining any partition, wall, ceiling or other internal structure.
In the Secretary of State’s view, requirement B2 is met by achieving a restricted spread of flame
over internal linings. The building fabric should make a limited contribution to fire growth,
including a low rate of heat release.
It is particularly important in circulation spaces, where linings may offer the main means by which
fire spreads and where rapid spread is most likely to prevent occupants from escaping.
Requirement B2 does not include guidance on the following.
a. Generation of smoke and fumes.
b. The upper surfaces of floors and stairs.
c. Furniture and fittings.
construction
Diffusers constructed of thermoplastic material may be incorporated in ceilings to rooms and circulation spaces, but not to protected stairways, if both the following conditions are met.
a. Except for the upper surfaces of the thermoplastic panels, wall and ceiling surfaces exposed in the space above the suspended ceiling should comply with paragraph 4.1.
b. Diffusers should be classified as one of the following.
i. TP(a) rigid – no restrictions on their extent.
ii. TP(b) – limited in their extent (see Table 4.2 and Diagram 4.2).
construction control plan
NOTE:
1.Wallcoverings which conform to BS EN 15102, achieving at least class C-s3, d2 and bonded to a class A2-s3, d2 substrate, will also be acceptable.
construction programme
In rooms and circulation spaces other than protected stairways, rooflights may be constructed of thermoplastic material if they comply with both of the following.
a. The lower surface is classified as TP(a) rigid or TP(b).
b. The size and location of the rooflights follow the limits in Table 4.2, Table 12.2 and Table 12.3.
construction strategy
In rooms and circulation spaces other than protected stairways, rooflights may be constructed of thermoplastic material if they comply with both of the following.
a. The lower surface is classified as TP(a) rigid or TP(b).
b. The size and location of the rooflights follow the limits in Table 4.2, Table 12.2 and Table 12.3.
construction work
Any flexible membrane covering a structure, other than an air-supported structure, should comply with Appendix A of BS 7157.
Guidance on the use of PTFE-based materials for tension-membrane roofs and structures is given in the BRE report BR 274.
core service disciplines
Insulating core panels consist of an inner core of insulation sandwiched between, and bonded to, a membrane, such as galvanised steel or aluminium.
Where they are used internally they can present particular problems with regard to fire spread and should meet all of the following conditions.
a. Panels should be sealed to prevent exposure of the core to a fire. This includes at joints and where services penetrate the panel.
b. In high fire risk areas, such as kitchens, places of special fire hazard, or in proximity to where hot works occur, only class A1 cored panels should be used.
c. Fixing systems for all panels should be designed to take account of the potential for the panel to delaminate. For instance, where panels are used to form a suspended ceiling, the fixing should pass through the panel and support it from the lower face.
coupled assembly
For the purposes of this requirement, a wall does not include any of the following.
a. Doors and door frames.
b. Window frames and frames in which glazing is fitted.
c. Architraves, cover moulds, picture rails, skirtings and similar narrow members.
d. Fireplace surrounds, mantle shelves and fitted furniture.
For the purposes of this requirement, a ceiling does not include any of the following.
a. Trap doors and their frames.
b. The frames of windows or rooflights and frames in which glazing is fitted.
c. Architraves, cover moulds, picture rails, exposed beams and similar narrow members.
db
NOTES:
1. Upper and lower surfaces of suspended ceiling, between plastic panels, to comply with paragraph 4.1.
2. No restriction on class D-s3, d2 diffusers or rooflights in small rooms.
3. See note 4 to Table 4.2. 5m²
See Table 4.2
definitions
The following paragraphs apply to lighting diffusers forming part of a ceiling. Diffusers may be part of a luminaire or used below sources of light. The following paragraphs do not apply to diffusers of light fittings attached to the soffit of a ceiling or suspended beneath a ceiling (Diagram 4.1).
definitions (ada)
Guidance on the control of flame spread is given in the following sections.
a. Stairs and landings: Sections 2 and 3 (escape stairs) and Section 15 (firefighting shafts).
b. Exposed surfaces above fire-protecting suspended ceilings: Section 8.
c. Enclosures to above-ground drainage system pipes: Section 9.
direct distance
In rooms and circulation spaces other than protected stairways, rooflights may be constructed of thermoplastic material if they comply with both of the following.
a. The lower surface is classified as TP(a) rigid or TP(b).
b. The size and location of the rooflights follow the limits in Table 4.2, Table 12.2 and Table 12.3.
Parts of walls in rooms may be of lower performance than stated in Table 4.1, but no worse than class D-s3, d2. In any one room, the total area of lower performance wall lining should be less than an area equivalent to half of the room’s floor area, up to a maximum of 20m2 of wall lining.
direct transmission
A ceiling constructed from TP(a) flexible panels should meet the following conditions.
a. Have a maximum area of 5m2.
b. Be supported on all sides.
display lighting
The following paragraphs apply to lighting diffusers forming part of a ceiling. Diffusers may be part of a luminaire or used below sources of light. The following paragraphs do not apply to diffusers of light fittings attached to the soffit of a ceiling or suspended beneath a ceiling (Diagram 4.1).
display window
Thermoplastic material classified as a TP(a) rigid product may be used to glaze external windows to rooms, but not external windows to circulation spaces. Approved Document K includes guidance on the safety of glazing.
For the purposes of this requirement, a wall includes both of the following.
a. The internal surface of internal and external glazing (except glazing in doors).
b. Any part of a ceiling which slopes at an angle greater than 70 degrees to the horizontal.
For the purposes of this requirement, a wall does not include any of the following.
a. Doors and door frames.
b. Window frames and frames in which glazing is fitted.
c. Architraves, cover moulds, picture rails, skirtings and similar narrow members.
d. Fireplace surrounds, mantle shelves and fitted furniture.
For the purposes of this requirement, a ceiling includes all of the following.
a. Glazed surfaces.
b. Any part of a wall at 70 degrees or less to the horizontal.
c. The underside of a gallery.
d. The underside of a roof exposed to the room below.
For the purposes of this requirement, a ceiling does not include any of the following.
a. Trap doors and their frames.
b. The frames of windows or rooflights and frames in which glazing is fitted.
c. Architraves, cover moulds, picture rails, exposed beams and similar narrow members.
doorset
For the purposes of this requirement, a wall does not include any of the following.
a. Doors and door frames.
b. Window frames and frames in which glazing is fitted.
c. Architraves, cover moulds, picture rails, skirtings and similar narrow members.
d. Fireplace surrounds, mantle shelves and fitted furniture.
draught diverter
A ceiling constructed from TP(a) flexible panels should meet the following conditions.
a. Have a maximum area of 5m2.
b. Be supported on all sides.
dwelling type
A ceiling constructed from TP(a) flexible panels should meet the following conditions.
a. Have a maximum area of 5m2.
b. Be supported on all sides.
element of structure
For the purposes of this requirement, a wall does not include any of the following.
a. Doors and door frames.
b. Window frames and frames in which glazing is fitted.
c. Architraves, cover moulds, picture rails, skirtings and similar narrow members.
d. Fireplace surrounds, mantle shelves and fitted furniture.
