access
See para 2.5
Fire resisting construction minimum REI 30
Fd Fire doorset minimum E 20
Access openings to refuse storage chambers should not be sited in the following areas.
a. Next to escape routes or final exits.
b. Near the windows of flats.
Access to an external escape stair may be via a flat roof, provided the flat roof meets the requirements of paragraph 3.30.
The construction separating two adjacent protected stairways (or exit passageways leading to different final exits) should be imperforate.
access room
Where new habitable rooms are provided, a fire detection and alarm system should be installed
where either of the following applies.
a. The room is provided above or below the ground storey.
b. The room is provided at the ground storey, without a final exit.
Smoke alarms should be provided in the circulation spaces of the dwelling in accordance with
paragraphs 1.1 to 1.4.
NOTE: This does not apply where inner rooms are provided (see paragraph 2.11 for inner room
requirements).
An inner room is permitted when it is one of the following.
a. A kitchen.
b. A laundry or utility room.
c. A dressing room.
d. A bathroom, WC or shower room.
e. Any room on a storey that is a maximum of 4.5m above ground level which is provided with an emergency escape window as described in paragraph 2.10.
f. A gallery that complies with paragraph 2.15.
A room accessed only via an inner room (an inner inner room) is acceptable when all of the following apply.
a. It complies with paragraph 2.11.
b. The access rooms each have a smoke alarm (see Section 1).
c. None of the access rooms is a kitchen.
See Diagram 2.1b. Where served by only one stair, all habitable rooms (excluding kitchens) should have either of the following.
a. An emergency escape window or external door, as described in paragraph 2.10.
b. Direct access to a protected stairway, as described in paragraph 2.5a.
Two rooms may be served by a single window. A door between the rooms should provide access to the window without passing through the stair enclosure. Both rooms should have their own access to the internal stair.
All habitable rooms (excluding kitchens) should have either of the following.
a. An emergency escape window or external door, as described in paragraph 3.6.
b. In multi-storey flats, direct access to a protected internal stairway (minimum REI 30) leading to an exit from the flat.
Two rooms may be served by a single escape window. A door between rooms should provide access to the escape window without passing through the stair enclosure. Both rooms should have their own access to the internal stair.
One of the following approaches should be adopted, observing the inner room restrictions described in paragraphs 3.7 and 3.8.
a. Provide a protected entrance hall (minimum REI 30) serving all habitable rooms that meets the conditions shown in Diagram 3.2.
b. Plan the flat to meet the conditions shown in Diagram 3.3, so that both of the following apply.
i. The travel distance from the flat entrance door to any point in any habitable room is a maximum of 9m.
ii. Cooking facilities are remote from the main entrance door and do not impede the escape route from anywhere in the flat.
c. Provide an alternative exit from the flat complying with paragraph 3.22.
Where access from any habitable room to the entrance hall or flat entrance is impossible without passing through another room, all of the following conditions should be met (Diagram 3.4).
a. Bedrooms should be separated from living accommodation by fire resisting construction (minimum REI 30) and fire doorsets (minimum E 20).
b. The alternative exit should be in the part of the flat that contains the bedrooms.
A person escaping through the common area, if confronted by the effects of a fire in another flat, should be able to turn away from it and make a safe escape via an alternative route.
Escape route travel distances should comply with Table 3.1.
An escape route should not pass through one stair enclosure to reach another. It may pass through a protected lobby (minimum REI 30) of one stair to reach another.
Escape routes should have a minimum clear headroom of 2m. The only projections allowed below this height are door frames.
See para 3.19
NOTE: The bedrooms are not classified as inner rooms because escape is possible in two directions.
Fire doorset
Fire resisting construction (minimum REI 30) between living and bedroom accommodation
Alternative exit
All escape routes should have adequate artificial lighting. If the mains electricity power supply fails, escape lighting should illuminate the route (including external escape routes).
In addition, escape lighting should be provided to all of the following.
a. Toilet accommodation with a minimum floor area of 8m2.
b. Electricity and generator rooms.
c. Switch room/battery room for emergency lighting system.
d. Emergency control rooms.
The approach to rooms containing refuse chutes or for storing refuse should comply with one of the following conditions.
a. Be directly from the open air.
b. Be through a protected lobby with a minimum of 0.2m2 of permanent ventilation.
An inner room is permitted when it is one of the following.
a. A kitchen.
b. A laundry or utility room.
c. A dressing room.
d. A bathroom, WC or shower room.
e. Any room on a storey that is a maximum of 4.5m above ground level which is provided with an emergency escape window as described in paragraph 3.6.
f. A gallery that complies with paragraph 3.13.
Except in buildings described in paragraph 3.28, common stairs forming part of the only escape route from a flat should not serve any of the following.
a. Covered car park.
b. Boiler room.
c. Fuel storage space.
d. Other ancillary accommodation of similar fire risk.
A room accessed only via an inner room (an inner inner room) is acceptable when all of the following apply.
a. It complies with paragraph 3.7.
b. The access rooms each have a smoke alarm (see Section 1).
c. None of the access rooms is a kitchen.
accessible
Access openings to refuse storage chambers should not be sited in the following areas.
a. Next to escape routes or final exits.
b. Near the windows of flats.
Access to an external escape stair may be via a flat roof, provided the flat roof meets the requirements of paragraph 3.30.
accessible entrance
See para 3.18
Flat entrance
Kitchen area
Bath
air path
Air circulation systems which circulate air within an individual dwellinghouse with a floor more than
4.5m above ground level should meet the guidance given in paragraph 2.9.
The approach to rooms containing refuse chutes or for storing refuse should comply with one of the following conditions.
a. Be directly from the open air.
b. Be through a protected lobby with a minimum of 0.2m2 of permanent ventilation.
air permeability
All of the following precautions should be taken to avoid the spread of smoke and fire to the protected stairway.
a. Transfer grilles should not be fitted in any wall, door, floor or ceiling of the stair enclosure.
b. Any duct passing through the stair enclosure should be rigid steel. Joints between the ductwork and stair enclosure should be fire-stopped.
c. Ventilation ducts supplying or extracting air directly to or from a protected stairway should not serve other areas as well.
d. Any system of mechanical ventilation which recirculates air and which serves both the stair and other areas should be designed to shut down on the detection of smoke within the system.
e. For ducted warm air heating systems, a room thermostat should be sited in the living room. It should be mounted at a height between 1370mm and 1830mm above the floor. The maximum setting should be 27°C.
NOTE: Ventilation ducts passing through compartment walls should comply with the guidance in Section 9.
For systems circulating air only within an individual flat, take all of the following precautions.
a. Transfer grilles should not be fitted in any wall, door, floor or ceiling of the enclosure.
b. Any duct passing through the enclosure should be rigid steel. Joints between the ductwork and enclosure should be fire-stopped.
c. Ventilation ducts serving the enclosure should not serve any other areas.
d. Any system of mechanical ventilation which recirculates air and which serves both the stair and other areas should be designed to shut down on the detection of smoke within the system.
e. For ducted warm air heating systems, a room thermostat should be sited in the living room. It should be mounted at a height between 1370mm and 1830mm above the floor. The maximum setting should be 27°C.
NOTE: Ventilation ducts passing through compartment walls should comply with the guidance in Section 9.
Guidance on the design of smoke control systems that use pressure differentials is available in BS EN 12101-6.
With some configurations of external wall, a fire in one part of a building could subject the external wall of a protected stairway to heat (for example, where the two are adjacent at an internal angle in the façade, as shown in Diagram 3.10).
If a protected stairway projects beyond, is recessed from or is in an internal angle of the adjoining external wall of the building, then the minimum distance between an unprotected area of the building enclosure and an unprotected area of the stair enclosure should be 1800mm.
alternating tread stair
Dwellinghouses with one internal stair should comply with paragraphs 2.5 and 2.6. In dwellinghouses with more than one stair, the stairs should provide effective alternative means of escape. The stairs should be physically separated by either of the following.
a. Fire resisting construction (minimum REI 30).
b. More than one room.
Flats may be served by an external stair if the provisions in paragraphs 3.66 to 3.69 are followed.
alternative escape routes
In the Secretary of State’s view, requirement B1 is met by achieving all of the following.
a. There are sufficient means for giving early warning of fire to people in the building.
b. All people can escape to a place of safety without external assistance.
c. Escape routes are suitably located, sufficient in number and of adequate capacity.
d. Where necessary, escape routes are sufficiently protected from the effects of fire and smoke.
e. Escape routes are adequately lit and exits are suitably signed.
f. There are appropriate provisions to limit the ingress of smoke to the escape routes, or to
restrict the spread of fire and remove smoke.
g. For buildings containing flats, there are appropriate provisions to support a stay put evacuation
strategy.
The extent to which any of these measures are necessary is dependent on the use of the building,
its size and its height.
Building work and material changes of use subject to requirement B1 include both new and existing
buildings.
Where a flat roof forms part of a means of escape, it should comply with all of the following.
a. It should be part of the same building from which escape is being made.
b. The route across the roof should lead to a storey exit or external escape route.
c. The part of the roof (including its supporting structure) forming the escape route, and any opening within 3m of the escape route, should be of fire resisting construction (minimum REI 30).
A balcony or flat roof intended to form part of an escape route should be provided with guarding etc. in accordance with Approved Document K.
Any external escape stair should meet all of the following conditions (Diagram 2.7).
a. Doors to the stair should be fire resisting (minimum E 30), except for a single exit door from the building to the top landing of a downward-leading external stair.
b. Fire resisting construction (minimum RE 30) is required for the building envelope within the following zones, measured from the flights and landings of the external stair.
i. 1800mm horizontally.
ii. 9m vertically below.
iii. 1100mm above the top landing of the stair (except where the stair leads from basement to ground level).
c. Fire resisting construction (minimum RE 30) should be provided for any part of the building (including doors) within 1800mm of the escape route from the foot of the stair to a place of safety. This does not apply if there are alternative escape routes from the foot of the external escape stair.
d. Stairs more than 6m in height should be protected from adverse weather. Protection should prevent the build-up of snow or ice but does not require full enclosure.
e. Glazing in areas of fire resisting construction should be fixed shut and fire resisting (in terms of integrity, but not insulation) (minimum E 30).
Where an existing window would be an escape window in a new dwellinghouse, and is big enough to be used for escape purposes, then the replacement should comply with one of the following.
a. The replacement window should be sized to provide at least the same potential for escape.
b. If the existing window was larger than required for escape purposes, the opening can be reduced to the minimum described in paragraph 2.10.
Where a new storey is added through conversion to create a storey above 4.5m, both of the following should apply.
a. The full extent of the escape route should be addressed.
b. Fire resisting doors (minimum E 20) and partitions (minimum REI 30) should be provided, including upgrading the existing doors where necessary.
NOTE: Where the layout is open plan, new partitions should be provided to enclose the escape route (Diagram 2.2).
An alternative approach to that described in paragraph 2.21 would be to comply with all of the following.
a. Provide sprinkler protection to the open-plan areas.
b. Provide a fire resisting partition (minimum REI 30) and door (minimum E 20) to separate the ground storey from the upper storeys. The door should allow occupants of the loft room access to a first storey escape window.
c. Separate cooking facilities from the open-plan area with fire resisting construction (minimum REI 30).
See para 2.6
Example of alternative exit in para 2.6(a) (see definition in Appendix A)
See Diagram 2.1c. The dwellinghouse should have either of the following. Cavity barriers or a fire resisting ceiling (minimum EI 30) should be provided above a protected stairway enclosure (Diagram 2.3). b. Alternative escape route – a top storey separated from lower storeys by fire resisting construction (minimum REI 30) and with an alternative escape route leading to its own final exit.
a. Protected stairway – a stair separated by fire resisting construction (minimum REI 30) at all storeys, that complies with one of the following.
i. Extends to a final exit (Diagram 2.2a).
ii. Gives access to a minimum of two ground level final exits that are separated from each other by fire resisting construction (minimum REI 30) and fire doorsets (minimum E 20) (Diagram 2.2b).
See Diagram 2.1d. In addition to meeting the provisions in paragraph 2.5, the dwellinghouse should comply with either of the following.
a. Provide an alternative escape route from each storey more than 7.5m above ground level. At the first storey above 7.5m, the protected stairway should be separated from the lower storeys by fire resisting construction (minimum REI 30) if the alternative escape route is accessed via either of the following.
i. The protected stairway to an upper storey.
ii. A landing within the protected stairway enclosure to an alternative escape route on the same storey. The protected stairway at or about 7.5m above ground level should be separated from the lower storeys or levels by fire resisting construction (see Diagram 2.4).
b. Provide a sprinkler system throughout, designed and installed in accordance with BS 9251.
NOTES:
1. This diagram does not apply where the gallery is provided with one of the following:
i. An alternative escape route
ii. An emergency escape window (where the gallery floor is not more than 4.5m above ground level).
2. Any cooking facilities within a room containing a gallery should comply with one of the following conditions:
i. Be enclosed with fire resisting construction
ii. Be remote from the stair to the gallery and positioned such that they do not prejudice escape from the gallery.
See para 2.15
NOTES:
1. This diagram does not apply where the gallery is provided with one of the following:
i. An alternative escape route
ii. An emergency escape window (where the gallery floor is not more than 4.5m above ground level).
2. Any cooking facilities within a room containing a gallery should comply with one of the following conditions:
i. Be enclosed with fire resisting construction
ii. Be remote from the stair to the gallery and positioned such that they do not prejudice escape from the gallery.
See para 3.13
Where a flat roof forms part of a means of escape, it should comply with all of the following.
a. It should be part of the same building from which escape is being made.
b. The route across the roof should lead to a storey exit or external escape route.
c. The part of the roof (including its supporting structure) forming the escape route, and any opening within 3m of the escape route, should be of fire resisting construction (minimum REI 30).
Configurations of stairs and external wall
Fire resisting construction
Fire resisting construction of adjacent building enclosure of protected stairway
Non-fire resisting construction
See para 3.63
A balcony or flat roof intended to form part of an escape route should be provided with guarding etc. in accordance with Approved Document K.
See para 3.18
NOTE: Bathrooms do not need to have fire doorsets provided that the bathroom is separated by fire resisting construction from the adjacent rooms.
A person escaping through the common area, if confronted by the effects of a fire in another flat, should be able to turn away from it and make a safe escape via an alternative route.
Provisions are recommended to support a stay put evacuation strategy for blocks of flats. It is based on the principle that a fire is contained in the flat of origin and common escape routes are maintained relatively free from smoke and heat. It allows occupants, some of whom may require assistance to escape in the event of a fire, in other flats that are not affected to remain.
Sufficient protection to common means of escape is necessary to allow occupants to escape should they choose to do so or are instructed/aided to by the fire service. A higher standard of protection is therefore needed to ensure common escape routes remain available for a longer period than is provided in other buildings.
Where a storey or part of a building has multiple escape routes available, one may be over a flat roof that complies with all of the following.
a. It should be part of the same building from which escape is being made.
b. The route across the roof should lead to a storey exit or external escape route.
c. The part of the roof (including its supporting structure) forming the escape route, and any opening within 3m of the escape route, should be of fire resisting construction (minimum REI 30).
d. The route should be clearly defined and guarded by walls and/or protective barriers to protect against falling.
Where a storey or part of a building has multiple escape routes available, one may be over a flat roof that complies with all of the following.
d. The route should be clearly defined and guarded by walls and/or protective barriers to protect against falling.
Escape route travel distances should comply with Table 3.1.
Escape routes should have a minimum clear headroom of 2m. The only projections allowed below this height are door frames.
See para 3.19
NOTE: The bedrooms are not classified as inner rooms because escape is possible in two directions.
Fire doorset
Fire resisting construction (minimum REI 30) between living and bedroom accommodation
Alternative exit
All escape routes should have adequate artificial lighting. If the mains electricity power supply fails, escape lighting should illuminate the route (including external escape routes).
Escape stair lighting should be on a separate circuit from the electricity supply to any other part of the escape route.
See para 3.21
NOTE: This only applies where at least one storey is more than 4.5m above ground level.
Fire doorset
Fire resisting stair enclosure(minimum REI 30)
Alternative exit
If a building does not meet the criteria of paragraph 3.28, an escape stair forming part of the only escape route from an upper storey should not continue down to serve a basement storey. The basement storey should be served by a separate escape stair.
Except in buildings described in paragraph 3.28, common stairs forming part of the only escape route from a flat should not serve any of the following.
a. Covered car park.
b. Boiler room.
c. Fuel storage space.
d. Other ancillary accommodation of similar fire risk.
In single stair buildings, electricity meters should be in securely locked cupboards. Cupboards should be separated from the escape route by fire resisting construction.
alternative exit
A gallery should comply with one of the following.
a. It should be provided with an alternative exit.
b. It should be provided with an emergency escape window, as described in paragraph 2.10, where the gallery floor is a maximum of 4.5m above ground level.
c. It should meet all the conditions shown in Diagram 2.6.
See para 2.5
Fire resisting construction minimum REI 30
Fd Fire doorset minimum E 20
See para 2.6
Example of alternative exit in para 2.6(a) (see definition in Appendix A)
See Diagram 2.1c. The dwellinghouse should have either of the following. Cavity barriers or a fire resisting ceiling (minimum EI 30) should be provided above a protected stairway enclosure (Diagram 2.3). b. Alternative escape route – a top storey separated from lower storeys by fire resisting construction (minimum REI 30) and with an alternative escape route leading to its own final exit.
a. Protected stairway – a stair separated by fire resisting construction (minimum REI 30) at all storeys, that complies with one of the following.
i. Extends to a final exit (Diagram 2.2a).
ii. Gives access to a minimum of two ground level final exits that are separated from each other by fire resisting construction (minimum REI 30) and fire doorsets (minimum E 20) (Diagram 2.2b).
NOTES:
1. This diagram does not apply where the gallery is provided with one of the following:
i. An alternative escape route
ii. An emergency escape window (where the gallery floor is not more than 4.5m above ground level).
2. Any cooking facilities within a room containing a gallery should comply with one of the following conditions:
i. Be enclosed with fire resisting construction
ii. Be remote from the stair to the gallery and positioned such that they do not prejudice escape from the gallery.
See para 2.15
For flats more than 4.5m above ground level, a balcony outside an alternative exit should be a common balcony meeting the conditions described in paragraph 3.22.
A gallery should comply with one of the following.
a. It should be provided with an alternative exit.
b. It should be provided with an emergency escape window, as described in paragraph 3.6, where the gallery floor is a maximum of 4.5m above ground level.
c. It should meet the conditions shown in Diagram 3.1.
Where access from any habitable room to the entrance hall or flat entrance is impossible without passing through another room, all of the following conditions should be met (Diagram 3.4).
a. Bedrooms should be separated from living accommodation by fire resisting construction (minimum REI 30) and fire doorsets (minimum E 20).
b. The alternative exit should be in the part of the flat that contains the bedrooms.
Any alternative exit from a flat should comply with all of the following.
a. It should be remote from the main entrance door to the flat.
b. It should lead to a final exit, via a common stair if necessary, through one of the following.
i. A door to an access corridor, access lobby or common balcony.
ii. An internal private stair leading to an access corridor, access lobby or common balcony at another level.
iii. A door to a common stair.
iv. A door to an external stair.
v. A door to an escape route over a flat roof.
Any access route leading to a final exit or common stair should comply with the provisions for means of escape in the common parts of a flat (see paragraph 3.25).
The following paragraphs deal with means of escape from the entrance doors of flats to a final exit.
Divide a common corridor connecting two or more storey exits with a fire doorset fitted with a self-closing device (minimum E 30 Sa). See Diagram 3.8. Associated screens should be fire resisting. Site doors so that smoke does not affect access to more than one stair.
See para 3.19
NOTE: The bedrooms are not classified as inner rooms because escape is possible in two directions.
Fire doorset
Fire resisting construction (minimum REI 30) between living and bedroom accommodation
Alternative exit
Every doorway or other exit providing access to a means of escape, other than exits in ordinary use (e.g. main entrances), should be distinctively and conspicuously marked by an exit sign in accordance with BS ISO 3864-1 and BS 5499-4. For this reason, blocks of flats with a single stair in regular use would not usually require any fire exit signage.
Advice on fire safety signs, including emergency escape signs, is given in the HSE publication Safety Signs and Signals: Guidance on Regulations.
Some buildings may require additional signs to comply with other legislation.
See para 3.21
NOTE: This only applies where at least one storey is more than 4.5m above ground level.
Alternative exit
Bathroom
ENTRANCE LEVEL
LEVEL(S) ABOVE OR BELOW ENTRANCE LEVEL
See para 3.21
NOTE: This only applies where at least one storey is more than 4.5m above ground level.
Fire doorset
Fire resisting stair enclosure(minimum REI 30)
Alternative exit
The construction separating two adjacent protected stairways (or exit passageways leading to different final exits) should be imperforate.
In buildings with a maximum of three storeys above the ground storey, stairs may serve both flats and other occupancies, provided that the stairs are separated from each occupancy by protected lobbies (minimum REI 30) at each storey.
Every protected stairway should lead to a final exit, either directly or via a protected exit passageway. Any protected exit corridor or stair should have the same standard of fire resistance and lobby protection as the stair it serves.
annex c: glossary
Escape routes should have a minimum clear headroom of 2m. The only projections allowed below this height are door frames.
appliance ventilation duct
All of the following precautions should be taken to avoid the spread of smoke and fire to the protected stairway.
a. Transfer grilles should not be fitted in any wall, door, floor or ceiling of the stair enclosure.
b. Any duct passing through the stair enclosure should be rigid steel. Joints between the ductwork and stair enclosure should be fire-stopped.
c. Ventilation ducts supplying or extracting air directly to or from a protected stairway should not serve other areas as well.
d. Any system of mechanical ventilation which recirculates air and which serves both the stair and other areas should be designed to shut down on the detection of smoke within the system.
e. For ducted warm air heating systems, a room thermostat should be sited in the living room. It should be mounted at a height between 1370mm and 1830mm above the floor. The maximum setting should be 27°C.
NOTE: Ventilation ducts passing through compartment walls should comply with the guidance in Section 9.
For systems circulating air only within an individual flat, take all of the following precautions.
a. Transfer grilles should not be fitted in any wall, door, floor or ceiling of the enclosure.
b. Any duct passing through the enclosure should be rigid steel. Joints between the ductwork and enclosure should be fire-stopped.
c. Ventilation ducts serving the enclosure should not serve any other areas.
d. Any system of mechanical ventilation which recirculates air and which serves both the stair and other areas should be designed to shut down on the detection of smoke within the system.
e. For ducted warm air heating systems, a room thermostat should be sited in the living room. It should be mounted at a height between 1370mm and 1830mm above the floor. The maximum setting should be 27°C.
NOTE: Ventilation ducts passing through compartment walls should comply with the guidance in Section 9.
approved document
Means of warning and escape
B1.The building shall be designed and constructed so that there are appropriate provisions for the early warning of fire, and appropriate means of escape in case of fire from the building to a place of safety outside the building capable of being safely and effectively used at all material times.
Requirement B1 does not apply to any prison provided under section 33 of the Prison Act 1952
(a) (power to provide prisons, etc.).
(a) 1952 c. 52; section 33 was amended by section 100 of the Criminal Justice and Public Order Act 1994 (c. 33) and by S.I. 1963/597.
A balcony or flat roof intended to form part of an escape route should be provided with guarding etc. in accordance with Approved Document K.
A balcony or flat roof intended to form part of an escape route should be provided with guarding etc. in accordance with Approved Document K.
A balcony or flat roof intended to form part of an escape route should be provided with guarding etc. in accordance with Approved Document K.
A balcony or flat roof intended to form part of an escape route should be provided with guarding etc. in accordance with Approved Document K.
The internal arrangement of single storey or multi-storey flats should comply with paragraphs 3.15 to 3.17. Alternatively, the guidance in paragraphs 3.18 to 3.22 may be followed.
A flat accessed via the common parts of the building should also comply with the provisions for small single stair buildings in paragraph 3.28 and Diagram 3.9. A protected entrance hall may be required as a result.
Paragraph 3.27 may be modified using the guidance in clause 7.3 of BS 9991.
Guidance on cables for large and complex buildings is given in BS 5839-1, BS 5266-1 and BS 8519.
Guidance on cables for large and complex buildings is given in BS 5839-1, BS 5266-1 and BS 8519.
Except in buildings that comply with Diagram 3.9, the corridor or lobby next to each stair should have a smoke vent. The location of the vent should comply with both of the following.
a. Be as high as practicable.
b. Be positioned so the top edge is at least as high as the top of the door to the stair.
Guidance on the design of smoke control systems that use pressure differentials is available in BS EN 12101-6.
Section 7 provides guidance on avoiding the spread of fire between storeys. For a stair that is also a firefighting stair, guidance in Section 15 should be followed.
approved inspectors regulations
A balcony or flat roof intended to form part of an escape route should be provided with guarding etc. in accordance with Approved Document K.
A balcony or flat roof intended to form part of an escape route should be provided with guarding etc. in accordance with Approved Document K.
atrium (plural atria)
An escape route should not pass through one stair enclosure to reach another. It may pass through a protected lobby (minimum REI 30) of one stair to reach another.
automatic release mechanism
The fire detection and alarm systems in flats should connect to a central monitoring point or alarm
receiving centre. The systems should alert the warden or supervisor and identify the individual flat
where a fire has been detected.
Smoke alarms should be mains operated and conform to BS EN 14604.
Smoke and heat alarms should have a standby power supply, such as a battery (rechargeable
or non-rechargeable) or capacitor. More information on power supplies is given in clause 15 of
BS 5839-6.
NOTE: The term ‘fire alarm system’ describes the combination of components for giving an audible
and/or other perceptible warning of fire.
NOTE: In this document, the term ‘fire detection system’ describes any type of automatic sensor
network and associated control and indicating equipment. Sensors may be sensitive to smoke,
heat, gaseous combustion products or radiation. Automatic sprinkler systems can also be used to
operate a fire alarm system.
A large dwellinghouse of two storeys (excluding basement storeys) should be fitted with a Grade A
Category LD3 fire detection and alarm system, as described in BS 5839-6.
A large dwellinghouse of three or more storeys (excluding basement storeys) should be fitted with
a Grade A Category LD2 fire detection and alarm system as described in BS 5839-6.
b1 means of waring and escape
Means of warning and escape
B1.The building shall be designed and constructed so that there are appropriate provisions for the early warning of fire, and appropriate means of escape in case of fire from the building to a place of safety outside the building capable of being safely and effectively used at all material times.
Requirement B1 does not apply to any prison provided under section 33 of the Prison Act 1952
(a) (power to provide prisons, etc.).
(a) 1952 c. 52; section 33 was amended by section 100 of the Criminal Justice and Public Order Act 1994 (c. 33) and by S.I. 1963/597.
In the Secretary of State’s view, requirement B1 is met by achieving all of the following.
a. There are sufficient means for giving early warning of fire to people in the building.
b. All people can escape to a place of safety without external assistance.
c. Escape routes are suitably located, sufficient in number and of adequate capacity.
d. Where necessary, escape routes are sufficiently protected from the effects of fire and smoke.
e. Escape routes are adequately lit and exits are suitably signed.
f. There are appropriate provisions to limit the ingress of smoke to the escape routes, or to
restrict the spread of fire and remove smoke.
g. For buildings containing flats, there are appropriate provisions to support a stay put evacuation
strategy.
The extent to which any of these measures are necessary is dependent on the use of the building,
its size and its height.
Building work and material changes of use subject to requirement B1 include both new and existing
buildings.
Where a flat roof forms part of a means of escape, it should comply with all of the following.
a. It should be part of the same building from which escape is being made.
b. The route across the roof should lead to a storey exit or external escape route.
c. The part of the roof (including its supporting structure) forming the escape route, and any opening within 3m of the escape route, should be of fire resisting construction (minimum REI 30).
Where an existing window would be an escape window in a new dwellinghouse, and is big enough to be used for escape purposes, then the replacement should comply with one of the following.
a. The replacement window should be sized to provide at least the same potential for escape.
b. If the existing window was larger than required for escape purposes, the opening can be reduced to the minimum described in paragraph 2.10.
Separate guidance applies to means of escape within the flat and within the common parts of the building that lead to a place of safety. Flats at ground level are treated similarly to dwellinghouses. With increasing height, more complex provisions are needed.
Where a flat roof forms part of a means of escape, it should comply with all of the following.
a. It should be part of the same building from which escape is being made.
b. The route across the roof should lead to a storey exit or external escape route.
c. The part of the roof (including its supporting structure) forming the escape route, and any opening within 3m of the escape route, should be of fire resisting construction (minimum REI 30).
A person escaping through the common area, if confronted by the effects of a fire in another flat, should be able to turn away from it and make a safe escape via an alternative route.
Provisions are recommended to support a stay put evacuation strategy for blocks of flats. It is based on the principle that a fire is contained in the flat of origin and common escape routes are maintained relatively free from smoke and heat. It allows occupants, some of whom may require assistance to escape in the event of a fire, in other flats that are not affected to remain.
Sufficient protection to common means of escape is necessary to allow occupants to escape should they choose to do so or are instructed/aided to by the fire service. A higher standard of protection is therefore needed to ensure common escape routes remain available for a longer period than is provided in other buildings.
Paragraphs 3.6 to 3.23 deal with the means of escape within each flat. Paragraphs 3.25 to 3.89 deal with the means of escape in common areas of the building (including mixed use buildings in paragraphs 3.76 and 3.77). Guidance for live/work units is given in paragraph 3.24.
In a converted building with a maximum of three storeys, a minimum REI 30 fire resistance could be accepted for elements of structure if the means of escape conform to the provisions of Section 3.
b3 internal fire spread structure
Means of warning and escape
B1.The building shall be designed and constructed so that there are appropriate provisions for the early warning of fire, and appropriate means of escape in case of fire from the building to a place of safety outside the building capable of being safely and effectively used at all material times.
Requirement B1 does not apply to any prison provided under section 33 of the Prison Act 1952
(a) (power to provide prisons, etc.).
(a) 1952 c. 52; section 33 was amended by section 100 of the Criminal Justice and Public Order Act 1994 (c. 33) and by S.I. 1963/597.
In the Secretary of State’s view, requirement B1 is met by achieving all of the following.
a. There are sufficient means for giving early warning of fire to people in the building.
b. All people can escape to a place of safety without external assistance.
c. Escape routes are suitably located, sufficient in number and of adequate capacity.
d. Where necessary, escape routes are sufficiently protected from the effects of fire and smoke.
e. Escape routes are adequately lit and exits are suitably signed.
f. There are appropriate provisions to limit the ingress of smoke to the escape routes, or to
restrict the spread of fire and remove smoke.
g. For buildings containing flats, there are appropriate provisions to support a stay put evacuation
strategy.
The extent to which any of these measures are necessary is dependent on the use of the building,
its size and its height.
Building work and material changes of use subject to requirement B1 include both new and existing
buildings.
The provisions in this section make the following assumptions.
a. Any fire is likely to be in a flat.
b. There is no reliance on external rescue.
c. Simultaneous evacuation of all flats is unlikely to be necessary due to compartmentation.
d. Fires in common parts of the building should not spread beyond the fabric in the immediate vicinity. In some cases, however, communal facilities exist that require additional measures to be taken.
A fire doorset (minimum E 30 Sa) fitted with a self-closing device (and fire resisting screen, where required) should separate the dead-end portion of a common corridor from the rest of the corridor (Diagrams 3.7a, 3.8b and 3.8c).
In single stair buildings, smoke vents on the storey where the fire is initiated, and the vent at the head of the stair, should be activated by smoke detectors in the common parts.
In buildings with more than one stair, smoke vents may be activated manually. The control system should open the vent at the head of the stair before, or at the same time as, the vent on the storey where the fire is located. Smoke detection is not required for ventilation purposes in this instance.
b4 external fire spread
Means of warning and escape
B1.The building shall be designed and constructed so that there are appropriate provisions for the early warning of fire, and appropriate means of escape in case of fire from the building to a place of safety outside the building capable of being safely and effectively used at all material times.
Requirement B1 does not apply to any prison provided under section 33 of the Prison Act 1952
(a) (power to provide prisons, etc.).
(a) 1952 c. 52; section 33 was amended by section 100 of the Criminal Justice and Public Order Act 1994 (c. 33) and by S.I. 1963/597.
In the Secretary of State’s view, requirement B1 is met by achieving all of the following.
a. There are sufficient means for giving early warning of fire to people in the building.
b. All people can escape to a place of safety without external assistance.
c. Escape routes are suitably located, sufficient in number and of adequate capacity.
d. Where necessary, escape routes are sufficiently protected from the effects of fire and smoke.
e. Escape routes are adequately lit and exits are suitably signed.
f. There are appropriate provisions to limit the ingress of smoke to the escape routes, or to
restrict the spread of fire and remove smoke.
g. For buildings containing flats, there are appropriate provisions to support a stay put evacuation
strategy.
The extent to which any of these measures are necessary is dependent on the use of the building,
its size and its height.
Building work and material changes of use subject to requirement B1 include both new and existing
buildings.
The fire detection and alarm systems in flats should connect to a central monitoring point or alarm
receiving centre. The systems should alert the warden or supervisor and identify the individual flat
where a fire has been detected.