For the purposes of this requirement, a ceiling includes all of the following.
a. Glazed surfaces.
b. Any part of a wall at 70 degrees or less to the horizontal.
c. The underside of a gallery.
d. The underside of a roof exposed to the room below.
For the purposes of this requirement, a ceiling does not include any of the following.
a. Trap doors and their frames.
b. The frames of windows or rooflights and frames in which glazing is fitted.
c. Architraves, cover moulds, picture rails, exposed beams and similar narrow members.
Any flexible membrane covering a structure, other than an air-supported structure, should comply with Appendix A of BS 7157.
emergency lighting
The following paragraphs apply to lighting diffusers forming part of a ceiling. Diffusers may be part of a luminaire or used below sources of light. The following paragraphs do not apply to diffusers of light fittings attached to the soffit of a ceiling or suspended beneath a ceiling (Diagram 4.1).
equivalent area
Parts of walls in rooms may be of lower performance than stated in Table 4.1, but no worse than class D-s3, d2. In any one room, the total area of lower performance wall lining should be less than an area equivalent to half of the room’s floor area, up to a maximum of 20m2 of wall lining.
escape lighting
The following paragraphs apply to lighting diffusers forming part of a ceiling. Diffusers may be part of a luminaire or used below sources of light. The following paragraphs do not apply to diffusers of light fittings attached to the soffit of a ceiling or suspended beneath a ceiling (Diagram 4.1).
external wall
The surface linings of walls and ceilings should meet the classifications in Table 4.1.
a. DIFFUSER FORMING PART OF CEILING
b. DIFFUSER IN FITTING BELOW AND NOT FORMING PART OF CEILING
See para 4.15
Thermoplastic material classified as a TP(a) rigid product may be used to glaze external windows to rooms, but not external windows to circulation spaces. Approved Document K includes guidance on the safety of glazing.
Diffusers constructed of thermoplastic material may be incorporated in ceilings to rooms and circulation spaces, but not to protected stairways, if both the following conditions are met.
a. Except for the upper surfaces of the thermoplastic panels, wall and ceiling surfaces exposed in the space above the suspended ceiling should comply with paragraph 4.1.
b. Diffusers should be classified as one of the following.
i. TP(a) rigid – no restrictions on their extent.
ii. TP(b) – limited in their extent (see Table 4.2 and Diagram 4.2).
For the purposes of this requirement, a wall includes both of the following.
a. The internal surface of internal and external glazing (except glazing in doors).
b. Any part of a ceiling which slopes at an angle greater than 70 degrees to the horizontal.
For the purposes of this requirement, a wall does not include any of the following.
a. Doors and door frames.
b. Window frames and frames in which glazing is fitted.
c. Architraves, cover moulds, picture rails, skirtings and similar narrow members.
d. Fireplace surrounds, mantle shelves and fitted furniture.
Parts of walls in rooms may be of lower performance than stated in Table 4.1, but no worse than class D-s3, d2. In any one room, the total area of lower performance wall lining should be less than an area equivalent to half of the room’s floor area, up to a maximum of 20m2 of wall lining.
For the purposes of this requirement, a ceiling includes all of the following.
a. Glazed surfaces.
b. Any part of a wall at 70 degrees or less to the horizontal.
c. The underside of a gallery.
d. The underside of a roof exposed to the room below.
For the purposes of this requirement, a ceiling does not include any of the following.
a. Trap doors and their frames.
b. The frames of windows or rooflights and frames in which glazing is fitted.
c. Architraves, cover moulds, picture rails, exposed beams and similar narrow members.
final certificate
In rooms and circulation spaces other than protected stairways, rooflights may be constructed of thermoplastic material if they comply with both of the following.
a. The lower surface is classified as TP(a) rigid or TP(b).
b. The size and location of the rooflights follow the limits in Table 4.2, Table 12.2 and Table 12.3.
NOTES:
1. This table does not apply to products that meet the provisions in Table 4.1.
2. Smaller rooflights and diffusers can be grouped together provided that both of the following satisfy the dimensions in Diagram 4.2 or 4.3.
a. The overall size of the group.
b. The space between one group and any others.
3. Lighting diffusers of TP(a) flexible rating should be used only in panels of a maximum of 5m2 each. See paragraph 4.17.
4. There are no limits on the use of class D-s3, d2 materials in small rooms. See Table 4.1.
5. The minimum 3m separation given in Diagram 4.2 between each 5m2 group must be maintained. Therefore, in some cases, it may not be possible to use the maximum percentage quoted.
fire and smoke damper
In the Secretary of State’s view, requirement B2 is met by achieving a restricted spread of flame
over internal linings. The building fabric should make a limited contribution to fire growth,
including a low rate of heat release.
It is particularly important in circulation spaces, where linings may offer the main means by which
fire spreads and where rapid spread is most likely to prevent occupants from escaping.
Requirement B2 does not include guidance on the following.
a. Generation of smoke and fumes.
b. The upper surfaces of floors and stairs.
c. Furniture and fittings.
fire compartment
In the Secretary of State’s view, requirement B2 is met by achieving a restricted spread of flame
over internal linings. The building fabric should make a limited contribution to fire growth,
including a low rate of heat release.
It is particularly important in circulation spaces, where linings may offer the main means by which
fire spreads and where rapid spread is most likely to prevent occupants from escaping.
Requirement B2 does not include guidance on the following.
a. Generation of smoke and fumes.
b. The upper surfaces of floors and stairs.
c. Furniture and fittings.
fire doorset
For the purposes of this requirement, a wall does not include any of the following.
a. Doors and door frames.
b. Window frames and frames in which glazing is fitted.
c. Architraves, cover moulds, picture rails, skirtings and similar narrow members.
d. Fireplace surrounds, mantle shelves and fitted furniture.
For the purposes of this requirement, a ceiling does not include any of the following.
a. Trap doors and their frames.
b. The frames of windows or rooflights and frames in which glazing is fitted.
c. Architraves, cover moulds, picture rails, exposed beams and similar narrow members.
fire risk assessment
Insulating core panels consist of an inner core of insulation sandwiched between, and bonded to, a membrane, such as galvanised steel or aluminium.