Where a flat roof forms part of a means of escape, it should comply with all of the following.
a. It should be part of the same building from which escape is being made.
b. The route across the roof should lead to a storey exit or external escape route.
c. The part of the roof (including its supporting structure) forming the escape route, and any opening within 3m of the escape route, should be of fire resisting construction (minimum REI 30).
Any external escape stair should meet all of the following conditions (Diagram 2.7).
a. Doors to the stair should be fire resisting (minimum E 30), except for a single exit door from the building to the top landing of a downward-leading external stair.
b. Fire resisting construction (minimum RE 30) is required for the building envelope within the following zones, measured from the flights and landings of the external stair.
i. 1800mm horizontally.
ii. 9m vertically below.
iii. 1100mm above the top landing of the stair (except where the stair leads from basement to ground level).
c. Fire resisting construction (minimum RE 30) should be provided for any part of the building (including doors) within 1800mm of the escape route from the foot of the stair to a place of safety. This does not apply if there are alternative escape routes from the foot of the external escape stair.
d. Stairs more than 6m in height should be protected from adverse weather. Protection should prevent the build-up of snow or ice but does not require full enclosure.
e. Glazing in areas of fire resisting construction should be fixed shut and fire resisting (in terms of integrity, but not insulation) (minimum E 30).
Where a flat roof forms part of a means of escape, it should comply with all of the following.
a. It should be part of the same building from which escape is being made.
b. The route across the roof should lead to a storey exit or external escape route.
c. The part of the roof (including its supporting structure) forming the escape route, and any opening within 3m of the escape route, should be of fire resisting construction (minimum REI 30).
Where access from any habitable room to the entrance hall or flat entrance is impossible without passing through another room, all of the following conditions should be met (Diagram 3.4).
a. Bedrooms should be separated from living accommodation by fire resisting construction (minimum REI 30) and fire doorsets (minimum E 20).
b. The alternative exit should be in the part of the flat that contains the bedrooms.
The provisions in this section make the following assumptions.
a. Any fire is likely to be in a flat.
b. There is no reliance on external rescue.
c. Simultaneous evacuation of all flats is unlikely to be necessary due to compartmentation.
d. Fires in common parts of the building should not spread beyond the fabric in the immediate vicinity. In some cases, however, communal facilities exist that require additional measures to be taken.
See para 3.18
NOTE: Bathrooms do not need to have fire doorsets provided that the bathroom is separated by fire resisting construction from the adjacent rooms.
The following paragraphs deal with means of escape from the entrance doors of flats to a final exit. They do not apply to flats with a top storey that is a maximum of 4.5m above ground level (designed in accordance with paragraphs 3.16 and 3.17).
Reference should also be made to the following.
a. Requirement B3 regarding compartment walls and protected shafts.
b. Requirement B5 regarding access for the fire and rescue service.
Where a storey or part of a building has multiple escape routes available, one may be over a flat roof that complies with all of the following.
a. It should be part of the same building from which escape is being made.
b. The route across the roof should lead to a storey exit or external escape route.
c. The part of the roof (including its supporting structure) forming the escape route, and any opening within 3m of the escape route, should be of fire resisting construction (minimum REI 30).
d. The route should be clearly defined and guarded by walls and/or protective barriers to protect against falling.
Where a storey or part of a building has multiple escape routes available, one may be over a flat roof that complies with all of the following.
d. The route should be clearly defined and guarded by walls and/or protective barriers to protect against falling.
A fire doorset (minimum E 30 Sa) fitted with a self-closing device (and fire resisting screen, where required) should separate the dead-end portion of a common corridor from the rest of the corridor (Diagrams 3.7a, 3.8b and 3.8c).
Except in buildings that comply with Diagram 3.9, the corridor or lobby next to each stair should have a smoke vent. The location of the vent should comply with both of the following.
a. Be as high as practicable.
b. Be positioned so the top edge is at least as high as the top of the door to the stair.
Smoke vents should comply with one of the following.
a. They should be located on an external wall with minimum free area of 1.5m2.
b. They should discharge into a vertical smoke shaft, closed at the base, that meets all of the following criteria.
i. The shaft should conform to the following conditions.
• Have a minimum cross-sectional area of 1.5m2 (minimum dimension 0.85m in any direction).
• Open at roof level, minimum 0.5m above any surrounding structures within 2m of it horizontally.
• Extend a minimum of 2.5m above the ceiling of the highest storey served by the shaft.
ii. The free area of all the following vents should be a minimum of 1m2 in the following places.
• From the corridor or lobby into the shaft.
• At the opening at the head of the shaft.
• At all internal locations within the shaft (e.g. safety grilles).
iii. The smoke shaft should be constructed from a class A1 material. All vents should either be a fire doorset (see Appendix C, Table C1, item 2.e for minimum fire resistance) or fitted with a smoke control damper achieving the same period of fire resistance and designed to operate as described below. The shaft should be vertical from base to head, with a maximum of 4m at a maximum inclined angle of 30 degrees.
iv. If smoke is detected in the common corridor or lobby, both of the following should occur.
• Simultaneous opening of vents on the storey where the fire is located, at the top of the smoke shaft and to the stair.
• Vents from the corridors or lobbies on all other storeys should remain closed, even if smoke is subsequently detected on storeys other than where the fire is located.
In single stair buildings, smoke vents on the storey where the fire is initiated, and the vent at the head of the stair, should be activated by smoke detectors in the common parts.
In buildings with more than one stair, smoke vents may be activated manually. The control system should open the vent at the head of the stair before, or at the same time as, the vent on the storey where the fire is located. Smoke detection is not required for ventilation purposes in this instance.
With some configurations of external wall, a fire in one part of a building could subject the external wall of a protected stairway to heat (for example, where the two are adjacent at an internal angle in the façade, as shown in Diagram 3.10).
If a protected stairway projects beyond, is recessed from or is in an internal angle of the adjoining external wall of the building, then the minimum distance between an unprotected area of the building enclosure and an unprotected area of the stair enclosure should be 1800mm.
Any external escape stair should meet all of the following conditions (Diagram 3.11).
a. Doors to the stair should be fire resisting (minimum E 30) and be fitted with a self-closing device, except for a single exit door from the building to the top landing of a downward-leading external stair, provided it is the only door onto the landing.
b. Fire resisting construction (minimum RE 30) is required for the building envelope within the following zones, measured from the flights and landings of the external stair.
i. 1800mm above and horizontally.
ii. 9m vertically below.
iii. 1100mm above the top landing of the stair (except where the stair leads from basement to ground level).
c. Fire resisting construction (minimum RE 30) should be provided for any part of the building (including doors) within 1800mm of the escape route from the foot of the stair to a place of safety. This does not apply if there are alternative escape routes from the foot of the external escape stair.
d. Glazing in areas of fire resisting construction should be fixed shut and fire resisting (in terms of integrity but not insulation) (minimum E 30).
e. Stairs more than 6m in height above ground level (e.g. where they are provided above a podium) should be protected from adverse weather. Protection should prevent the build-up of snow or ice but does not require full enclosure.
Access to an external escape stair may be via a flat roof, provided the flat roof meets the requirements of paragraph 3.30.
a. CORRIDOR ACCESS WITHOUT DEAD ENDS
b. CORRIDOR ACCESS WITH DEAD ENDS
The central door may be omitted if maximum travel distance is not more than 15m.
1. The arrangements shown also apply to the top storey.
2. For further guidance on the fire rating of the fire doorsets from the corridor to the flat and/or stairway refer to Appendix C ,Table C1.
Fire doorset provided in accordance with paragraphs 3.50 to 3.53(An external wall vent or smoke shaft located anywhere in the shaded area)
See paras 3.27 and 3.36
a. SMALL SINGLE STAIR BUILDING
*If smoke control is provided in the lobby, the travel distance can be increased to 7.5m maximum(see Diagram 3.7, example b).
b. SMALL SINGLE STAIR BUILDING WITH NO MORE THAN TWO FLATS PER STOREY
The door between stair and lobby should be free from security fastenings.
If the flats have protected entrance halls, the lobby between the common stair and flat entrance is not essential.
NOTES:
1. The arrangements shown also apply to the top storey.
2. If the travel distance across the lobby in diagram (a) exceeds 4.5m, Diagram 3.7 applies.
3. Where,in Diagram (b), the lobby between the common stair and the dwelling is omitted in smal lsingle stair buildings, an automatic opening vent with a free area of at least 1m2 is required at the top of the stair,which is operated automatically on detection of smoke at any storey in the stair.
4. For further guidance on the fire rating of the fire doorsets from the corridor to the flat and/or stairway refer to Appendix C, Table C1.
Fire resisting construction
Openable vent at high level for fire service use (1.0m2 minimum free area); see paragraph 3.28eSee para 3.28
Diagram 3.9
b5 access and facilities for the fire service
Means of warning and escape
B1.The building shall be designed and constructed so that there are appropriate provisions for the early warning of fire, and appropriate means of escape in case of fire from the building to a place of safety outside the building capable of being safely and effectively used at all material times.
Requirement B1 does not apply to any prison provided under section 33 of the Prison Act 1952
(a) (power to provide prisons, etc.).
(a) 1952 c. 52; section 33 was amended by section 100 of the Criminal Justice and Public Order Act 1994 (c. 33) and by S.I. 1963/597.
Fire detection and alarm systems must be properly designed, installed and maintained. A design,
installation and commissioning certificate should be provided for fire detection and alarm systems.
Third party certification schemes for fire protection products and related services are an effective
means of providing assurances of quality, reliability and safety.
The provisions in this section make the following assumptions.
a. Any fire is likely to be in a flat.
b. There is no reliance on external rescue.
c. Simultaneous evacuation of all flats is unlikely to be necessary due to compartmentation.
d. Fires in common parts of the building should not spread beyond the fabric in the immediate vicinity. In some cases, however, communal facilities exist that require additional measures to be taken.
In a converted building with a maximum of three storeys, a minimum REI 30 fire resistance could be accepted for elements of structure if the means of escape conform to the provisions of Section 3.
basement
Basement storeys containing habitable rooms should have one of the following.
a. An emergency escape window or external door providing escape from the basement (paragraph 2.10).
b. A protected stairway (paragraph 2.5a) leading from the basement to a final exit.
Basement storeys containing habitable rooms should have one of the following.
a. An emergency escape window or external door providing escape from the basement (see paragraph 3.6).
b. A protected stairway (minimum REI 30) leading from the basement to a final exit.
basement storey
A large dwellinghouse has more than one storey, and at least one storey exceeds 200m2.
A large dwellinghouse of two storeys (excluding basement storeys) should be fitted with a Grade A
Category LD3 fire detection and alarm system, as described in BS 5839-6.
A large dwellinghouse of three or more storeys (excluding basement storeys) should be fitted with
a Grade A Category LD2 fire detection and alarm system as described in BS 5839-6.
Where new habitable rooms are provided, a fire detection and alarm system should be installed
where either of the following applies.
a. The room is provided above or below the ground storey.
b. The room is provided at the ground storey, without a final exit.
See paras 2.1 to 2.6
Single storey dwellinghouse(see paragraph 2.1)
Dwellinghouse with one storey more than 4.5m above ground level(see paragraph 2.5)
Dwellinghouse with two or more storeys more than 4.5m above ground level(see paragraph 2.6)
Basement storeys containing habitable rooms should have one of the following.
a. An emergency escape window or external door providing escape from the basement (paragraph 2.10).
b. A protected stairway (paragraph 2.5a) leading from the basement to a final exit.
Where it is undesirable to replace existing doors because of historical or architectural merit, the possibility of retaining, and where necessary upgrading, them should be investigated.
See para 2.6
Example of alternative exit in para 2.6(a) (see definition in Appendix A)
Where escape from a dwellinghouse is to an enclosed space with exit only possible through other buildings (e.g. a courtyard or back garden), the length of the space should exceed whichever is the greater of the following.
a. The height of the dwellinghouse above ground level (x).
b. Where a rear extension is provided, the height of the extension (y).
See para 2.10
See Diagram 2.1d. In addition to meeting the provisions in paragraph 2.5, the dwellinghouse should comply with either of the following.
a. Provide an alternative escape route from each storey more than 7.5m above ground level. At the first storey above 7.5m, the protected stairway should be separated from the lower storeys by fire resisting construction (minimum REI 30) if the alternative escape route is accessed via either of the following.
i. The protected stairway to an upper storey.
ii. A landing within the protected stairway enclosure to an alternative escape route on the same storey. The protected stairway at or about 7.5m above ground level should be separated from the lower storeys or levels by fire resisting construction (see Diagram 2.4).
b. Provide a sprinkler system throughout, designed and installed in accordance with BS 9251.
A passenger lift serving any storey more than 4.5m above ground level should be in either of the following.
a. The enclosure to the protected stairway, as described in paragraph 2.5.
b. A fire resisting lift shaft (minimum REI 30).
For flats more than 4.5m above ground level, a balcony outside an alternative exit should be a common balcony meeting the conditions described in paragraph 3.22.
The internal arrangement of single storey or multi-storey flats should comply with paragraphs 3.15 to 3.17. Alternatively, the guidance in paragraphs 3.18 to 3.22 may be followed.
A flat accessed via the common parts of the building should also comply with the provisions for small single stair buildings in paragraph 3.28 and Diagram 3.9. A protected entrance hall may be required as a result.
A multi-storey flat with an independent external entrance at ground level is similar to a dwellinghouse and means of escape should be planned on the basis of Section 2, depending on the height of the top storey above ground level.
When multi-storey flats do not have their own external entrance at ground level, adopt one of the following approaches.
a. Approach 1 – provide at least one alternative exit from each habitable room that is not on the entrance storey of the flat (Diagram 3.5 and paragraph 3.22).
b. Approach 2 – provide at least one alternative exit from each storey that is not the entrance storey of the flat. All habitable rooms should have direct access to a protected landing (Diagram 3.6 and paragraph 3.22).
c. Approach 3 – provide a protected stairway plus a sprinkler system in accordance with Appendix E and provide smoke alarms in accordance with BS 5839-6.
d. Approach 4 – if the vertical distance between the entrance storey of the flat and any of the storeys above or below does not exceed 7.5m, provide all of the following.
i. A protected stairway.
ii. Additional smoke alarms in all habitable rooms.
iii. A heat alarm in any kitchen.
For some low rise buildings, the provisions in paragraphs 3.26 and 3.27 may be modified and the use of a single stair, protected in accordance with Diagram 3.9, may be permitted where all of the following apply.
a. The top storey of the building is a maximum of 11m above ground level.
b. No more than three storeys are above the ground storey.
c. The stair does not connect to a covered car park, unless the car park is open sided (as defined in Section 11 of Approved Document B Volume 2).
d. The stair does not serve offices, stores or other ancillary accommodation. If it does, they should be separated from the stair by a protected lobby or protected corridor (minimum REI 30) with a minimum 0.4m2 of permanent ventilation, or be protected from the ingress of smoke by a mechanical smoke control system.
NOTE: For refuse chutes and storage see paragraphs 3.55 to 3.58.
e. Either of the following is provided for the fire and rescue service.
i. A high-level openable vent with a free area of at least 1m2 at each storey.
ii. A single openable vent with a free area of at least 1m2 at the head of the stair, operable remotely at the fire and rescue service access level.
Common corridors should be protected corridors. The wall between each flat and the corridor should be a compartment wall (minimum REI 30 where the top storey is up to 5m above ground level, otherwise REI 60).
See para 3.21
NOTE: This only applies where at least one storey is more than 4.5m above ground level.
Alternative exit
Bathroom
ENTRANCE LEVEL
LEVEL(S) ABOVE OR BELOW ENTRANCE LEVEL
A vent to the outside with a minimum free area of 1m2 should be provided from the top storey of the stair.
See para 3.21
NOTE: This only applies where at least one storey is more than 4.5m above ground level.
Fire doorset
Fire resisting stair enclosure(minimum REI 30)
Alternative exit
Where more than one escape route is available from a storey (or part of a building), then some of the escape routes from that storey or part of the building may be by way of an external stair provided all of the following conditions are met:
a. There is a at least one internal escape stair from every part of each storey (excluding plant areas).
b. The stair serves a floor not more than 6m above either the ground level or a roof podium which is itself served by an independent protected stairway.
c. The stair meets the provisions in paragraph 3.68.
If a building does not meet the criteria of paragraph 3.28, an escape stair forming part of the only escape route from an upper storey should not continue down to serve a basement storey. The basement storey should be served by a separate escape stair.
Where multiple escape stairs serve the upper storeys, only one needs to end at ground level. Other stairs may connect with the basement storeys if there is a protected lobby or a protected corridor between the stairs and accommodation at each basement level.
In buildings with a maximum of three storeys above the ground storey, stairs may serve both flats and other occupancies, provided that the stairs are separated from each occupancy by protected lobbies (minimum REI 30) at each storey.