Where they are used internally they can present particular problems with regard to fire spread and should meet all of the following conditions.
a. Panels should be sealed to prevent exposure of the core to a fire. This includes at joints and where services penetrate the panel.
b. In high fire risk areas, such as kitchens, places of special fire hazard, or in proximity to where hot works occur, only class A1 cored panels should be used.
c. Fixing systems for all panels should be designed to take account of the potential for the panel to delaminate. For instance, where panels are used to form a suspended ceiling, the fixing should pass through the panel and support it from the lower face.
fire safety - volume 1: dwellings. 2019 edition - for use in england
Internal fire spread (linings)
B2.(1) To inhibit the spread of fire within the building, the internal linings shall —
(a) adequately resist the spread of flame over their surfaces; and
(b) have, if ignited, either a rate of heat release or a rate of fire growth, which is reasonable in the circumstances.
(2) In this paragraph “internal linings” means the materials or products used in lining any partition, wall, ceiling or other internal structure.
In the Secretary of State’s view, requirement B2 is met by achieving a restricted spread of flame
over internal linings. The building fabric should make a limited contribution to fire growth,
including a low rate of heat release.
It is particularly important in circulation spaces, where linings may offer the main means by which
fire spreads and where rapid spread is most likely to prevent occupants from escaping.
Requirement B2 does not include guidance on the following.
a. Generation of smoke and fumes.
b. The upper surfaces of floors and stairs.
c. Furniture and fittings.
Insulating core panels consist of an inner core of insulation sandwiched between, and bonded to, a membrane, such as galvanised steel or aluminium.
Where they are used internally they can present particular problems with regard to fire spread and should meet all of the following conditions.
a. Panels should be sealed to prevent exposure of the core to a fire. This includes at joints and where services penetrate the panel.
b. In high fire risk areas, such as kitchens, places of special fire hazard, or in proximity to where hot works occur, only class A1 cored panels should be used.
c. Fixing systems for all panels should be designed to take account of the potential for the panel to delaminate. For instance, where panels are used to form a suspended ceiling, the fixing should pass through the panel and support it from the lower face.
Any flexible membrane covering a structure, other than an air-supported structure, should comply with Appendix A of BS 7157.
fire safety - volume 2: buildings other than dwellings. 2019 edition - for use in england
Internal fire spread (linings)
B2.(1) To inhibit the spread of fire within the building, the internal linings shall —
(a) adequately resist the spread of flame over their surfaces; and
(b) have, if ignited, either a rate of heat release or a rate of fire growth, which is reasonable in the circumstances.
(2) In this paragraph “internal linings” means the materials or products used in lining any partition, wall, ceiling or other internal structure.
In the Secretary of State’s view, requirement B2 is met by achieving a restricted spread of flame
over internal linings. The building fabric should make a limited contribution to fire growth,
including a low rate of heat release.
It is particularly important in circulation spaces, where linings may offer the main means by which
fire spreads and where rapid spread is most likely to prevent occupants from escaping.
Requirement B2 does not include guidance on the following.
a. Generation of smoke and fumes.
b. The upper surfaces of floors and stairs.
c. Furniture and fittings.
Insulating core panels consist of an inner core of insulation sandwiched between, and bonded to, a membrane, such as galvanised steel or aluminium.
Where they are used internally they can present particular problems with regard to fire spread and should meet all of the following conditions.
a. Panels should be sealed to prevent exposure of the core to a fire. This includes at joints and where services penetrate the panel.
b. In high fire risk areas, such as kitchens, places of special fire hazard, or in proximity to where hot works occur, only class A1 cored panels should be used.
c. Fixing systems for all panels should be designed to take account of the potential for the panel to delaminate. For instance, where panels are used to form a suspended ceiling, the fixing should pass through the panel and support it from the lower face.
Guidance on the control of flame spread is given in the following sections.
a. Stairs and landings: Sections 2 and 3 (escape stairs) and Section 15 (firefighting shafts).
b. Exposed surfaces above fire-protecting suspended ceilings: Section 8.
c. Enclosures to above-ground drainage system pipes: Section 9.
Any flexible membrane covering a structure, other than an air-supported structure, should comply with Appendix A of BS 7157.
fire-stop (Fire-stopping)
In the Secretary of State’s view, requirement B2 is met by achieving a restricted spread of flame
over internal linings. The building fabric should make a limited contribution to fire growth,
including a low rate of heat release.
It is particularly important in circulation spaces, where linings may offer the main means by which
fire spreads and where rapid spread is most likely to prevent occupants from escaping.
Requirement B2 does not include guidance on the following.
a. Generation of smoke and fumes.
b. The upper surfaces of floors and stairs.
c. Furniture and fittings.
firefighting lift
Guidance on the control of flame spread is given in the following sections.
a. Stairs and landings: Sections 2 and 3 (escape stairs) and Section 15 (firefighting shafts).
b. Exposed surfaces above fire-protecting suspended ceilings: Section 8.
c. Enclosures to above-ground drainage system pipes: Section 9.
Guidance on the control of flame spread is given in the following sections.
a. Stairs and landings: Sections 2 and 3 (escape stairs) and Section 15 (firefighting shafts).
b. Exposed surfaces above fire-protecting suspended ceilings: Section 8.
c. Enclosures to above-ground drainage system pipes: Section 9.
firefighting shaft
Guidance on the control of flame spread is given in the following sections.
a. Stairs and landings: Sections 2 and 3 (escape stairs) and Section 15 (firefighting shafts).
b. Exposed surfaces above fire-protecting suspended ceilings: Section 8.
c. Enclosures to above-ground drainage system pipes: Section 9.
flat
a. DIFFUSER FORMING PART OF CEILING
b. DIFFUSER IN FITTING BELOW AND NOT FORMING PART OF CEILING
See para 4.15
flueless appliance
NOTES:
1. This table does not apply to products that meet the provisions in Table 4.1.
2. Smaller rooflights and diffusers can be grouped together provided that both of the following satisfy the dimensions in Diagram 4.2 or 4.3.
a. The overall size of the group.
b. The space between one group and any others.
3. Lighting diffusers of TP(a) flexible rating should be used only in panels of a maximum of 5m2 each. See paragraph 4.17.
4. There are no limits on the use of class D-s3, d2 materials in small rooms. See Table 4.1.
5. The minimum 3m separation given in Diagram 4.2 between each 5m2 group must be maintained. Therefore, in some cases, it may not be possible to use the maximum percentage quoted.
following edge (of door)
In rooms and circulation spaces other than protected stairways, rooflights may be constructed of thermoplastic material if they comply with both of the following.
a. The lower surface is classified as TP(a) rigid or TP(b).
b. The size and location of the rooflights follow the limits in Table 4.2, Table 12.2 and Table 12.3.