Basement storeys containing habitable rooms should have one of the following.
a. An emergency escape window or external door providing escape from the basement (see paragraph 3.6).
b. A protected stairway (minimum REI 30) leading from the basement to a final exit.
bathroom
An inner room is permitted when it is one of the following.
a. A kitchen.
b. A laundry or utility room.
c. A dressing room.
d. A bathroom, WC or shower room.
e. Any room on a storey that is a maximum of 4.5m above ground level which is provided with an emergency escape window as described in paragraph 2.10.
f. A gallery that complies with paragraph 2.15.
An inner room is permitted when it is one of the following.
a. A kitchen.
b. A laundry or utility room.
c. A dressing room.
d. A bathroom, WC or shower room.
e. Any room on a storey that is a maximum of 4.5m above ground level which is provided with an emergency escape window as described in paragraph 3.6.
f. A gallery that complies with paragraph 3.13.
bedspace
See para 3.19
NOTE: The bedrooms are not classified as inner rooms because escape is possible in two directions.
Fire doorset
Fire resisting construction (minimum REI 30) between living and bedroom accommodation
Alternative exit
boundary
One of the following approaches should be adopted, observing the inner room restrictions described in paragraphs 3.7 and 3.8.
a. Provide a protected entrance hall (minimum REI 30) serving all habitable rooms that meets the conditions shown in Diagram 3.2.
b. Plan the flat to meet the conditions shown in Diagram 3.3, so that both of the following apply.
i. The travel distance from the flat entrance door to any point in any habitable room is a maximum of 9m.
ii. Cooking facilities are remote from the main entrance door and do not impede the escape route from anywhere in the flat.
c. Provide an alternative exit from the flat complying with paragraph 3.22.
Paragraph 3.27 may be modified using the guidance in clause 7.3 of BS 9991.
building
Guidance on cables for large and complex buildings is given in BS 5839-1, BS 5266-1 and BS 8519.
building and land associated with the building
The internal arrangement of single storey or multi-storey flats should comply with paragraphs 3.15 to 3.17. Alternatively, the guidance in paragraphs 3.18 to 3.22 may be followed.
A flat accessed via the common parts of the building should also comply with the provisions for small single stair buildings in paragraph 3.28 and Diagram 3.9. A protected entrance hall may be required as a result.
Paragraph 3.27 may be modified using the guidance in clause 7.3 of BS 9991.
Paragraphs 3.6 to 3.23 deal with the means of escape within each flat. Paragraphs 3.25 to 3.89 deal with the means of escape in common areas of the building (including mixed use buildings in paragraphs 3.76 and 3.77). Guidance for live/work units is given in paragraph 3.24.
In mixed use buildings, separate means of escape should be provided from any storeys or parts of storeys used for the ‘residential’ or ‘assembly and recreation’ purpose groups (purpose groups 1, 2 and 5), other than in the case of certain small buildings or buildings in which the residential accommodation is ancillary (see paragraphs 3.76 and 3.77)
Any external escape stair should meet all of the following conditions (Diagram 3.11).
a. Doors to the stair should be fire resisting (minimum E 30) and be fitted with a self-closing device, except for a single exit door from the building to the top landing of a downward-leading external stair, provided it is the only door onto the landing.
b. Fire resisting construction (minimum RE 30) is required for the building envelope within the following zones, measured from the flights and landings of the external stair.
i. 1800mm above and horizontally.
ii. 9m vertically below.
iii. 1100mm above the top landing of the stair (except where the stair leads from basement to ground level).
c. Fire resisting construction (minimum RE 30) should be provided for any part of the building (including doors) within 1800mm of the escape route from the foot of the stair to a place of safety. This does not apply if there are alternative escape routes from the foot of the external escape stair.
d. Glazing in areas of fire resisting construction should be fixed shut and fire resisting (in terms of integrity but not insulation) (minimum E 30).
e. Stairs more than 6m in height above ground level (e.g. where they are provided above a podium) should be protected from adverse weather. Protection should prevent the build-up of snow or ice but does not require full enclosure.
In buildings with more than three storeys above the ground storey, stairs may serve the flats and other occupancies if all of the following apply.
a. The flat is ancillary to the main use of the building.
b. The flat has an independent alternative escape route.
c. The stair is separated from occupancies on lower storeys by a protected lobby (minimum REI 30) at each of those storeys.
d. The stair enclosure has at least the same standard of fire resistance as the structural elements of the building (see Appendix B, Table B4); if the stair is a firefighting stair, it should comply with the provisions in Section 15 (see also paragraph 3.60).
e. Any automatic fire detection and alarm system fitted in the main part of the building also covers all flats.
f. Any security measures in any parts of the building do not prevent escape at all material times.
building contract
Guidance on cables for large and complex buildings is given in BS 5839-1, BS 5266-1 and BS 8519.
building control
Work should comply with Parts K and L of Schedule 1 to the Building Regulations. When complete, the building should comply with other applicable parts of Schedule 1 to at least the same level as before.
Paragraphs 3.6 to 3.23 deal with the means of escape within each flat. Paragraphs 3.25 to 3.89 deal with the means of escape in common areas of the building (including mixed use buildings in paragraphs 3.76 and 3.77). Guidance for live/work units is given in paragraph 3.24.
Guidance on cables for large and complex buildings is given in BS 5839-1, BS 5266-1 and BS 8519.
building control bodies
Smoke alarms should be mains operated and conform to BS EN 14604.
Heat alarms should be mains operated and conform to BS 5446-2.
Escape lighting should conform to BS 5266-1.
In a converted building with a maximum of three storeys, a minimum REI 30 fire resistance could be accepted for elements of structure if the means of escape conform to the provisions of Section 3.
building regulations advisory committee (brac)
Means of warning and escape
B1.The building shall be designed and constructed so that there are appropriate provisions for the early warning of fire, and appropriate means of escape in case of fire from the building to a place of safety outside the building capable of being safely and effectively used at all material times.
Requirement B1 does not apply to any prison provided under section 33 of the Prison Act 1952
(a) (power to provide prisons, etc.).
(a) 1952 c. 52; section 33 was amended by section 100 of the Criminal Justice and Public Order Act 1994 (c. 33) and by S.I. 1963/597.
building regulations compliance certificate
Fire detection and alarm systems must be properly designed, installed and maintained. A design,
installation and commissioning certificate should be provided for fire detection and alarm systems.
Third party certification schemes for fire protection products and related services are an effective
means of providing assurances of quality, reliability and safety.
Work should comply with Parts K and L of Schedule 1 to the Building Regulations. When complete, the building should comply with other applicable parts of Schedule 1 to at least the same level as before.
building safety
Every doorway or other exit providing access to a means of escape, other than exits in ordinary use (e.g. main entrances), should be distinctively and conspicuously marked by an exit sign in accordance with BS ISO 3864-1 and BS 5499-4. For this reason, blocks of flats with a single stair in regular use would not usually require any fire exit signage.
Advice on fire safety signs, including emergency escape signs, is given in the HSE publication Safety Signs and Signals: Guidance on Regulations.
Some buildings may require additional signs to comply with other legislation.
Gas service and installation pipes and meters should not be within a protected stairway, unless installed in accordance with the Pipelines Safety Regulations 1996 and the Gas Safety (Installation and Use) Regulations 1998.
building work
Where escape from a dwellinghouse is to an enclosed space with exit only possible through other buildings (e.g. a courtyard or back garden), the length of the space should exceed whichever is the greater of the following.
a. The height of the dwellinghouse above ground level (x).
b. Where a rear extension is provided, the height of the extension (y).
See para 2.10
cavity barrier
Smoke alarms should be mains operated and conform to BS EN 14604.
If windows are replaced, it may be necessary to provide cavity barriers around the opening in accordance with Section 5.
Smoke vents should comply with one of the following.
a. They should be located on an external wall with minimum free area of 1.5m2.
b. They should discharge into a vertical smoke shaft, closed at the base, that meets all of the following criteria.
i. The shaft should conform to the following conditions.
• Have a minimum cross-sectional area of 1.5m2 (minimum dimension 0.85m in any direction).
• Open at roof level, minimum 0.5m above any surrounding structures within 2m of it horizontally.
• Extend a minimum of 2.5m above the ceiling of the highest storey served by the shaft.
ii. The free area of all the following vents should be a minimum of 1m2 in the following places.
• From the corridor or lobby into the shaft.
• At the opening at the head of the shaft.
• At all internal locations within the shaft (e.g. safety grilles).
iii. The smoke shaft should be constructed from a class A1 material. All vents should either be a fire doorset (see Appendix C, Table C1, item 2.e for minimum fire resistance) or fitted with a smoke control damper achieving the same period of fire resistance and designed to operate as described below. The shaft should be vertical from base to head, with a maximum of 4m at a maximum inclined angle of 30 degrees.
iv. If smoke is detected in the common corridor or lobby, both of the following should occur.
• Simultaneous opening of vents on the storey where the fire is located, at the top of the smoke shaft and to the stair.
• Vents from the corridors or lobbies on all other storeys should remain closed, even if smoke is subsequently detected on storeys other than where the fire is located.
Guidance on the design of smoke control systems that use pressure differentials is available in BS EN 12101-6.
Where a stair serves an enclosed car park or place of special fire hazard, the lobby or corridor should have a minimum 0.4m2 of permanent ventilation or be protected from the ingress of smoke by a mechanical smoke control system.
NOTE: For refuse chutes and storage see paragraphs 3.55 to 3.58.
cavity stop
If windows are replaced, it may be necessary to provide cavity barriers around the opening in accordance with Section 5.
cavity width
If windows are replaced, it may be necessary to provide cavity barriers around the opening in accordance with Section 5.
A stair of acceptable width for everyday use will be sufficient for escape purposes. If it is also a firefighting stair, it should be at least 1100mm wide. The width is the clear width between the walls or balustrades. Any handrails and strings intruding into that width by a maximum of 100mm on each side may be ignored.
ceiling
To limit potential damage to cables in protected circuits, all of the following should apply.
a. Cables should be sufficiently robust.
b. Cable routes should be carefully selected and/or physically protected in areas where cables may be exposed to damage.
c. Methods of cable support should be class A1 rated and offer at least the same integrity as the cable. They should maintain circuit integrity and hold cables in place when exposed to fire.
cellar
Basement storeys containing habitable rooms should have one of the following.
a. An emergency escape window or external door providing escape from the basement (paragraph 2.10).
b. A protected stairway (paragraph 2.5a) leading from the basement to a final exit.
See para 3.21
NOTE: This only applies where at least one storey is more than 4.5m above ground level.
Alternative exit
Bathroom
ENTRANCE LEVEL
LEVEL(S) ABOVE OR BELOW ENTRANCE LEVEL
Basement storeys containing habitable rooms should have one of the following.
a. An emergency escape window or external door providing escape from the basement (see paragraph 3.6).
b. A protected stairway (minimum REI 30) leading from the basement to a final exit.
change control procedures
Guidance on the design of smoke control systems that use pressure differentials is available in BS EN 12101-6.
circulation space
Smoke alarms should be mains operated and conform to BS EN 14604.
Heat alarms should be mains operated and conform to BS 5446-2.
Smoke alarms should be provided in the circulation spaces of the dwelling in accordance with
paragraphs 1.1 to 1.4.
NOTE: This does not apply where inner rooms are provided (see paragraph 2.11 for inner room
requirements).
Basement storeys containing habitable rooms should have one of the following.
a. An emergency escape window or external door providing escape from the basement (paragraph 2.10).
b. A protected stairway (paragraph 2.5a) leading from the basement to a final exit.
See para 2.5
Fire resisting construction minimum REI 30
Fd Fire doorset minimum E 20
See para 2.5
Alternative cavity barrier arrangements in roof space over protected stairway in a house with a storey more than 4.5m above ground level
Where escape from a dwellinghouse is to an enclosed space with exit only possible through other buildings (e.g. a courtyard or back garden), the length of the space should exceed whichever is the greater of the following.
a. The height of the dwellinghouse above ground level (x).
b. Where a rear extension is provided, the height of the extension (y).
See para 2.10
All habitable rooms (excluding kitchens) should have either of the following.
a. An emergency escape window or external door, as described in paragraph 3.6.
b. In multi-storey flats, direct access to a protected internal stairway (minimum REI 30) leading to an exit from the flat.
Every doorway or other exit providing access to a means of escape, other than exits in ordinary use (e.g. main entrances), should be distinctively and conspicuously marked by an exit sign in accordance with BS ISO 3864-1 and BS 5499-4. For this reason, blocks of flats with a single stair in regular use would not usually require any fire exit signage.
Advice on fire safety signs, including emergency escape signs, is given in the HSE publication Safety Signs and Signals: Guidance on Regulations.
Some buildings may require additional signs to comply with other legislation.
Refuse chutes and rooms for storing refuse should meet both of the following conditions.
a. Be separated from other parts of the building by fire resisting construction (minimum REI 30 in buildings with a top storey up to 5m above ground level; otherwise REI 60).
b. Not be situated within a protected stairway or protected lobby.
The construction separating two adjacent protected stairways (or exit passageways leading to different final exits) should be imperforate.
A protected stairway should not be used for anything else, except a lift well or electricity meters.
Every protected stairway should lead to a final exit, either directly or via a protected exit passageway. Any protected exit corridor or stair should have the same standard of fire resistance and lobby protection as the stair it serves.
Basement storeys containing habitable rooms should have one of the following.
a. An emergency escape window or external door providing escape from the basement (see paragraph 3.6).
b. A protected stairway (minimum REI 30) leading from the basement to a final exit.
clear access route
Escape routes should have a minimum clear headroom of 2m. The only projections allowed below this height are door frames.
clear opening width
Where it is undesirable to replace existing doors because of historical or architectural merit, the possibility of retaining, and where necessary upgrading, them should be investigated.
Escape routes should have a minimum clear headroom of 2m. The only projections allowed below this height are door frames.
A stair of acceptable width for everyday use will be sufficient for escape purposes. If it is also a firefighting stair, it should be at least 1100mm wide. The width is the clear width between the walls or balustrades. Any handrails and strings intruding into that width by a maximum of 100mm on each side may be ignored.
clear turning circle
Escape routes should have a minimum clear headroom of 2m. The only projections allowed below this height are door frames.
clear width
A stair of acceptable width for everyday use will be sufficient for escape purposes. If it is also a firefighting stair, it should be at least 1100mm wide. The width is the clear width between the walls or balustrades. Any handrails and strings intruding into that width by a maximum of 100mm on each side may be ignored.
closable opening
If windows are replaced, it may be necessary to provide cavity barriers around the opening in accordance with Section 5.
combustion appliance (or appliance)
Heat alarms should be mains operated and conform to BS 5446-2.
commissioning
Each flat in a block should have alarms as set out in paragraphs 1.1 to 1.4. With effective compartmentation, a communal fire alarm system is not normally needed. In some buildings, detectors in common parts of the building may need to operate smoke control or other fire protection systems but do not usually sound an audible warning.
The fire detection and alarm systems in flats should connect to a central monitoring point or alarm
receiving centre. The systems should alert the warden or supervisor and identify the individual flat
where a fire has been detected.
Fire detection and alarm systems must be properly designed, installed and maintained. A design,
installation and commissioning certificate should be provided for fire detection and alarm systems.
Third party certification schemes for fire protection products and related services are an effective
means of providing assurances of quality, reliability and safety.
Fire detection and alarm systems sometimes trigger other systems. The interface between systems
must be reliable. Particular care should be taken if the interface is facilitated via another system.
Where any part of BS 7273 applies to the triggering of other systems, the recommendations of that
part of BS 7273 should be followed.
Smoke and heat alarms should have a standby power supply, such as a battery (rechargeable
or non-rechargeable) or capacitor. More information on power supplies is given in clause 15 of
BS 5839-6.
NOTE: The term ‘fire alarm system’ describes the combination of components for giving an audible
and/or other perceptible warning of fire.
NOTE: In this document, the term ‘fire detection system’ describes any type of automatic sensor
network and associated control and indicating equipment. Sensors may be sensitive to smoke,
heat, gaseous combustion products or radiation. Automatic sprinkler systems can also be used to
operate a fire alarm system.
For systems circulating air only within an individual flat, take all of the following precautions.
a. Transfer grilles should not be fitted in any wall, door, floor or ceiling of the enclosure.
b. Any duct passing through the enclosure should be rigid steel. Joints between the ductwork and enclosure should be fire-stopped.
c. Ventilation ducts serving the enclosure should not serve any other areas.
d. Any system of mechanical ventilation which recirculates air and which serves both the stair and other areas should be designed to shut down on the detection of smoke within the system.
e. For ducted warm air heating systems, a room thermostat should be sited in the living room. It should be mounted at a height between 1370mm and 1830mm above the floor. The maximum setting should be 27°C.
NOTE: Ventilation ducts passing through compartment walls should comply with the guidance in Section 9.