Diffusers constructed of thermoplastic material may be incorporated in ceilings to rooms and circulation spaces, but not to protected stairways, if both the following conditions are met.
a. Except for the upper surfaces of the thermoplastic panels, wall and ceiling surfaces exposed in the space above the suspended ceiling should comply with paragraph 4.1.
b. Diffusers should be classified as one of the following.
i. TP(a) rigid – no restrictions on their extent.
ii. TP(b) – limited in their extent (see Table 4.2 and Diagram 4.2).
A ceiling constructed from TP(a) flexible panels should meet the following conditions.
a. Have a maximum area of 5m2.
b. Be supported on all sides.
For the purposes of this requirement, a wall includes both of the following.
a. The internal surface of internal and external glazing (except glazing in doors).
b. Any part of a ceiling which slopes at an angle greater than 70 degrees to the horizontal.
For the purposes of this requirement, a wall does not include any of the following.
a. Doors and door frames.
b. Window frames and frames in which glazing is fitted.
c. Architraves, cover moulds, picture rails, skirtings and similar narrow members.
d. Fireplace surrounds, mantle shelves and fitted furniture.
For the purposes of this requirement, a ceiling does not include any of the following.
a. Trap doors and their frames.
b. The frames of windows or rooflights and frames in which glazing is fitted.
c. Architraves, cover moulds, picture rails, exposed beams and similar narrow members.
framed wall
For the purposes of this requirement, a wall does not include any of the following.
a. Doors and door frames.
b. Window frames and frames in which glazing is fitted.
c. Architraves, cover moulds, picture rails, skirtings and similar narrow members.
d. Fireplace surrounds, mantle shelves and fitted furniture.
For the purposes of this requirement, a ceiling does not include any of the following.
a. Trap doors and their frames.
b. The frames of windows or rooflights and frames in which glazing is fitted.
c. Architraves, cover moulds, picture rails, exposed beams and similar narrow members.
free area
A ceiling constructed from TP(a) flexible panels should meet the following conditions.
a. Have a maximum area of 5m2.
b. Be supported on all sides.
Parts of walls in rooms may be of lower performance than stated in Table 4.1, but no worse than class D-s3, d2. In any one room, the total area of lower performance wall lining should be less than an area equivalent to half of the room’s floor area, up to a maximum of 20m2 of wall lining.
frequency band
NOTES:
1. Upper and lower surfaces of suspended ceiling, between plastic panels, to comply with paragraph 4.1.
2. No restriction on class D-s3, d2 diffusers or rooflights in small rooms.
3. See note 4 to Table 4.2. 5m²
See Table 4.2
going
NOTES:
1. Upper and lower surfaces of suspended ceiling, between plastic panels, to comply with paragraph 4.1.
2. No restriction on class D-s3, d2 diffusers or rooflights in small rooms.
3. See note 4 to Table 4.2. 5m²
See Table 4.2
gross internal volume
Internal fire spread (linings)
B2.(1) To inhibit the spread of fire within the building, the internal linings shall —
(a) adequately resist the spread of flame over their surfaces; and
(b) have, if ignited, either a rate of heat release or a rate of fire growth, which is reasonable in the circumstances.
(2) In this paragraph “internal linings” means the materials or products used in lining any partition, wall, ceiling or other internal structure.
For the purposes of this requirement, a wall includes both of the following.
a. The internal surface of internal and external glazing (except glazing in doors).
b. Any part of a ceiling which slopes at an angle greater than 70 degrees to the horizontal.
groundwater
In rooms and circulation spaces other than protected stairways, rooflights may be constructed of thermoplastic material if they comply with both of the following.
a. The lower surface is classified as TP(a) rigid or TP(b).
b. The size and location of the rooflights follow the limits in Table 4.2, Table 12.2 and Table 12.3.
NOTES:
1. Upper and lower surfaces of suspended ceiling, between plastic panels, to comply with paragraph 4.1.
2. No restriction on class D-s3, d2 diffusers or rooflights in small rooms.
3. See note 4 to Table 4.2. 5m²
See Table 4.2
Materials within this zone – at plane of ceiling – should comply with Table 4.1
Rooflights
See Table 4.2
Rooflights should meet the following classifications, according to material. No guidance for European fire test performance is currently available, because there is no generally accepted test and classification procedure.
a. Non-plastic rooflights should meet the relevant classification in Table 4.1.
b. Plastic rooflights, if the limitations in Table 4.2 and Table 12.2 are observed, should be a minimum class D-s3, d2 rating. Otherwise they should meet the relevant classification in Table 4.1.
habitable room
Thermoplastic material classified as a TP(a) rigid product may be used to glaze external windows to rooms, but not external windows to circulation spaces. Approved Document K includes guidance on the safety of glazing.
high-speed electronic communications network
NOTE:
1.Wallcoverings which conform to BS EN 15102, achieving at least class C-s3, d2 and bonded to a class A2-s3, d2 substrate, will also be acceptable.
independent ceiling
a. DIFFUSER FORMING PART OF CEILING
b. DIFFUSER IN FITTING BELOW AND NOT FORMING PART OF CEILING
See para 4.15
NOTES:
1. Upper and lower surfaces of suspended ceiling, between plastic panels, to comply with paragraph 4.1.
2. No restriction on class D-s3, d2 diffusers or rooflights in small rooms.
3. See note 4 to Table 4.2. 5m²
See Table 4.2
Materials within this zone – at plane of ceiling – should comply with Table 4.1
Rooflights
See Table 4.2
light reflectance value (lrv)
The following paragraphs apply to lighting diffusers forming part of a ceiling. Diffusers may be part of a luminaire or used below sources of light. The following paragraphs do not apply to diffusers of light fittings attached to the soffit of a ceiling or suspended beneath a ceiling (Diagram 4.1).
The following paragraphs apply to lighting diffusers forming part of a ceiling. Diffusers may be part of a luminaire or used below sources of light. The following paragraphs do not apply to diffusers of light fittings attached to the soffit of a ceiling or suspended beneath a ceiling (Diagram 4.1).
live–work units
NOTES:
1. This table does not apply to products that meet the provisions in Table 4.1.
2. Smaller rooflights and diffusers can be grouped together provided that both of the following satisfy the dimensions in Diagram 4.2 or 4.3.
a. The overall size of the group.
b. The space between one group and any others.
3. Lighting diffusers of TP(a) flexible rating should be used only in panels of a maximum of 5m2 each. See paragraph 4.17.
4. There are no limits on the use of class D-s3, d2 materials in small rooms. See Table 4.1.
5. The minimum 3m separation given in Diagram 4.2 between each 5m2 group must be maintained. Therefore, in some cases, it may not be possible to use the maximum percentage quoted.
material alteration
Internal fire spread (linings)
B2.(1) To inhibit the spread of fire within the building, the internal linings shall —
(a) adequately resist the spread of flame over their surfaces; and
(b) have, if ignited, either a rate of heat release or a rate of fire growth, which is reasonable in the circumstances.
(2) In this paragraph “internal linings” means the materials or products used in lining any partition, wall, ceiling or other internal structure.
material changes of use
Thermoplastic materials that do not meet the classifications in Table 4.1 can be used as described in paragraphs 4.13 to 4.17. No guidance for European fire test performance is currently available, because there is no generally accepted test and classification procedure.
Thermoplastic materials are defined in Appendix B, paragraph B11. Classifications used here are explained in paragraph B13.
Thermoplastic materials that do not meet the classifications in Table 4.1 can be used as described in paragraphs 4.13 to 4.17. No guidance for European fire test performance is currently available, because there is no generally accepted test and classification procedure.
Thermoplastic materials are defined in Appendix B, paragraph B11. Classifications used here are explained in paragraph B13.
Guidance on the use of PTFE-based materials for tension-membrane roofs and structures is given in the BRE report BR 274.
Guidance on the use of PTFE-based materials for tension-membrane roofs and structures is given in the BRE report BR 274.
materials
Materials within this zone – at plane of ceiling – should comply with Table 4.1
Rooflights
See Table 4.2
means of escape
Any flexible membrane covering a structure, other than an air-supported structure, should comply with Appendix A of BS 7157.
measurement
Thermoplastic materials that do not meet the classifications in Table 4.1 can be used as described in paragraphs 4.13 to 4.17. No guidance for European fire test performance is currently available, because there is no generally accepted test and classification procedure.
Thermoplastic materials are defined in Appendix B, paragraph B11. Classifications used here are explained in paragraph B13.
non-combustible material
Thermoplastic materials that do not meet the classifications in Table 4.1 can be used as described in paragraphs 4.13 to 4.17. No guidance for European fire test performance is currently available, because there is no generally accepted test and classification procedure.
Thermoplastic materials are defined in Appendix B, paragraph B11. Classifications used here are explained in paragraph B13.
Thermoplastic material classified as a TP(a) rigid product may be used to glaze external windows to rooms, but not external windows to circulation spaces. Approved Document K includes guidance on the safety of glazing.
Materials within this zone – at plane of ceiling – should comply with Table 4.1
Rooflights
See Table 4.2
Rooflights should meet the following classifications, according to material. No guidance for European fire test performance is currently available, because there is no generally accepted test and classification procedure.
a. Non-plastic rooflights should meet the relevant classification in Table 4.1.
b. Plastic rooflights, if the limitations in Table 4.2 and Table 12.2 are observed, should be a minimum class D-s3, d2 rating. Otherwise they should meet the relevant classification in Table 4.1.
Guidance on the use of PTFE-based materials for tension-membrane roofs and structures is given in the BRE report BR 274.
outcomes-based system
Guidance on the use of PTFE-based materials for tension-membrane roofs and structures is given in the BRE report BR 274.
passive stack ventilation (psv)
For the purposes of this requirement, a ceiling includes all of the following.
a. Glazed surfaces.
b. Any part of a wall at 70 degrees or less to the horizontal.
c. The underside of a gallery.
d. The underside of a roof exposed to the room below.
Guidance on the use of PTFE-based materials for tension-membrane roofs and structures is given in the BRE report BR 274.
pier
NOTE:
1.Wallcoverings which conform to BS EN 15102, achieving at least class C-s3, d2 and bonded to a class A2-s3, d2 substrate, will also be acceptable.
a. DIFFUSER FORMING PART OF CEILING
b. DIFFUSER IN FITTING BELOW AND NOT FORMING PART OF CEILING
See para 4.15
pipe
Guidance on the control of flame spread is given in the following sections.
a. Stairs and landings: Sections 2 and 3 (escape stairs) and Section 15 (firefighting shafts).
b. Exposed surfaces above fire-protecting suspended ceilings: Section 8.
c. Enclosures to above-ground drainage system pipes: Section 9.
pitch
The surface linings of walls and ceilings should meet the classifications in Table 4.1.
For the purposes of this requirement, a wall includes both of the following.
a. The internal surface of internal and external glazing (except glazing in doors).
b. Any part of a ceiling which slopes at an angle greater than 70 degrees to the horizontal.
pitch line
Internal fire spread (linings)
B2.(1) To inhibit the spread of fire within the building, the internal linings shall —
(a) adequately resist the spread of flame over their surfaces; and
(b) have, if ignited, either a rate of heat release or a rate of fire growth, which is reasonable in the circumstances.
(2) In this paragraph “internal linings” means the materials or products used in lining any partition, wall, ceiling or other internal structure.
The surface linings of walls and ceilings should meet the classifications in Table 4.1.
platform floor
Any flexible membrane covering a structure, other than an air-supported structure, should comply with Appendix A of BS 7157.
pre-construction information
NOTE:
1.Wallcoverings which conform to BS EN 15102, achieving at least class C-s3, d2 and bonded to a class A2-s3, d2 substrate, will also be acceptable.
principal works
The surface linings of walls and ceilings should meet the classifications in Table 4.1.
Insulating core panels consist of an inner core of insulation sandwiched between, and bonded to, a membrane, such as galvanised steel or aluminium.
Where they are used internally they can present particular problems with regard to fire spread and should meet all of the following conditions.
a. Panels should be sealed to prevent exposure of the core to a fire. This includes at joints and where services penetrate the panel.
b. In high fire risk areas, such as kitchens, places of special fire hazard, or in proximity to where hot works occur, only class A1 cored panels should be used.
c. Fixing systems for all panels should be designed to take account of the potential for the panel to delaminate. For instance, where panels are used to form a suspended ceiling, the fixing should pass through the panel and support it from the lower face.
Diffusers constructed of thermoplastic material may be incorporated in ceilings to rooms and circulation spaces, but not to protected stairways, if both the following conditions are met.
a. Except for the upper surfaces of the thermoplastic panels, wall and ceiling surfaces exposed in the space above the suspended ceiling should comply with paragraph 4.1.
b. Diffusers should be classified as one of the following.
i. TP(a) rigid – no restrictions on their extent.
ii. TP(b) – limited in their extent (see Table 4.2 and Diagram 4.2).
NOTES:
1. This table does not apply to products that meet the provisions in Table 4.1.
2. Smaller rooflights and diffusers can be grouped together provided that both of the following satisfy the dimensions in Diagram 4.2 or 4.3.
a. The overall size of the group.
b. The space between one group and any others.
3. Lighting diffusers of TP(a) flexible rating should be used only in panels of a maximum of 5m2 each. See paragraph 4.17.
4. There are no limits on the use of class D-s3, d2 materials in small rooms. See Table 4.1.
5. The minimum 3m separation given in Diagram 4.2 between each 5m2 group must be maintained. Therefore, in some cases, it may not be possible to use the maximum percentage quoted.