Guidance on the design of smoke control systems that use pressure differentials is available in BS EN 12101-6.
common balcony
A large dwellinghouse has more than one storey, and at least one storey exceeds 200m2.
Where a flat roof forms part of a means of escape, it should comply with all of the following.
a. It should be part of the same building from which escape is being made.
b. The route across the roof should lead to a storey exit or external escape route.
c. The part of the roof (including its supporting structure) forming the escape route, and any opening within 3m of the escape route, should be of fire resisting construction (minimum REI 30).
A balcony or flat roof intended to form part of an escape route should be provided with guarding etc. in accordance with Approved Document K.
Where an existing window would be an escape window in a new dwellinghouse, and is big enough to be used for escape purposes, then the replacement should comply with one of the following.
a. The replacement window should be sized to provide at least the same potential for escape.
b. If the existing window was larger than required for escape purposes, the opening can be reduced to the minimum described in paragraph 2.10.
Dwellinghouses with one internal stair should comply with paragraphs 2.5 and 2.6. In dwellinghouses with more than one stair, the stairs should provide effective alternative means of escape. The stairs should be physically separated by either of the following.
a. Fire resisting construction (minimum REI 30).
b. More than one room.
Air circulation systems which circulate air within an individual dwellinghouse with a floor more than
4.5m above ground level should meet the guidance given in paragraph 2.9.
Separate guidance applies to means of escape within the flat and within the common parts of the building that lead to a place of safety. Flats at ground level are treated similarly to dwellinghouses. With increasing height, more complex provisions are needed.
NOTES:
1. This diagram does not apply where the gallery is provided with one of the following:
i. An alternative escape route
ii. An emergency escape window (where the gallery floor is not more than 4.5m above ground level).
2. Any cooking facilities within a room containing a gallery should comply with one of the following conditions:
i. Be enclosed with fire resisting construction
ii. Be remote from the stair to the gallery and positioned such that they do not prejudice escape from the gallery.
See para 3.13
Where a flat roof forms part of a means of escape, it should comply with all of the following.
a. It should be part of the same building from which escape is being made.
b. The route across the roof should lead to a storey exit or external escape route.
c. The part of the roof (including its supporting structure) forming the escape route, and any opening within 3m of the escape route, should be of fire resisting construction (minimum REI 30).
A balcony or flat roof intended to form part of an escape route should be provided with guarding etc. in accordance with Approved Document K.
For flats more than 4.5m above ground level, a balcony outside an alternative exit should be a common balcony meeting the conditions described in paragraph 3.22.
Any alternative exit from a flat should comply with all of the following.
a. It should be remote from the main entrance door to the flat.
b. It should lead to a final exit, via a common stair if necessary, through one of the following.
i. A door to an access corridor, access lobby or common balcony.
ii. An internal private stair leading to an access corridor, access lobby or common balcony at another level.
iii. A door to a common stair.
iv. A door to an external stair.
v. A door to an escape route over a flat roof.
Any access route leading to a final exit or common stair should comply with the provisions for means of escape in the common parts of a flat (see paragraph 3.25).
A person escaping through the common area, if confronted by the effects of a fire in another flat, should be able to turn away from it and make a safe escape via an alternative route.
From the flat entrance door, a single escape route is acceptable in either of the following cases.
a. The flat is on a storey served by a single common stair and both of the following apply.
i. Every flat is separated from the common stair by a protected lobby or common protected corridor (see Diagram 3.7).
ii. The maximum travel distance in Table 3.1, for escape in one direction only, is not exceeded.
b. The flat is in a dead end of a common corridor served by two (or more) common stairs and the maximum travel distance given in Table 3.1, for escape in one direction only, is not exceeded (Diagram 3.8).
Provisions are recommended to support a stay put evacuation strategy for blocks of flats. It is based on the principle that a fire is contained in the flat of origin and common escape routes are maintained relatively free from smoke and heat. It allows occupants, some of whom may require assistance to escape in the event of a fire, in other flats that are not affected to remain.
Sufficient protection to common means of escape is necessary to allow occupants to escape should they choose to do so or are instructed/aided to by the fire service. A higher standard of protection is therefore needed to ensure common escape routes remain available for a longer period than is provided in other buildings.
Where a storey or part of a building has multiple escape routes available, one may be over a flat roof that complies with all of the following.
a. It should be part of the same building from which escape is being made.
b. The route across the roof should lead to a storey exit or external escape route.
c. The part of the roof (including its supporting structure) forming the escape route, and any opening within 3m of the escape route, should be of fire resisting construction (minimum REI 30).
d. The route should be clearly defined and guarded by walls and/or protective barriers to protect against falling.
Where a storey or part of a building has multiple escape routes available, one may be over a flat roof that complies with all of the following.
d. The route should be clearly defined and guarded by walls and/or protective barriers to protect against falling.
Divide a common corridor connecting two or more storey exits with a fire doorset fitted with a self-closing device (minimum E 30 Sa). See Diagram 3.8. Associated screens should be fire resisting. Site doors so that smoke does not affect access to more than one stair.
Ancillary accommodation should not be located in, or entered from, a protected lobby or protected corridor forming the only common escape route on that storey.
A ramp forming part of an escape route should meet the provisions in Approved Document M. Any sloping floor or tier should have a pitch of not more than 35 degrees to the horizontal.
Escape stair lighting should be on a separate circuit from the electricity supply to any other part of the escape route.
The approach to rooms containing refuse chutes or for storing refuse should comply with one of the following conditions.
a. Be directly from the open air.
b. Be through a protected lobby with a minimum of 0.2m2 of permanent ventilation.
Access openings to refuse storage chambers should not be sited in the following areas.
a. Next to escape routes or final exits.
b. Near the windows of flats.
A building should provide access to more than one common stair if it does not meet the criteria for a single common stair (see paragraph 3.26 and 3.27).
Where more than one escape route is available from a storey (or part of a building), then some of the escape routes from that storey or part of the building may be by way of an external stair provided all of the following conditions are met:
a. There is a at least one internal escape stair from every part of each storey (excluding plant areas).
b. The stair serves a floor not more than 6m above either the ground level or a roof podium which is itself served by an independent protected stairway.
c. The stair meets the provisions in paragraph 3.68.
If a building does not meet the criteria of paragraph 3.28, an escape stair forming part of the only escape route from an upper storey should not continue down to serve a basement storey. The basement storey should be served by a separate escape stair.
Except in buildings described in paragraph 3.28, common stairs forming part of the only escape route from a flat should not serve any of the following.
a. Covered car park.
b. Boiler room.
c. Fuel storage space.
d. Other ancillary accommodation of similar fire risk.
Where a common stair is not part of the only escape route from a flat, it may also serve ancillary accommodation from which it is separated by a protected lobby or protected corridor (minimum REI 30).
common parts
Each flat in a block should have alarms as set out in paragraphs 1.1 to 1.4. With effective compartmentation, a communal fire alarm system is not normally needed. In some buildings, detectors in common parts of the building may need to operate smoke control or other fire protection systems but do not usually sound an audible warning.
In student residences that are designed and occupied as a block of flats, separate automatic detection should be provided in each self-contained flat where all of the following apply.
a. A group of up to six students shares the flat.
b. Each flat has its own entrance door.
c. The compartmentation principles for flats in Section 7 have been followed.
Where a total evacuation strategy is adopted, the alarm system should follow the guidance for buildings other than dwellings in Volume 2 of Approved Document B.
The fire detection and alarm systems in flats should connect to a central monitoring point or alarm
receiving centre. The systems should alert the warden or supervisor and identify the individual flat
where a fire has been detected.
Where a flat roof forms part of a means of escape, it should comply with all of the following.
a. It should be part of the same building from which escape is being made.
b. The route across the roof should lead to a storey exit or external escape route.
c. The part of the roof (including its supporting structure) forming the escape route, and any opening within 3m of the escape route, should be of fire resisting construction (minimum REI 30).
A balcony or flat roof intended to form part of an escape route should be provided with guarding etc. in accordance with Approved Document K.
Separate guidance applies to means of escape within the flat and within the common parts of the building that lead to a place of safety. Flats at ground level are treated similarly to dwellinghouses. With increasing height, more complex provisions are needed.
Where a flat roof forms part of a means of escape, it should comply with all of the following.
a. It should be part of the same building from which escape is being made.
b. The route across the roof should lead to a storey exit or external escape route.
c. The part of the roof (including its supporting structure) forming the escape route, and any opening within 3m of the escape route, should be of fire resisting construction (minimum REI 30).
A balcony or flat roof intended to form part of an escape route should be provided with guarding etc. in accordance with Approved Document K.
For flats more than 4.5m above ground level, a balcony outside an alternative exit should be a common balcony meeting the conditions described in paragraph 3.22.
The provisions in this section make the following assumptions.
a. Any fire is likely to be in a flat.
b. There is no reliance on external rescue.
c. Simultaneous evacuation of all flats is unlikely to be necessary due to compartmentation.
d. Fires in common parts of the building should not spread beyond the fabric in the immediate vicinity. In some cases, however, communal facilities exist that require additional measures to be taken.
Any alternative exit from a flat should comply with all of the following.
a. It should be remote from the main entrance door to the flat.
b. It should lead to a final exit, via a common stair if necessary, through one of the following.
i. A door to an access corridor, access lobby or common balcony.
ii. An internal private stair leading to an access corridor, access lobby or common balcony at another level.
iii. A door to a common stair.
iv. A door to an external stair.
v. A door to an escape route over a flat roof.
Any access route leading to a final exit or common stair should comply with the provisions for means of escape in the common parts of a flat (see paragraph 3.25).
A person escaping through the common area, if confronted by the effects of a fire in another flat, should be able to turn away from it and make a safe escape via an alternative route.
From the flat entrance door, a single escape route is acceptable in either of the following cases.
a. The flat is on a storey served by a single common stair and both of the following apply.
i. Every flat is separated from the common stair by a protected lobby or common protected corridor (see Diagram 3.7).
ii. The maximum travel distance in Table 3.1, for escape in one direction only, is not exceeded.
b. The flat is in a dead end of a common corridor served by two (or more) common stairs and the maximum travel distance given in Table 3.1, for escape in one direction only, is not exceeded (Diagram 3.8).
Provisions are recommended to support a stay put evacuation strategy for blocks of flats. It is based on the principle that a fire is contained in the flat of origin and common escape routes are maintained relatively free from smoke and heat. It allows occupants, some of whom may require assistance to escape in the event of a fire, in other flats that are not affected to remain.
Sufficient protection to common means of escape is necessary to allow occupants to escape should they choose to do so or are instructed/aided to by the fire service. A higher standard of protection is therefore needed to ensure common escape routes remain available for a longer period than is provided in other buildings.
Where a storey or part of a building has multiple escape routes available, one may be over a flat roof that complies with all of the following.
a. It should be part of the same building from which escape is being made.
b. The route across the roof should lead to a storey exit or external escape route.
c. The part of the roof (including its supporting structure) forming the escape route, and any opening within 3m of the escape route, should be of fire resisting construction (minimum REI 30).
d. The route should be clearly defined and guarded by walls and/or protective barriers to protect against falling.
Where a storey or part of a building has multiple escape routes available, one may be over a flat roof that complies with all of the following.
d. The route should be clearly defined and guarded by walls and/or protective barriers to protect against falling.
Common corridors should be protected corridors. The wall between each flat and the corridor should be a compartment wall (minimum REI 30 where the top storey is up to 5m above ground level, otherwise REI 60).
Divide a common corridor connecting two or more storey exits with a fire doorset fitted with a self-closing device (minimum E 30 Sa). See Diagram 3.8. Associated screens should be fire resisting. Site doors so that smoke does not affect access to more than one stair.
A fire doorset (minimum E 30 Sa) fitted with a self-closing device (and fire resisting screen, where required) should separate the dead-end portion of a common corridor from the rest of the corridor (Diagrams 3.7a, 3.8b and 3.8c).
Ancillary accommodation should not be located in, or entered from, a protected lobby or protected corridor forming the only common escape route on that storey.
Paragraphs 3.6 to 3.23 deal with the means of escape within each flat. Paragraphs 3.25 to 3.89 deal with the means of escape in common areas of the building (including mixed use buildings in paragraphs 3.76 and 3.77). Guidance for live/work units is given in paragraph 3.24.
A ramp forming part of an escape route should meet the provisions in Approved Document M. Any sloping floor or tier should have a pitch of not more than 35 degrees to the horizontal.
Despite the provisions described, it is probable that some smoke will get into the common corridor or lobby from a fire in a flat.
There should therefore be some means of ventilating the common corridors/lobbies to control smoke and so protect the common stairs. This means of ventilation offers additional protection to that provided by the fire doors to the stair, as well as some protection to the corridors/lobbies.
Ventilation can be natural (paragraphs 3.50 to 3.53) or mechanical (paragraph 3.54).
A building should provide access to more than one common stair if it does not meet the criteria for a single common stair (see paragraph 3.26 and 3.27).
Access to an external escape stair may be via a flat roof, provided the flat roof meets the requirements of paragraph 3.30.
Except in buildings described in paragraph 3.28, common stairs forming part of the only escape route from a flat should not serve any of the following.
a. Covered car park.
b. Boiler room.
c. Fuel storage space.
d. Other ancillary accommodation of similar fire risk.
Where a common stair is not part of the only escape route from a flat, it may also serve ancillary accommodation from which it is separated by a protected lobby or protected corridor (minimum REI 30).
In buildings with more than three storeys above the ground storey, stairs may serve the flats and other occupancies if all of the following apply.
a. The flat is ancillary to the main use of the building.
b. The flat has an independent alternative escape route.
c. The stair is separated from occupancies on lower storeys by a protected lobby (minimum REI 30) at each of those storeys.
d. The stair enclosure has at least the same standard of fire resistance as the structural elements of the building (see Appendix B, Table B4); if the stair is a firefighting stair, it should comply with the provisions in Section 15 (see also paragraph 3.60).
e. Any automatic fire detection and alarm system fitted in the main part of the building also covers all flats.
f. Any security measures in any parts of the building do not prevent escape at all material times.
common space
Smoke alarms should be provided in the circulation spaces of the dwelling in accordance with
paragraphs 1.1 to 1.4.
NOTE: This does not apply where inner rooms are provided (see paragraph 2.11 for inner room
requirements).
Common corridors should be protected corridors. The wall between each flat and the corridor should be a compartment wall (minimum REI 30 where the top storey is up to 5m above ground level, otherwise REI 60).
common stair
A large dwellinghouse has more than one storey, and at least one storey exceeds 200m2.
A large dwellinghouse has more than one storey, and at least one storey exceeds 200m2.
Any external escape stair should meet all of the following conditions (Diagram 2.7).
a. Doors to the stair should be fire resisting (minimum E 30), except for a single exit door from the building to the top landing of a downward-leading external stair.
b. Fire resisting construction (minimum RE 30) is required for the building envelope within the following zones, measured from the flights and landings of the external stair.
i. 1800mm horizontally.
ii. 9m vertically below.
iii. 1100mm above the top landing of the stair (except where the stair leads from basement to ground level).
c. Fire resisting construction (minimum RE 30) should be provided for any part of the building (including doors) within 1800mm of the escape route from the foot of the stair to a place of safety. This does not apply if there are alternative escape routes from the foot of the external escape stair.
d. Stairs more than 6m in height should be protected from adverse weather. Protection should prevent the build-up of snow or ice but does not require full enclosure.
e. Glazing in areas of fire resisting construction should be fixed shut and fire resisting (in terms of integrity, but not insulation) (minimum E 30).
See Diagram 2.1b. Where served by only one stair, all habitable rooms (excluding kitchens) should have either of the following.
a. An emergency escape window or external door, as described in paragraph 2.10.
b. Direct access to a protected stairway, as described in paragraph 2.5a.
See Diagram 2.1b. Where served by only one stair, all habitable rooms (excluding kitchens) should have either of the following.
a. An emergency escape window or external door, as described in paragraph 2.10.
b. Direct access to a protected stairway, as described in paragraph 2.5a.
Two rooms may be served by a single window. A door between the rooms should provide access to the window without passing through the stair enclosure. Both rooms should have their own access to the internal stair.
Two rooms may be served by a single window. A door between the rooms should provide access to the window without passing through the stair enclosure. Both rooms should have their own access to the internal stair.
Dwellinghouses with one internal stair should comply with paragraphs 2.5 and 2.6. In dwellinghouses with more than one stair, the stairs should provide effective alternative means of escape. The stairs should be physically separated by either of the following.
a. Fire resisting construction (minimum REI 30).
b. More than one room.
Dwellinghouses with one internal stair should comply with paragraphs 2.5 and 2.6. In dwellinghouses with more than one stair, the stairs should provide effective alternative means of escape. The stairs should be physically separated by either of the following.
a. Fire resisting construction (minimum REI 30).
b. More than one room.