For the purposes of this requirement, a ceiling includes all of the following.
a. Glazed surfaces.
b. Any part of a wall at 70 degrees or less to the horizontal.
c. The underside of a gallery.
d. The underside of a roof exposed to the room below.
Rooflights should meet the following classifications, according to material. No guidance for European fire test performance is currently available, because there is no generally accepted test and classification procedure.
a. Non-plastic rooflights should meet the relevant classification in Table 4.1.
b. Plastic rooflights, if the limitations in Table 4.2 and Table 12.2 are observed, should be a minimum class D-s3, d2 rating. Otherwise they should meet the relevant classification in Table 4.1.
Guidance on the use of PTFE-based materials for tension-membrane roofs and structures is given in the BRE report BR 274.
project roles table
In rooms and circulation spaces other than protected stairways, rooflights may be constructed of thermoplastic material if they comply with both of the following.
a. The lower surface is classified as TP(a) rigid or TP(b).
b. The size and location of the rooflights follow the limits in Table 4.2, Table 12.2 and Table 12.3.
Materials within this zone – at plane of ceiling – should comply with Table 4.1
Rooflights
See Table 4.2
Rooflights should meet the following classifications, according to material. No guidance for European fire test performance is currently available, because there is no generally accepted test and classification procedure.
a. Non-plastic rooflights should meet the relevant classification in Table 4.1.
b. Plastic rooflights, if the limitations in Table 4.2 and Table 12.2 are observed, should be a minimum class D-s3, d2 rating. Otherwise they should meet the relevant classification in Table 4.1.
proven
Thermoplastic materials that do not meet the classifications in Table 4.1 can be used as described in paragraphs 4.13 to 4.17. No guidance for European fire test performance is currently available, because there is no generally accepted test and classification procedure.
Thermoplastic materials are defined in Appendix B, paragraph B11. Classifications used here are explained in paragraph B13.
Rooflights should meet the following classifications, according to material. No guidance for European fire test performance is currently available, because there is no generally accepted test and classification procedure.
a. Non-plastic rooflights should meet the relevant classification in Table 4.1.
b. Plastic rooflights, if the limitations in Table 4.2 and Table 12.2 are observed, should be a minimum class D-s3, d2 rating. Otherwise they should meet the relevant classification in Table 4.1.
purpose group
The surface linings of walls and ceilings should meet the classifications in Table 4.1.
Thermoplastic materials that do not meet the classifications in Table 4.1 can be used as described in paragraphs 4.13 to 4.17. No guidance for European fire test performance is currently available, because there is no generally accepted test and classification procedure.
Thermoplastic materials are defined in Appendix B, paragraph B11. Classifications used here are explained in paragraph B13.
In rooms and circulation spaces other than protected stairways, rooflights may be constructed of thermoplastic material if they comply with both of the following.
a. The lower surface is classified as TP(a) rigid or TP(b).
b. The size and location of the rooflights follow the limits in Table 4.2, Table 12.2 and Table 12.3.
NOTES:
1. Upper and lower surfaces of suspended ceiling, between plastic panels, to comply with paragraph 4.1.
2. No restriction on class D-s3, d2 diffusers or rooflights in small rooms.
3. See note 4 to Table 4.2. 5m²
See Table 4.2
NOTES:
1. This table does not apply to products that meet the provisions in Table 4.1.
2. Smaller rooflights and diffusers can be grouped together provided that both of the following satisfy the dimensions in Diagram 4.2 or 4.3.
a. The overall size of the group.
b. The space between one group and any others.
3. Lighting diffusers of TP(a) flexible rating should be used only in panels of a maximum of 5m2 each. See paragraph 4.17.
4. There are no limits on the use of class D-s3, d2 materials in small rooms. See Table 4.1.
5. The minimum 3m separation given in Diagram 4.2 between each 5m2 group must be maintained. Therefore, in some cases, it may not be possible to use the maximum percentage quoted.
Materials within this zone – at plane of ceiling – should comply with Table 4.1
Rooflights
See Table 4.2
Rooflights should meet the following classifications, according to material. No guidance for European fire test performance is currently available, because there is no generally accepted test and classification procedure.
a. Non-plastic rooflights should meet the relevant classification in Table 4.1.
b. Plastic rooflights, if the limitations in Table 4.2 and Table 12.2 are observed, should be a minimum class D-s3, d2 rating. Otherwise they should meet the relevant classification in Table 4.1.
regulation 7 - materials and workmanship
Thermoplastic materials that do not meet the classifications in Table 4.1 can be used as described in paragraphs 4.13 to 4.17. No guidance for European fire test performance is currently available, because there is no generally accepted test and classification procedure.
Thermoplastic materials are defined in Appendix B, paragraph B11. Classifications used here are explained in paragraph B13.
relevant boundary
A ceiling constructed from TP(a) flexible panels should meet the following conditions.
a. Have a maximum area of 5m2.
b. Be supported on all sides.
rise
NOTES:
1. Upper and lower surfaces of suspended ceiling, between plastic panels, to comply with paragraph 4.1.
2. No restriction on class D-s3, d2 diffusers or rooflights in small rooms.
3. See note 4 to Table 4.2. 5m²
See Table 4.2
NOTES:
1. This table does not apply to products that meet the provisions in Table 4.1.
2. Smaller rooflights and diffusers can be grouped together provided that both of the following satisfy the dimensions in Diagram 4.2 or 4.3.
a. The overall size of the group.
b. The space between one group and any others.
3. Lighting diffusers of TP(a) flexible rating should be used only in panels of a maximum of 5m2 each. See paragraph 4.17.
4. There are no limits on the use of class D-s3, d2 materials in small rooms. See Table 4.1.
5. The minimum 3m separation given in Diagram 4.2 between each 5m2 group must be maintained. Therefore, in some cases, it may not be possible to use the maximum percentage quoted.
roof
For the purposes of this requirement, a wall includes both of the following.
a. The internal surface of internal and external glazing (except glazing in doors).
b. Any part of a ceiling which slopes at an angle greater than 70 degrees to the horizontal.
For the purposes of this requirement, a ceiling includes all of the following.
a. Glazed surfaces.
b. Any part of a wall at 70 degrees or less to the horizontal.
c. The underside of a gallery.
d. The underside of a roof exposed to the room below.
rooflight
The following paragraphs apply to lighting diffusers forming part of a ceiling. Diffusers may be part of a luminaire or used below sources of light. The following paragraphs do not apply to diffusers of light fittings attached to the soffit of a ceiling or suspended beneath a ceiling (Diagram 4.1).
Rooflights should meet the following classifications, according to material. No guidance for European fire test performance is currently available, because there is no generally accepted test and classification procedure.
a. Non-plastic rooflights should meet the relevant classification in Table 4.1.
b. Plastic rooflights, if the limitations in Table 4.2 and Table 12.2 are observed, should be a minimum class D-s3, d2 rating. Otherwise they should meet the relevant classification in Table 4.1.
room
a. DIFFUSER FORMING PART OF CEILING
b. DIFFUSER IN FITTING BELOW AND NOT FORMING PART OF CEILING
See para 4.15
Thermoplastic material classified as a TP(a) rigid product may be used to glaze external windows to rooms, but not external windows to circulation spaces. Approved Document K includes guidance on the safety of glazing.
Diffusers constructed of thermoplastic material may be incorporated in ceilings to rooms and circulation spaces, but not to protected stairways, if both the following conditions are met.
a. Except for the upper surfaces of the thermoplastic panels, wall and ceiling surfaces exposed in the space above the suspended ceiling should comply with paragraph 4.1.
b. Diffusers should be classified as one of the following.
i. TP(a) rigid – no restrictions on their extent.
ii. TP(b) – limited in their extent (see Table 4.2 and Diagram 4.2).
NOTES:
1. This table does not apply to products that meet the provisions in Table 4.1.
2. Smaller rooflights and diffusers can be grouped together provided that both of the following satisfy the dimensions in Diagram 4.2 or 4.3.
a. The overall size of the group.
b. The space between one group and any others.
3. Lighting diffusers of TP(a) flexible rating should be used only in panels of a maximum of 5m2 each. See paragraph 4.17.
4. There are no limits on the use of class D-s3, d2 materials in small rooms. See Table 4.1.
5. The minimum 3m separation given in Diagram 4.2 between each 5m2 group must be maintained. Therefore, in some cases, it may not be possible to use the maximum percentage quoted.
section
Guidance on the control of flame spread is given in the following sections.
a. Stairs and landings: Sections 2 and 3 (escape stairs) and Section 15 (firefighting shafts).
b. Exposed surfaces above fire-protecting suspended ceilings: Section 8.
c. Enclosures to above-ground drainage system pipes: Section 9.
secure window
Thermoplastic material classified as a TP(a) rigid product may be used to glaze external windows to rooms, but not external windows to circulation spaces. Approved Document K includes guidance on the safety of glazing.
self-closing device
For the purposes of this requirement, a wall does not include any of the following.
a. Doors and door frames.
b. Window frames and frames in which glazing is fitted.
c. Architraves, cover moulds, picture rails, skirtings and similar narrow members.
d. Fireplace surrounds, mantle shelves and fitted furniture.
For the purposes of this requirement, a ceiling does not include any of the following.
a. Trap doors and their frames.
b. The frames of windows or rooflights and frames in which glazing is fitted.
c. Architraves, cover moulds, picture rails, exposed beams and similar narrow members.
separated part
a. DIFFUSER FORMING PART OF CEILING
b. DIFFUSER IN FITTING BELOW AND NOT FORMING PART OF CEILING
See para 4.15
a. DIFFUSER FORMING PART OF CEILING
b. DIFFUSER IN FITTING BELOW AND NOT FORMING PART OF CEILING
See para 4.15
separating wall
The surface linings of walls and ceilings should meet the classifications in Table 4.1.
should
Insulating core panels consist of an inner core of insulation sandwiched between, and bonded to, a membrane, such as galvanised steel or aluminium.
Where they are used internally they can present particular problems with regard to fire spread and should meet all of the following conditions.
a. Panels should be sealed to prevent exposure of the core to a fire. This includes at joints and where services penetrate the panel.
b. In high fire risk areas, such as kitchens, places of special fire hazard, or in proximity to where hot works occur, only class A1 cored panels should be used.
c. Fixing systems for all panels should be designed to take account of the potential for the panel to delaminate. For instance, where panels are used to form a suspended ceiling, the fixing should pass through the panel and support it from the lower face.
Materials within this zone – at plane of ceiling – should comply with Table 4.1
Rooflights
See Table 4.2
Rooflights should meet the following classifications, according to material. No guidance for European fire test performance is currently available, because there is no generally accepted test and classification procedure.
a. Non-plastic rooflights should meet the relevant classification in Table 4.1.
b. Plastic rooflights, if the limitations in Table 4.2 and Table 12.2 are observed, should be a minimum class D-s3, d2 rating. Otherwise they should meet the relevant classification in Table 4.1.
Any flexible membrane covering a structure, other than an air-supported structure, should comply with Appendix A of BS 7157.
site rules
Any flexible membrane covering a structure, other than an air-supported structure, should comply with Appendix A of BS 7157.
specialist process lighting
The following paragraphs apply to lighting diffusers forming part of a ceiling. Diffusers may be part of a luminaire or used below sources of light. The following paragraphs do not apply to diffusers of light fittings attached to the soffit of a ceiling or suspended beneath a ceiling (Diagram 4.1).
storey
NOTES:
1. This table does not apply to products that meet the provisions in Table 4.1.
2. Smaller rooflights and diffusers can be grouped together provided that both of the following satisfy the dimensions in Diagram 4.2 or 4.3.
a. The overall size of the group.
b. The space between one group and any others.
3. Lighting diffusers of TP(a) flexible rating should be used only in panels of a maximum of 5m2 each. See paragraph 4.17.
4. There are no limits on the use of class D-s3, d2 materials in small rooms. See Table 4.1.
5. The minimum 3m separation given in Diagram 4.2 between each 5m2 group must be maintained. Therefore, in some cases, it may not be possible to use the maximum percentage quoted.
For the purposes of this requirement, a ceiling includes all of the following.
a. Glazed surfaces.
b. Any part of a wall at 70 degrees or less to the horizontal.
c. The underside of a gallery.
d. The underside of a roof exposed to the room below.
structure 2004 edition incorporating 20042010 and 2013 amendments
Guidance on the use of PTFE-based materials for tension-membrane roofs and structures is given in the BRE report BR 274.
suitable tread nosings
NOTE:
1.Wallcoverings which conform to BS EN 15102, achieving at least class C-s3, d2 and bonded to a class A2-s3, d2 substrate, will also be acceptable.
suspended ceiling
The surface linings of walls and ceilings should meet the classifications in Table 4.1.
a. DIFFUSER FORMING PART OF CEILING
b. DIFFUSER IN FITTING BELOW AND NOT FORMING PART OF CEILING
See para 4.15
Guidance on the control of flame spread is given in the following sections.
a. Stairs and landings: Sections 2 and 3 (escape stairs) and Section 15 (firefighting shafts).
b. Exposed surfaces above fire-protecting suspended ceilings: Section 8.
c. Enclosures to above-ground drainage system pipes: Section 9.