A passenger lift serving any storey more than 4.5m above ground level should be in either of the following.
a. The enclosure to the protected stairway, as described in paragraph 2.5.
b. A fire resisting lift shaft (minimum REI 30).
Separate guidance applies to means of escape within the flat and within the common parts of the building that lead to a place of safety. Flats at ground level are treated similarly to dwellinghouses. With increasing height, more complex provisions are needed.
NOTES:
1. If travel distance is measured to a stair lobby, the lobby must not provide direct access to any storage room, flat or other space containing a fire hazard.
2. In the case of a small single stair building in accordance with Diagram 3.9, this is reduced to 4.5m.
3. Does not apply if all flats on a storey have independent alternative means of escape.
4. Sheltered housing may require reduced maximum travel distances.
No fire resistance required for door
1100mm zone above top landing
1100mm zone above top landing
6m maximum height of stair
Fire resisting window (minimum RE30)
1800mm zone of fire resisting construction at side of stair
Fire doorset (minimum E30)
Ground level or a roof or podium served by an independent stairway
6m maximum height of stair without weather protection
9m zone of fire resisting construction below stair
Ground level or a roof or podium served by an independent stairway
See para 3.68
No fire resistance required for door
1100mm zone above top landing
1100mm zone above top landing
6m maximum height of stair
Fire resisting window (minimum RE30)
1800mm zone of fire resisting construction at side of stair
Fire doorset (minimum E30)
Ground level or a roof or podium served by an independent stairway
6m maximum height of stair without weather protection
9m zone of fire resisting construction below stair
Ground level or a roof or podium served by an independent stairway
See para 3.68
For flats more than 4.5m above ground level, a balcony outside an alternative exit should be a common balcony meeting the conditions described in paragraph 3.22.
For flats more than 4.5m above ground level, a balcony outside an alternative exit should be a common balcony meeting the conditions described in paragraph 3.22.
Two rooms may be served by a single escape window. A door between rooms should provide access to the escape window without passing through the stair enclosure. Both rooms should have their own access to the internal stair.
Two rooms may be served by a single escape window. A door between rooms should provide access to the escape window without passing through the stair enclosure. Both rooms should have their own access to the internal stair.
Any alternative exit from a flat should comply with all of the following.
a. It should be remote from the main entrance door to the flat.
b. It should lead to a final exit, via a common stair if necessary, through one of the following.
i. A door to an access corridor, access lobby or common balcony.
ii. An internal private stair leading to an access corridor, access lobby or common balcony at another level.
iii. A door to a common stair.
iv. A door to an external stair.
v. A door to an escape route over a flat roof.
Any access route leading to a final exit or common stair should comply with the provisions for means of escape in the common parts of a flat (see paragraph 3.25).
Any alternative exit from a flat should comply with all of the following.
a. It should be remote from the main entrance door to the flat.
b. It should lead to a final exit, via a common stair if necessary, through one of the following.
i. A door to an access corridor, access lobby or common balcony.
ii. An internal private stair leading to an access corridor, access lobby or common balcony at another level.
iii. A door to a common stair.
iv. A door to an external stair.
v. A door to an escape route over a flat roof.
Any access route leading to a final exit or common stair should comply with the provisions for means of escape in the common parts of a flat (see paragraph 3.25).
A person escaping through the common area, if confronted by the effects of a fire in another flat, should be able to turn away from it and make a safe escape via an alternative route.
From the flat entrance door, a single escape route is acceptable in either of the following cases.
a. The flat is on a storey served by a single common stair and both of the following apply.
i. Every flat is separated from the common stair by a protected lobby or common protected corridor (see Diagram 3.7).
ii. The maximum travel distance in Table 3.1, for escape in one direction only, is not exceeded.
b. The flat is in a dead end of a common corridor served by two (or more) common stairs and the maximum travel distance given in Table 3.1, for escape in one direction only, is not exceeded (Diagram 3.8).
From the flat entrance door, a single escape route is acceptable in either of the following cases.
a. The flat is on a storey served by a single common stair and both of the following apply.
i. Every flat is separated from the common stair by a protected lobby or common protected corridor (see Diagram 3.7).
ii. The maximum travel distance in Table 3.1, for escape in one direction only, is not exceeded.
b. The flat is in a dead end of a common corridor served by two (or more) common stairs and the maximum travel distance given in Table 3.1, for escape in one direction only, is not exceeded (Diagram 3.8).
Provisions are recommended to support a stay put evacuation strategy for blocks of flats. It is based on the principle that a fire is contained in the flat of origin and common escape routes are maintained relatively free from smoke and heat. It allows occupants, some of whom may require assistance to escape in the event of a fire, in other flats that are not affected to remain.
Sufficient protection to common means of escape is necessary to allow occupants to escape should they choose to do so or are instructed/aided to by the fire service. A higher standard of protection is therefore needed to ensure common escape routes remain available for a longer period than is provided in other buildings.
An escape route should not pass through one stair enclosure to reach another. It may pass through a protected lobby (minimum REI 30) of one stair to reach another.
An escape route should not pass through one stair enclosure to reach another. It may pass through a protected lobby (minimum REI 30) of one stair to reach another.
Divide a common corridor connecting two or more storey exits with a fire doorset fitted with a self-closing device (minimum E 30 Sa). See Diagram 3.8. Associated screens should be fire resisting. Site doors so that smoke does not affect access to more than one stair.
Divide a common corridor connecting two or more storey exits with a fire doorset fitted with a self-closing device (minimum E 30 Sa). See Diagram 3.8. Associated screens should be fire resisting. Site doors so that smoke does not affect access to more than one stair.
Escape stair lighting should be on a separate circuit from the electricity supply to any other part of the escape route.
Despite the provisions described, it is probable that some smoke will get into the common corridor or lobby from a fire in a flat.
There should therefore be some means of ventilating the common corridors/lobbies to control smoke and so protect the common stairs. This means of ventilation offers additional protection to that provided by the fire doors to the stair, as well as some protection to the corridors/lobbies.
Ventilation can be natural (paragraphs 3.50 to 3.53) or mechanical (paragraph 3.54).
In single stair buildings, smoke vents on the storey where the fire is initiated, and the vent at the head of the stair, should be activated by smoke detectors in the common parts.
In buildings with more than one stair, smoke vents may be activated manually. The control system should open the vent at the head of the stair before, or at the same time as, the vent on the storey where the fire is located. Smoke detection is not required for ventilation purposes in this instance.
A building should provide access to more than one common stair if it does not meet the criteria for a single common stair (see paragraph 3.26 and 3.27).
A building should provide access to more than one common stair if it does not meet the criteria for a single common stair (see paragraph 3.26 and 3.27).
See para 3.21
NOTE: This only applies where at least one storey is more than 4.5m above ground level.
Fire doorset
Fire resisting stair enclosure(minimum REI 30)
Alternative exit
See para 3.21
NOTE: This only applies where at least one storey is more than 4.5m above ground level.
Fire doorset
Fire resisting stair enclosure(minimum REI 30)
Alternative exit
A stair of acceptable width for everyday use will be sufficient for escape purposes. If it is also a firefighting stair, it should be at least 1100mm wide. The width is the clear width between the walls or balustrades. Any handrails and strings intruding into that width by a maximum of 100mm on each side may be ignored.
Section 7 provides guidance on avoiding the spread of fire between storeys. For a stair that is also a firefighting stair, guidance in Section 15 should be followed.
Every common stair should be a protected stairway, within a fire resisting enclosure (minimum REI 30).
Every common stair should be a protected stairway, within a fire resisting enclosure (minimum REI 30).
Flats may be served by an external stair if the provisions in paragraphs 3.66 to 3.69 are followed.
Flats may be served by an external stair if the provisions in paragraphs 3.66 to 3.69 are followed.
Where a storey (or part of a building) is served by a single access stair, that stair may be external provided both of the following conditions are met.
a. The stair serves a floor not more than 6m above the ground level.
b. The stair meets the provisions in paragraph 3.62.
Where a storey (or part of a building) is served by a single access stair, that stair may be external provided both of the following conditions are met.
a. The stair serves a floor not more than 6m above the ground level.
b. The stair meets the provisions in paragraph 3.62.
Where more than one escape route is available from a storey (or part of a building), then some of the escape routes from that storey or part of the building may be by way of an external stair provided all of the following conditions are met:
a. There is a at least one internal escape stair from every part of each storey (excluding plant areas).
b. The stair serves a floor not more than 6m above either the ground level or a roof podium which is itself served by an independent protected stairway.
c. The stair meets the provisions in paragraph 3.68.
Where more than one escape route is available from a storey (or part of a building), then some of the escape routes from that storey or part of the building may be by way of an external stair provided all of the following conditions are met:
a. There is a at least one internal escape stair from every part of each storey (excluding plant areas).
b. The stair serves a floor not more than 6m above either the ground level or a roof podium which is itself served by an independent protected stairway.
c. The stair meets the provisions in paragraph 3.68.
Any external escape stair should meet all of the following conditions (Diagram 3.11).
a. Doors to the stair should be fire resisting (minimum E 30) and be fitted with a self-closing device, except for a single exit door from the building to the top landing of a downward-leading external stair, provided it is the only door onto the landing.
b. Fire resisting construction (minimum RE 30) is required for the building envelope within the following zones, measured from the flights and landings of the external stair.
i. 1800mm above and horizontally.
ii. 9m vertically below.
iii. 1100mm above the top landing of the stair (except where the stair leads from basement to ground level).
c. Fire resisting construction (minimum RE 30) should be provided for any part of the building (including doors) within 1800mm of the escape route from the foot of the stair to a place of safety. This does not apply if there are alternative escape routes from the foot of the external escape stair.
d. Glazing in areas of fire resisting construction should be fixed shut and fire resisting (in terms of integrity but not insulation) (minimum E 30).
e. Stairs more than 6m in height above ground level (e.g. where they are provided above a podium) should be protected from adverse weather. Protection should prevent the build-up of snow or ice but does not require full enclosure.
Access to an external escape stair may be via a flat roof, provided the flat roof meets the requirements of paragraph 3.30.
If a building does not meet the criteria of paragraph 3.28, an escape stair forming part of the only escape route from an upper storey should not continue down to serve a basement storey. The basement storey should be served by a separate escape stair.
If a building does not meet the criteria of paragraph 3.28, an escape stair forming part of the only escape route from an upper storey should not continue down to serve a basement storey. The basement storey should be served by a separate escape stair.
Where multiple escape stairs serve the upper storeys, only one needs to end at ground level. Other stairs may connect with the basement storeys if there is a protected lobby or a protected corridor between the stairs and accommodation at each basement level.
Where multiple escape stairs serve the upper storeys, only one needs to end at ground level. Other stairs may connect with the basement storeys if there is a protected lobby or a protected corridor between the stairs and accommodation at each basement level.
Except in buildings described in paragraph 3.28, common stairs forming part of the only escape route from a flat should not serve any of the following.
a. Covered car park.
b. Boiler room.
c. Fuel storage space.
d. Other ancillary accommodation of similar fire risk.
Except in buildings described in paragraph 3.28, common stairs forming part of the only escape route from a flat should not serve any of the following.
a. Covered car park.
b. Boiler room.
c. Fuel storage space.
d. Other ancillary accommodation of similar fire risk.
Where a common stair is not part of the only escape route from a flat, it may also serve ancillary accommodation from which it is separated by a protected lobby or protected corridor (minimum REI 30).
Where a common stair is not part of the only escape route from a flat, it may also serve ancillary accommodation from which it is separated by a protected lobby or protected corridor (minimum REI 30).
Where a stair serves an enclosed car park or place of special fire hazard, the lobby or corridor should have a minimum 0.4m2 of permanent ventilation or be protected from the ingress of smoke by a mechanical smoke control system.
NOTE: For refuse chutes and storage see paragraphs 3.55 to 3.58.
In buildings with a maximum of three storeys above the ground storey, stairs may serve both flats and other occupancies, provided that the stairs are separated from each occupancy by protected lobbies (minimum REI 30) at each storey.
In buildings with a maximum of three storeys above the ground storey, stairs may serve both flats and other occupancies, provided that the stairs are separated from each occupancy by protected lobbies (minimum REI 30) at each storey.
In buildings with more than three storeys above the ground storey, stairs may serve the flats and other occupancies if all of the following apply.
a. The flat is ancillary to the main use of the building.
b. The flat has an independent alternative escape route.
c. The stair is separated from occupancies on lower storeys by a protected lobby (minimum REI 30) at each of those storeys.
d. The stair enclosure has at least the same standard of fire resistance as the structural elements of the building (see Appendix B, Table B4); if the stair is a firefighting stair, it should comply with the provisions in Section 15 (see also paragraph 3.60).
e. Any automatic fire detection and alarm system fitted in the main part of the building also covers all flats.
f. Any security measures in any parts of the building do not prevent escape at all material times.
In single stair buildings, electricity meters should be in securely locked cupboards. Cupboards should be separated from the escape route by fire resisting construction.
a. SMALL SINGLE STAIR BUILDING
*If smoke control is provided in the lobby, the travel distance can be increased to 7.5m maximum(see Diagram 3.7, example b).
b. SMALL SINGLE STAIR BUILDING WITH NO MORE THAN TWO FLATS PER STOREY
The door between stair and lobby should be free from security fastenings.
If the flats have protected entrance halls, the lobby between the common stair and flat entrance is not essential.
NOTES:
1. The arrangements shown also apply to the top storey.
2. If the travel distance across the lobby in diagram (a) exceeds 4.5m, Diagram 3.7 applies.
3. Where,in Diagram (b), the lobby between the common stair and the dwelling is omitted in smal lsingle stair buildings, an automatic opening vent with a free area of at least 1m2 is required at the top of the stair,which is operated automatically on detection of smoke at any storey in the stair.
4. For further guidance on the fire rating of the fire doorsets from the corridor to the flat and/or stairway refer to Appendix C, Table C1.
Fire resisting construction
Openable vent at high level for fire service use (1.0m2 minimum free area); see paragraph 3.28eSee para 3.28
Diagram 3.9
communal or common (area facilities or entrances)
For flats more than 4.5m above ground level, a balcony outside an alternative exit should be a common balcony meeting the conditions described in paragraph 3.22.
See para 3.18
Flat entrance
Kitchen area
Bath
A building should provide access to more than one common stair if it does not meet the criteria for a single common stair (see paragraph 3.26 and 3.27).
compartment (fire)
Each flat in a block should have alarms as set out in paragraphs 1.1 to 1.4. With effective compartmentation, a communal fire alarm system is not normally needed. In some buildings, detectors in common parts of the building may need to operate smoke control or other fire protection systems but do not usually sound an audible warning.
A large dwellinghouse of two storeys (excluding basement storeys) should be fitted with a Grade A
Category LD3 fire detection and alarm system, as described in BS 5839-6.
A large dwellinghouse of three or more storeys (excluding basement storeys) should be fitted with
a Grade A Category LD2 fire detection and alarm system as described in BS 5839-6.
See para 2.6
Example of alternative exit in para 2.6(a) (see definition in Appendix A)
Where access from any habitable room to the entrance hall or flat entrance is impossible without passing through another room, all of the following conditions should be met (Diagram 3.4).
a. Bedrooms should be separated from living accommodation by fire resisting construction (minimum REI 30) and fire doorsets (minimum E 20).
b. The alternative exit should be in the part of the flat that contains the bedrooms.
A protected circuit to operate equipment during a fire should achieve all of the following.
a. Cables should achieve PH 30 classification when tested in accordance with BS EN 50200 (incorporating Annex E) or an equivalent standard.
b. It should only pass through parts of the building in which the fire risk is negligible.
c. It should be separate from any circuit provided for another purpose.
In mixed use buildings, separate means of escape should be provided from any storeys or parts of storeys used for the ‘residential’ or ‘assembly and recreation’ purpose groups (purpose groups 1, 2 and 5), other than in the case of certain small buildings or buildings in which the residential accommodation is ancillary (see paragraphs 3.76 and 3.77)
Refuse chutes and rooms for storing refuse should meet both of the following conditions.
a. Be separated from other parts of the building by fire resisting construction (minimum REI 30 in buildings with a top storey up to 5m above ground level; otherwise REI 60).
b. Not be situated within a protected stairway or protected lobby.
Where more than one escape route is available from a storey (or part of a building), then some of the escape routes from that storey or part of the building may be by way of an external stair provided all of the following conditions are met:
a. There is a at least one internal escape stair from every part of each storey (excluding plant areas).
b. The stair serves a floor not more than 6m above either the ground level or a roof podium which is itself served by an independent protected stairway.
c. The stair meets the provisions in paragraph 3.68.
Except in buildings described in paragraph 3.28, common stairs forming part of the only escape route from a flat should not serve any of the following.
a. Covered car park.
b. Boiler room.
c. Fuel storage space.
d. Other ancillary accommodation of similar fire risk.
In buildings with more than three storeys above the ground storey, stairs may serve the flats and other occupancies if all of the following apply.
a. The flat is ancillary to the main use of the building.
b. The flat has an independent alternative escape route.
c. The stair is separated from occupancies on lower storeys by a protected lobby (minimum REI 30) at each of those storeys.
d. The stair enclosure has at least the same standard of fire resistance as the structural elements of the building (see Appendix B, Table B4); if the stair is a firefighting stair, it should comply with the provisions in Section 15 (see also paragraph 3.60).
e. Any automatic fire detection and alarm system fitted in the main part of the building also covers all flats.
f. Any security measures in any parts of the building do not prevent escape at all material times.
compartment wall
Common corridors should be protected corridors. The wall between each flat and the corridor should be a compartment wall (minimum REI 30 where the top storey is up to 5m above ground level, otherwise REI 60).
If a loadbearing wall is any of the following, guidance in other sections may also apply.
a. A compartment wall (including a wall common to two buildings): Section 7.
b. Enclosing a place of special fire hazard: Section 7.
c. Protecting a means of escape: Sections 2 and 3.
d. An external wall: Sections 10 and 11.
e. Enclosing a firefighting shaft: Section 15.
compartment wall or floor
Fire resisting window(minimum RE30)
No fire resistance required for door
1100mm zone above top landing
6m max. height without weather protection
1800mm zone of fire resisting construction at side of stairway
Fire doorset(minimum E30)
See para 2.17
Fire resisting window(minimum RE30)
No fire resistance required for door
1100mm zone above top landing
6m max. height without weather protection
1800mm zone of fire resisting construction at side of stairway
Fire doorset(minimum E30)
See para 2.17
Configurations of stairs and external wall
Fire resisting construction
Fire resisting construction of adjacent building enclosure of protected stairway
Non-fire resisting construction
See para 3.63
Configurations of stairs and external wall
Fire resisting construction
Fire resisting construction of adjacent building enclosure of protected stairway
Non-fire resisting construction
See para 3.63
No fire resistance required for door
1100mm zone above top landing
1100mm zone above top landing
6m maximum height of stair
Fire resisting window (minimum RE30)
1800mm zone of fire resisting construction at side of stair
Fire doorset (minimum E30)
Ground level or a roof or podium served by an independent stairway
6m maximum height of stair without weather protection
9m zone of fire resisting construction below stair
Ground level or a roof or podium served by an independent stairway
See para 3.68
See para 3.18
NOTE: Bathrooms do not need to have fire doorsets provided that the bathroom is separated by fire resisting construction from the adjacent rooms.
See para 3.18
NOTE: Bathrooms do not need to have fire doorsets provided that the bathroom is separated by fire resisting construction from the adjacent rooms.
In single stair buildings, electricity meters should be in securely locked cupboards. Cupboards should be separated from the escape route by fire resisting construction.
In single stair buildings, electricity meters should be in securely locked cupboards. Cupboards should be separated from the escape route by fire resisting construction.
compartmentation
Each flat in a block should have alarms as set out in paragraphs 1.1 to 1.4. With effective compartmentation, a communal fire alarm system is not normally needed. In some buildings, detectors in common parts of the building may need to operate smoke control or other fire protection systems but do not usually sound an audible warning.
The fire detection and alarm systems in flats should connect to a central monitoring point or alarm
receiving centre. The systems should alert the warden or supervisor and identify the individual flat
where a fire has been detected.
An alternative approach to that described in paragraph 2.21 would be to comply with all of the following.
a. Provide sprinkler protection to the open-plan areas.
b. Provide a fire resisting partition (minimum REI 30) and door (minimum E 20) to separate the ground storey from the upper storeys. The door should allow occupants of the loft room access to a first storey escape window.
c. Separate cooking facilities from the open-plan area with fire resisting construction (minimum REI 30).
See para 2.6
Example of alternative exit in para 2.6(a) (see definition in Appendix A)
See Diagram 2.1c. The dwellinghouse should have either of the following. Cavity barriers or a fire resisting ceiling (minimum EI 30) should be provided above a protected stairway enclosure (Diagram 2.3). b. Alternative escape route – a top storey separated from lower storeys by fire resisting construction (minimum REI 30) and with an alternative escape route leading to its own final exit.
a. Protected stairway – a stair separated by fire resisting construction (minimum REI 30) at all storeys, that complies with one of the following.
i. Extends to a final exit (Diagram 2.2a).
ii. Gives access to a minimum of two ground level final exits that are separated from each other by fire resisting construction (minimum REI 30) and fire doorsets (minimum E 20) (Diagram 2.2b).
Configurations of stairs and external wall
Fire resisting construction
Fire resisting construction of adjacent building enclosure of protected stairway
Non-fire resisting construction
See para 3.63
Where access from any habitable room to the entrance hall or flat entrance is impossible without passing through another room, all of the following conditions should be met (Diagram 3.4).
a. Bedrooms should be separated from living accommodation by fire resisting construction (minimum REI 30) and fire doorsets (minimum E 20).
b. The alternative exit should be in the part of the flat that contains the bedrooms.
The provisions in this section make the following assumptions.
a. Any fire is likely to be in a flat.
b. There is no reliance on external rescue.
c. Simultaneous evacuation of all flats is unlikely to be necessary due to compartmentation.
d. Fires in common parts of the building should not spread beyond the fabric in the immediate vicinity. In some cases, however, communal facilities exist that require additional measures to be taken.
See para 3.18
NOTE: Bathrooms do not need to have fire doorsets provided that the bathroom is separated by fire resisting construction from the adjacent rooms.
A fire doorset (minimum E 30 Sa) fitted with a self-closing device (and fire resisting screen, where required) should separate the dead-end portion of a common corridor from the rest of the corridor (Diagrams 3.7a, 3.8b and 3.8c).
A protected circuit to operate equipment during a fire should achieve all of the following.
a. Cables should achieve PH 30 classification when tested in accordance with BS EN 50200 (incorporating Annex E) or an equivalent standard.
b. It should only pass through parts of the building in which the fire risk is negligible.
c. It should be separate from any circuit provided for another purpose.
Refuse chutes and rooms for storing refuse should meet both of the following conditions.
a. Be separated from other parts of the building by fire resisting construction (minimum REI 30 in buildings with a top storey up to 5m above ground level; otherwise REI 60).
b. Not be situated within a protected stairway or protected lobby.
With some configurations of external wall, a fire in one part of a building could subject the external wall of a protected stairway to heat (for example, where the two are adjacent at an internal angle in the façade, as shown in Diagram 3.10).
Any external escape stair should meet all of the following conditions (Diagram 3.11).
a. Doors to the stair should be fire resisting (minimum E 30) and be fitted with a self-closing device, except for a single exit door from the building to the top landing of a downward-leading external stair, provided it is the only door onto the landing.
b. Fire resisting construction (minimum RE 30) is required for the building envelope within the following zones, measured from the flights and landings of the external stair.
i. 1800mm above and horizontally.
ii. 9m vertically below.
iii. 1100mm above the top landing of the stair (except where the stair leads from basement to ground level).
c. Fire resisting construction (minimum RE 30) should be provided for any part of the building (including doors) within 1800mm of the escape route from the foot of the stair to a place of safety. This does not apply if there are alternative escape routes from the foot of the external escape stair.
d. Glazing in areas of fire resisting construction should be fixed shut and fire resisting (in terms of integrity but not insulation) (minimum E 30).
e. Stairs more than 6m in height above ground level (e.g. where they are provided above a podium) should be protected from adverse weather. Protection should prevent the build-up of snow or ice but does not require full enclosure.
See paras 3.27 and 3.36
NOTES:
1. The arrangements shown also apply to the top storey.
2. See Diagram 3.9 for small single stair buildings.
3. All doors shown are fire doorsets.
4. Where travel distance is measured to a stair lobby, the lobby must not provide direct access to any storage room, flat or other space containing a potential fire hazard.
5. For further guidance on the fire rating of the fire doorsets from the corridor to the flat and/or stairway refer to Appendix C ,Table C1.
F Flat
Shaded areas indicate zones where ventilation should be provided in accordance with paragraphs 3.50 to 3.53(An external wall vent or smoke shaft located anywhere in the shaded area)
In single stair buildings, electricity meters should be in securely locked cupboards. Cupboards should be separated from the escape route by fire resisting construction.
construction programme
Refuse storage chambers, refuse chutes and refuse hoppers should be sited and constructed in accordance with BS 5906.
construction site
Refuse storage chambers, refuse chutes and refuse hoppers should be sited and constructed in accordance with BS 5906.
construction strategy
Refuse storage chambers, refuse chutes and refuse hoppers should be sited and constructed in accordance with BS 5906.
continuous operation
Despite the provisions described, it is probable that some smoke will get into the common corridor or lobby from a fire in a flat.
There should therefore be some means of ventilating the common corridors/lobbies to control smoke and so protect the common stairs. This means of ventilation offers additional protection to that provided by the fire doors to the stair, as well as some protection to the corridors/lobbies.
Ventilation can be natural (paragraphs 3.50 to 3.53) or mechanical (paragraph 3.54).
Where a stair serves an enclosed car park or place of special fire hazard, the lobby or corridor should have a minimum 0.4m2 of permanent ventilation or be protected from the ingress of smoke by a mechanical smoke control system.
NOTE: For refuse chutes and storage see paragraphs 3.55 to 3.58.
contractors proposals
Paragraph 3.27 may be modified using the guidance in clause 7.3 of BS 9991.
contrast visually
Where a new storey is added through conversion to create a storey above 4.5m, both of the following should apply.
a. The full extent of the escape route should be addressed.
b. Fire resisting doors (minimum E 20) and partitions (minimum REI 30) should be provided, including upgrading the existing doors where necessary.
NOTE: Where the layout is open plan, new partitions should be provided to enclose the escape route (Diagram 2.2).
Where it is undesirable to replace existing doors because of historical or architectural merit, the possibility of retaining, and where necessary upgrading, them should be investigated.
Escape routes should have a minimum clear headroom of 2m. The only projections allowed below this height are door frames.
Smoke vents should comply with one of the following.
a. They should be located on an external wall with minimum free area of 1.5m2.
b. They should discharge into a vertical smoke shaft, closed at the base, that meets all of the following criteria.
i. The shaft should conform to the following conditions.
• Have a minimum cross-sectional area of 1.5m2 (minimum dimension 0.85m in any direction).
• Open at roof level, minimum 0.5m above any surrounding structures within 2m of it horizontally.
• Extend a minimum of 2.5m above the ceiling of the highest storey served by the shaft.
ii. The free area of all the following vents should be a minimum of 1m2 in the following places.
• From the corridor or lobby into the shaft.
• At the opening at the head of the shaft.
• At all internal locations within the shaft (e.g. safety grilles).
iii. The smoke shaft should be constructed from a class A1 material. All vents should either be a fire doorset (see Appendix C, Table C1, item 2.e for minimum fire resistance) or fitted with a smoke control damper achieving the same period of fire resistance and designed to operate as described below. The shaft should be vertical from base to head, with a maximum of 4m at a maximum inclined angle of 30 degrees.
iv. If smoke is detected in the common corridor or lobby, both of the following should occur.
• Simultaneous opening of vents on the storey where the fire is located, at the top of the smoke shaft and to the stair.
• Vents from the corridors or lobbies on all other storeys should remain closed, even if smoke is subsequently detected on storeys other than where the fire is located.
controlled services or fittings
Gas service and installation pipes and meters should not be within a protected stairway, unless installed in accordance with the Pipelines Safety Regulations 1996 and the Gas Safety (Installation and Use) Regulations 1998.
corridor access
In student residences that are designed and occupied as a block of flats, separate automatic detection should be provided in each self-contained flat where all of the following apply.
a. A group of up to six students shares the flat.
b. Each flat has its own entrance door.
c. The compartmentation principles for flats in Section 7 have been followed.
Where a total evacuation strategy is adopted, the alarm system should follow the guidance for buildings other than dwellings in Volume 2 of Approved Document B.
NOTES:
1. If travel distance is measured to a stair lobby, the lobby must not provide direct access to any storage room, flat or other space containing a fire hazard.
2. In the case of a small single stair building in accordance with Diagram 3.9, this is reduced to 4.5m.
3. Does not apply if all flats on a storey have independent alternative means of escape.
4. Sheltered housing may require reduced maximum travel distances.
For flats more than 4.5m above ground level, a balcony outside an alternative exit should be a common balcony meeting the conditions described in paragraph 3.22.
The internal arrangement of single storey or multi-storey flats should comply with paragraphs 3.15 to 3.17. Alternatively, the guidance in paragraphs 3.18 to 3.22 may be followed.
A flat accessed via the common parts of the building should also comply with the provisions for small single stair buildings in paragraph 3.28 and Diagram 3.9. A protected entrance hall may be required as a result.
Any alternative exit from a flat should comply with all of the following.
a. It should be remote from the main entrance door to the flat.
b. It should lead to a final exit, via a common stair if necessary, through one of the following.
i. A door to an access corridor, access lobby or common balcony.
ii. An internal private stair leading to an access corridor, access lobby or common balcony at another level.
iii. A door to a common stair.
iv. A door to an external stair.
v. A door to an escape route over a flat roof.
Any access route leading to a final exit or common stair should comply with the provisions for means of escape in the common parts of a flat (see paragraph 3.25).
From the flat entrance door, a single escape route is acceptable in either of the following cases.
a. The flat is on a storey served by a single common stair and both of the following apply.
i. Every flat is separated from the common stair by a protected lobby or common protected corridor (see Diagram 3.7).
ii. The maximum travel distance in Table 3.1, for escape in one direction only, is not exceeded.
b. The flat is in a dead end of a common corridor served by two (or more) common stairs and the maximum travel distance given in Table 3.1, for escape in one direction only, is not exceeded (Diagram 3.8).
See para 3.18
Flat entrance
Kitchen area
Bath
Common corridors should be protected corridors. The wall between each flat and the corridor should be a compartment wall (minimum REI 30 where the top storey is up to 5m above ground level, otherwise REI 60).
Access to an external escape stair may be via a flat roof, provided the flat roof meets the requirements of paragraph 3.30.
Where a common stair is not part of the only escape route from a flat, it may also serve ancillary accommodation from which it is separated by a protected lobby or protected corridor (minimum REI 30).
a. CORRIDOR ACCESS WITHOUT DEAD ENDS
b. CORRIDOR ACCESS WITH DEAD ENDS
The central door may be omitted if maximum travel distance is not more than 15m.
1. The arrangements shown also apply to the top storey.
2. For further guidance on the fire rating of the fire doorsets from the corridor to the flat and/or stairway refer to Appendix C ,Table C1.
Fire doorset provided in accordance with paragraphs 3.50 to 3.53(An external wall vent or smoke shaft located anywhere in the shaded area)
See paras 3.27 and 3.36
dead end
See Diagram 2.1b. Where served by only one stair, all habitable rooms (excluding kitchens) should have either of the following.
a. An emergency escape window or external door, as described in paragraph 2.10.
b. Direct access to a protected stairway, as described in paragraph 2.5a.
Where it is undesirable to replace existing doors because of historical or architectural merit, the possibility of retaining, and where necessary upgrading, them should be investigated.
From the flat entrance door, a single escape route is acceptable in either of the following cases.
a. The flat is on a storey served by a single common stair and both of the following apply.
i. Every flat is separated from the common stair by a protected lobby or common protected corridor (see Diagram 3.7).
ii. The maximum travel distance in Table 3.1, for escape in one direction only, is not exceeded.
b. The flat is in a dead end of a common corridor served by two (or more) common stairs and the maximum travel distance given in Table 3.1, for escape in one direction only, is not exceeded (Diagram 3.8).
See para 3.19
NOTE: The bedrooms are not classified as inner rooms because escape is possible in two directions.
Fire doorset
Fire resisting construction (minimum REI 30) between living and bedroom accommodation
Alternative exit
dead load
Escape route floor finishes should minimise their slipperiness when wet. Finishes include the treads of steps and surfaces of ramps and landings.
decibel (dB)
See para 3.21
NOTE: This only applies where at least one storey is more than 4.5m above ground level.
Alternative exit
Bathroom
ENTRANCE LEVEL
LEVEL(S) ABOVE OR BELOW ENTRANCE LEVEL
definitions
These provisions do not apply to the following.
a. The common parts of a sheltered housing development, such as communal lounges.
b. Sheltered accommodation in the 'residential (institutional)' or 'residential (other)' purpose groups (purpose group 2(a) or 2(b)).