The following paragraphs apply to lighting diffusers forming part of a ceiling. Diffusers may be part of a luminaire or used below sources of light. The following paragraphs do not apply to diffusers of light fittings attached to the soffit of a ceiling or suspended beneath a ceiling (Diagram 4.1).
Diffusers constructed of thermoplastic material may be incorporated in ceilings to rooms and circulation spaces, but not to protected stairways, if both the following conditions are met.
a. Except for the upper surfaces of the thermoplastic panels, wall and ceiling surfaces exposed in the space above the suspended ceiling should comply with paragraph 4.1.
b. Diffusers should be classified as one of the following.
i. TP(a) rigid – no restrictions on their extent.
ii. TP(b) – limited in their extent (see Table 4.2 and Diagram 4.2).
A ceiling constructed from TP(a) flexible panels should meet the following conditions.
a. Have a maximum area of 5m2.
b. Be supported on all sides.
NOTES:
1. Upper and lower surfaces of suspended ceiling, between plastic panels, to comply with paragraph 4.1.
2. No restriction on class D-s3, d2 diffusers or rooflights in small rooms.
3. See note 4 to Table 4.2. 5m²
See Table 4.2
Materials within this zone – at plane of ceiling – should comply with Table 4.1
Rooflights
See Table 4.2
sustainability strategy
NOTE:
1.Wallcoverings which conform to BS EN 15102, achieving at least class C-s3, d2 and bonded to a class A2-s3, d2 substrate, will also be acceptable.
thermoplastic material
Thermoplastic materials that do not meet the classifications in Table 4.1 can be used as described in paragraphs 4.13 to 4.17. No guidance for European fire test performance is currently available, because there is no generally accepted test and classification procedure.
Thermoplastic materials are defined in Appendix B, paragraph B11. Classifications used here are explained in paragraph B13.
Thermoplastic material classified as a TP(a) rigid product may be used to glaze external windows to rooms, but not external windows to circulation spaces. Approved Document K includes guidance on the safety of glazing.
total useful floor area
Insulating core panels consist of an inner core of insulation sandwiched between, and bonded to, a membrane, such as galvanised steel or aluminium.
Where they are used internally they can present particular problems with regard to fire spread and should meet all of the following conditions.
a. Panels should be sealed to prevent exposure of the core to a fire. This includes at joints and where services penetrate the panel.
b. In high fire risk areas, such as kitchens, places of special fire hazard, or in proximity to where hot works occur, only class A1 cored panels should be used.
c. Fixing systems for all panels should be designed to take account of the potential for the panel to delaminate. For instance, where panels are used to form a suspended ceiling, the fixing should pass through the panel and support it from the lower face.
A ceiling constructed from TP(a) flexible panels should meet the following conditions.
a. Have a maximum area of 5m2.
b. Be supported on all sides.
A ceiling constructed from TP(a) flexible panels should meet the following conditions.
a. Have a maximum area of 5m2.
b. Be supported on all sides.
Parts of walls in rooms may be of lower performance than stated in Table 4.1, but no worse than class D-s3, d2. In any one room, the total area of lower performance wall lining should be less than an area equivalent to half of the room’s floor area, up to a maximum of 20m2 of wall lining.
Parts of walls in rooms may be of lower performance than stated in Table 4.1, but no worse than class D-s3, d2. In any one room, the total area of lower performance wall lining should be less than an area equivalent to half of the room’s floor area, up to a maximum of 20m2 of wall lining.
unprotected area
NOTE:
1.Wallcoverings which conform to BS EN 15102, achieving at least class C-s3, d2 and bonded to a class A2-s3, d2 substrate, will also be acceptable.
Thermoplastic material classified as a TP(a) rigid product may be used to glaze external windows to rooms, but not external windows to circulation spaces. Approved Document K includes guidance on the safety of glazing.
For the purposes of this requirement, a wall includes both of the following.
a. The internal surface of internal and external glazing (except glazing in doors).
b. Any part of a ceiling which slopes at an angle greater than 70 degrees to the horizontal.
NOTES:
1. This table does not apply to products that meet the provisions in Table 4.1.
2. Smaller rooflights and diffusers can be grouped together provided that both of the following satisfy the dimensions in Diagram 4.2 or 4.3.
a. The overall size of the group.
b. The space between one group and any others.
3. Lighting diffusers of TP(a) flexible rating should be used only in panels of a maximum of 5m2 each. See paragraph 4.17.
4. There are no limits on the use of class D-s3, d2 materials in small rooms. See Table 4.1.
5. The minimum 3m separation given in Diagram 4.2 between each 5m2 group must be maintained. Therefore, in some cases, it may not be possible to use the maximum percentage quoted.
For the purposes of this requirement, a wall does not include any of the following.
a. Doors and door frames.
b. Window frames and frames in which glazing is fitted.
c. Architraves, cover moulds, picture rails, skirtings and similar narrow members.
d. Fireplace surrounds, mantle shelves and fitted furniture.
Parts of walls in rooms may be of lower performance than stated in Table 4.1, but no worse than class D-s3, d2. In any one room, the total area of lower performance wall lining should be less than an area equivalent to half of the room’s floor area, up to a maximum of 20m2 of wall lining.
For the purposes of this requirement, a ceiling includes all of the following.
a. Glazed surfaces.
b. Any part of a wall at 70 degrees or less to the horizontal.
c. The underside of a gallery.
d. The underside of a roof exposed to the room below.
For the purposes of this requirement, a ceiling does not include any of the following.
a. Trap doors and their frames.
b. The frames of windows or rooflights and frames in which glazing is fitted.
c. Architraves, cover moulds, picture rails, exposed beams and similar narrow members.
Rooflights should meet the following classifications, according to material. No guidance for European fire test performance is currently available, because there is no generally accepted test and classification procedure.
a. Non-plastic rooflights should meet the relevant classification in Table 4.1.
b. Plastic rooflights, if the limitations in Table 4.2 and Table 12.2 are observed, should be a minimum class D-s3, d2 rating. Otherwise they should meet the relevant classification in Table 4.1.
wall
For the purposes of this requirement, a wall includes both of the following.
a. The internal surface of internal and external glazing (except glazing in doors).
b. Any part of a ceiling which slopes at an angle greater than 70 degrees to the horizontal.
window
Thermoplastic material classified as a TP(a) rigid product may be used to glaze external windows to rooms, but not external windows to circulation spaces. Approved Document K includes guidance on the safety of glazing.
Materials within this zone – at plane of ceiling – should comply with Table 4.1
Rooflights
See Table 4.2
For the purposes of this requirement, a ceiling does not include any of the following.
a. Trap doors and their frames.
b. The frames of windows or rooflights and frames in which glazing is fitted.
c. Architraves, cover moulds, picture rails, exposed beams and similar narrow members.