In these parts, means of warning should follow the guidance for buildings other than dwellings in Volume 2 of Approved Document B.
definitions (ada)
If a loadbearing wall is any of the following, guidance in other sections may also apply.
a. A compartment wall (including a wall common to two buildings): Section 7.
b. Enclosing a place of special fire hazard: Section 7.
c. Protecting a means of escape: Sections 2 and 3.
d. An external wall: Sections 10 and 11.
e. Enclosing a firefighting shaft: Section 15.
designation system
All dwellings should have a fire detection and alarm system, minimum Grade D2 Category LD3
standard, in accordance with the relevant recommendations of BS 5839-6.
A higher standard of protection should be considered where occupants of a proposed dwelling
would be at special risk from fire. Further advice on this is also given in BS 5839-6.
designer
Guidance on the design of smoke control systems that use pressure differentials is available in BS EN 12101-6.
direct distance
Where a new storey is added through conversion to create a storey above 4.5m, both of the following should apply.
a. The full extent of the escape route should be addressed.
b. Fire resisting doors (minimum E 20) and partitions (minimum REI 30) should be provided, including upgrading the existing doors where necessary.
NOTE: Where the layout is open plan, new partitions should be provided to enclose the escape route (Diagram 2.2).
An alternative approach to that described in paragraph 2.21 would be to comply with all of the following.
a. Provide sprinkler protection to the open-plan areas.
b. Provide a fire resisting partition (minimum REI 30) and door (minimum E 20) to separate the ground storey from the upper storeys. The door should allow occupants of the loft room access to a first storey escape window.
c. Separate cooking facilities from the open-plan area with fire resisting construction (minimum REI 30).
Where escape from a dwellinghouse is to an enclosed space with exit only possible through other buildings (e.g. a courtyard or back garden), the length of the space should exceed whichever is the greater of the following.
a. The height of the dwellinghouse above ground level (x).
b. Where a rear extension is provided, the height of the extension (y).
See para 2.10
See Diagram 2.1d. In addition to meeting the provisions in paragraph 2.5, the dwellinghouse should comply with either of the following.
a. Provide an alternative escape route from each storey more than 7.5m above ground level. At the first storey above 7.5m, the protected stairway should be separated from the lower storeys by fire resisting construction (minimum REI 30) if the alternative escape route is accessed via either of the following.
i. The protected stairway to an upper storey.
ii. A landing within the protected stairway enclosure to an alternative escape route on the same storey. The protected stairway at or about 7.5m above ground level should be separated from the lower storeys or levels by fire resisting construction (see Diagram 2.4).
b. Provide a sprinkler system throughout, designed and installed in accordance with BS 9251.
A passenger lift serving any storey more than 4.5m above ground level should be in either of the following.
a. The enclosure to the protected stairway, as described in paragraph 2.5.
b. A fire resisting lift shaft (minimum REI 30).
All of the following precautions should be taken to avoid the spread of smoke and fire to the protected stairway.
a. Transfer grilles should not be fitted in any wall, door, floor or ceiling of the stair enclosure.
b. Any duct passing through the stair enclosure should be rigid steel. Joints between the ductwork and stair enclosure should be fire-stopped.
c. Ventilation ducts supplying or extracting air directly to or from a protected stairway should not serve other areas as well.
d. Any system of mechanical ventilation which recirculates air and which serves both the stair and other areas should be designed to shut down on the detection of smoke within the system.
e. For ducted warm air heating systems, a room thermostat should be sited in the living room. It should be mounted at a height between 1370mm and 1830mm above the floor. The maximum setting should be 27°C.
NOTE: Ventilation ducts passing through compartment walls should comply with the guidance in Section 9.
NOTES:
1. If travel distance is measured to a stair lobby, the lobby must not provide direct access to any storage room, flat or other space containing a fire hazard.
2. In the case of a small single stair building in accordance with Diagram 3.9, this is reduced to 4.5m.
3. Does not apply if all flats on a storey have independent alternative means of escape.
4. Sheltered housing may require reduced maximum travel distances.
All habitable rooms (excluding kitchens) should have either of the following.
a. An emergency escape window or external door, as described in paragraph 3.6.
b. In multi-storey flats, direct access to a protected internal stairway (minimum REI 30) leading to an exit from the flat.
When multi-storey flats do not have their own external entrance at ground level, adopt one of the following approaches.
a. Approach 1 – provide at least one alternative exit from each habitable room that is not on the entrance storey of the flat (Diagram 3.5 and paragraph 3.22).
b. Approach 2 – provide at least one alternative exit from each storey that is not the entrance storey of the flat. All habitable rooms should have direct access to a protected landing (Diagram 3.6 and paragraph 3.22).
c. Approach 3 – provide a protected stairway plus a sprinkler system in accordance with Appendix E and provide smoke alarms in accordance with BS 5839-6.
d. Approach 4 – if the vertical distance between the entrance storey of the flat and any of the storeys above or below does not exceed 7.5m, provide all of the following.
i. A protected stairway.
ii. Additional smoke alarms in all habitable rooms.
iii. A heat alarm in any kitchen.
For systems circulating air only within an individual flat, take all of the following precautions.
a. Transfer grilles should not be fitted in any wall, door, floor or ceiling of the enclosure.
b. Any duct passing through the enclosure should be rigid steel. Joints between the ductwork and enclosure should be fire-stopped.
c. Ventilation ducts serving the enclosure should not serve any other areas.
d. Any system of mechanical ventilation which recirculates air and which serves both the stair and other areas should be designed to shut down on the detection of smoke within the system.
e. For ducted warm air heating systems, a room thermostat should be sited in the living room. It should be mounted at a height between 1370mm and 1830mm above the floor. The maximum setting should be 27°C.
NOTE: Ventilation ducts passing through compartment walls should comply with the guidance in Section 9.
For flats serving as a workplace for both occupants and people who do not live on the premises, provide both of the following.
a. A maximum travel distance of 18m between any part of the working area and either of the following.
i. The flat entrance door.
ii. An alternative means of escape that is not a window.
If the travel distance is over 18m, the assumptions in paragraph 3.2 may not be valid. The design should be considered on a case-by-case basis.
b. Escape lighting to windowless accommodation in accordance with BS 5266-1.
For some low rise buildings, the provisions in paragraphs 3.26 and 3.27 may be modified and the use of a single stair, protected in accordance with Diagram 3.9, may be permitted where all of the following apply.
a. The top storey of the building is a maximum of 11m above ground level.
b. No more than three storeys are above the ground storey.
c. The stair does not connect to a covered car park, unless the car park is open sided (as defined in Section 11 of Approved Document B Volume 2).
d. The stair does not serve offices, stores or other ancillary accommodation. If it does, they should be separated from the stair by a protected lobby or protected corridor (minimum REI 30) with a minimum 0.4m2 of permanent ventilation, or be protected from the ingress of smoke by a mechanical smoke control system.
NOTE: For refuse chutes and storage see paragraphs 3.55 to 3.58.
e. Either of the following is provided for the fire and rescue service.
i. A high-level openable vent with a free area of at least 1m2 at each storey.
ii. A single openable vent with a free area of at least 1m2 at the head of the stair, operable remotely at the fire and rescue service access level.
Smoke vents should comply with one of the following.
a. They should be located on an external wall with minimum free area of 1.5m2.
b. They should discharge into a vertical smoke shaft, closed at the base, that meets all of the following criteria.
i. The shaft should conform to the following conditions.
• Have a minimum cross-sectional area of 1.5m2 (minimum dimension 0.85m in any direction).
• Open at roof level, minimum 0.5m above any surrounding structures within 2m of it horizontally.
• Extend a minimum of 2.5m above the ceiling of the highest storey served by the shaft.
ii. The free area of all the following vents should be a minimum of 1m2 in the following places.
• From the corridor or lobby into the shaft.
• At the opening at the head of the shaft.
• At all internal locations within the shaft (e.g. safety grilles).
iii. The smoke shaft should be constructed from a class A1 material. All vents should either be a fire doorset (see Appendix C, Table C1, item 2.e for minimum fire resistance) or fitted with a smoke control damper achieving the same period of fire resistance and designed to operate as described below. The shaft should be vertical from base to head, with a maximum of 4m at a maximum inclined angle of 30 degrees.
iv. If smoke is detected in the common corridor or lobby, both of the following should occur.
• Simultaneous opening of vents on the storey where the fire is located, at the top of the smoke shaft and to the stair.
• Vents from the corridors or lobbies on all other storeys should remain closed, even if smoke is subsequently detected on storeys other than where the fire is located.
Refuse chutes and rooms for storing refuse should meet both of the following conditions.
a. Be separated from other parts of the building by fire resisting construction (minimum REI 30 in buildings with a top storey up to 5m above ground level; otherwise REI 60).
b. Not be situated within a protected stairway or protected lobby.
Every common stair should be a protected stairway, within a fire resisting enclosure (minimum REI 30).
With some configurations of external wall, a fire in one part of a building could subject the external wall of a protected stairway to heat (for example, where the two are adjacent at an internal angle in the façade, as shown in Diagram 3.10).
If a protected stairway projects beyond, is recessed from or is in an internal angle of the adjoining external wall of the building, then the minimum distance between an unprotected area of the building enclosure and an unprotected area of the stair enclosure should be 1800mm.
See paras 3.27 and 3.36
NOTES:
1. The arrangements shown also apply to the top storey.
2. See Diagram 3.9 for small single stair buildings.
3. All doors shown are fire doorsets.
4. Where travel distance is measured to a stair lobby, the lobby must not provide direct access to any storage room, flat or other space containing a potential fire hazard.
5. For further guidance on the fire rating of the fire doorsets from the corridor to the flat and/or stairway refer to Appendix C ,Table C1.
F Flat
Shaded areas indicate zones where ventilation should be provided in accordance with paragraphs 3.50 to 3.53(An external wall vent or smoke shaft located anywhere in the shaded area)
The construction separating two adjacent protected stairways (or exit passageways leading to different final exits) should be imperforate.
In buildings with more than three storeys above the ground storey, stairs may serve the flats and other occupancies if all of the following apply.
a. The flat is ancillary to the main use of the building.
b. The flat has an independent alternative escape route.
c. The stair is separated from occupancies on lower storeys by a protected lobby (minimum REI 30) at each of those storeys.
d. The stair enclosure has at least the same standard of fire resistance as the structural elements of the building (see Appendix B, Table B4); if the stair is a firefighting stair, it should comply with the provisions in Section 15 (see also paragraph 3.60).
e. Any automatic fire detection and alarm system fitted in the main part of the building also covers all flats.
f. Any security measures in any parts of the building do not prevent escape at all material times.
a. CORRIDOR ACCESS WITHOUT DEAD ENDS
b. CORRIDOR ACCESS WITH DEAD ENDS
The central door may be omitted if maximum travel distance is not more than 15m.
1. The arrangements shown also apply to the top storey.
2. For further guidance on the fire rating of the fire doorsets from the corridor to the flat and/or stairway refer to Appendix C ,Table C1.
Fire doorset provided in accordance with paragraphs 3.50 to 3.53(An external wall vent or smoke shaft located anywhere in the shaded area)
See paras 3.27 and 3.36
Every protected stairway should lead to a final exit, either directly or via a protected exit passageway. Any protected exit corridor or stair should have the same standard of fire resistance and lobby protection as the stair it serves.
display window
Windows or external doors providing emergency escape should comply with all of the following.
a. Windows should have an unobstructed openable area that complies with all of the following.
i. A minimum area of 0.33m2.
ii. A minimum height of 450mm and a minimum width of 450mm (the route through the window may be at an angle rather than straight through).
iii. The bottom of the openable area is a maximum of 1100mm above the floor.
b. People escaping should be able to reach a place free from danger from fire. Courtyards or inaccessible back gardens should comply with Diagram 2.5.
c. Locks (with or without removable keys) and opening stays (with child-resistant release catches) may be fitted to escape windows.
d. Windows should be capable of remaining open without being held.
A gallery should comply with one of the following.
a. It should be provided with an alternative exit.
b. It should be provided with an emergency escape window, as described in paragraph 2.10, where the gallery floor is a maximum of 4.5m above ground level.
c. It should meet all the conditions shown in Diagram 2.6.
Where an existing window would be an escape window in a new dwellinghouse, and is big enough to be used for escape purposes, then the replacement should comply with one of the following.
a. The replacement window should be sized to provide at least the same potential for escape.
b. If the existing window was larger than required for escape purposes, the opening can be reduced to the minimum described in paragraph 2.10.
Where it is undesirable to replace existing doors because of historical or architectural merit, the possibility of retaining, and where necessary upgrading, them should be investigated.
A gallery should comply with one of the following.
a. It should be provided with an alternative exit.
b. It should be provided with an emergency escape window, as described in paragraph 3.6, where the gallery floor is a maximum of 4.5m above ground level.
c. It should meet the conditions shown in Diagram 3.1.
To limit potential damage to cables in protected circuits, all of the following should apply.
a. Cables should be sufficiently robust.
b. Cable routes should be carefully selected and/or physically protected in areas where cables may be exposed to damage.
c. Methods of cable support should be class A1 rated and offer at least the same integrity as the cable. They should maintain circuit integrity and hold cables in place when exposed to fire.
Windows or external doors providing emergency escape should comply with all of the following.
a. Windows should have an unobstructed openable area that complies with all of the following.
i. A minimum area of 0.33m2.
ii. A minimum height of 450mm and a minimum width of 450mm (the route through the window may be at an angle rather than straight through).
iii. The bottom of the openable area is a maximum of 1100mm above the floor.
b. People escaping should be able to reach a place free from danger from fire.
c. Locks (with or without removable keys) and opening stays (with child-resistant release catches) may be fitted to escape windows.
d. Windows should be capable of remaining open without being held.
Any external escape stair should meet all of the following conditions (Diagram 3.11).
a. Doors to the stair should be fire resisting (minimum E 30) and be fitted with a self-closing device, except for a single exit door from the building to the top landing of a downward-leading external stair, provided it is the only door onto the landing.
b. Fire resisting construction (minimum RE 30) is required for the building envelope within the following zones, measured from the flights and landings of the external stair.
i. 1800mm above and horizontally.
ii. 9m vertically below.
iii. 1100mm above the top landing of the stair (except where the stair leads from basement to ground level).
c. Fire resisting construction (minimum RE 30) should be provided for any part of the building (including doors) within 1800mm of the escape route from the foot of the stair to a place of safety. This does not apply if there are alternative escape routes from the foot of the external escape stair.
d. Glazing in areas of fire resisting construction should be fixed shut and fire resisting (in terms of integrity but not insulation) (minimum E 30).
e. Stairs more than 6m in height above ground level (e.g. where they are provided above a podium) should be protected from adverse weather. Protection should prevent the build-up of snow or ice but does not require full enclosure.
dwelling
In student residences that are designed and occupied as a block of flats, separate automatic detection should be provided in each self-contained flat where all of the following apply.
a. A group of up to six students shares the flat.
b. Each flat has its own entrance door.
c. The compartmentation principles for flats in Section 7 have been followed.
Where a total evacuation strategy is adopted, the alarm system should follow the guidance for buildings other than dwellings in Volume 2 of Approved Document B.
In student residences that are designed and occupied as a block of flats, separate automatic detection should be provided in each self-contained flat where all of the following apply.
a. A group of up to six students shares the flat.
b. Each flat has its own entrance door.
c. The compartmentation principles for flats in Section 7 have been followed.
Where a total evacuation strategy is adopted, the alarm system should follow the guidance for buildings other than dwellings in Volume 2 of Approved Document B.
A large dwellinghouse has more than one storey, and at least one storey exceeds 200m2.
A large dwellinghouse has more than one storey, and at least one storey exceeds 200m2.
A large dwellinghouse of two storeys (excluding basement storeys) should be fitted with a Grade A
Category LD3 fire detection and alarm system, as described in BS 5839-6.
A large dwellinghouse of two storeys (excluding basement storeys) should be fitted with a Grade A
Category LD3 fire detection and alarm system, as described in BS 5839-6.
A large dwellinghouse of three or more storeys (excluding basement storeys) should be fitted with
a Grade A Category LD2 fire detection and alarm system as described in BS 5839-6.
A large dwellinghouse of three or more storeys (excluding basement storeys) should be fitted with
a Grade A Category LD2 fire detection and alarm system as described in BS 5839-6.
See paras 2.1 to 2.6
Single storey dwellinghouse(see paragraph 2.1)
Dwellinghouse with one storey more than 4.5m above ground level(see paragraph 2.5)
Dwellinghouse with two or more storeys more than 4.5m above ground level(see paragraph 2.6)
See paras 2.1 to 2.6
Single storey dwellinghouse(see paragraph 2.1)
Dwellinghouse with one storey more than 4.5m above ground level(see paragraph 2.5)
Dwellinghouse with two or more storeys more than 4.5m above ground level(see paragraph 2.6)
Air circulation systems which circulate air within an individual dwellinghouse with a floor more than
4.5m above ground level should meet the guidance given in paragraph 2.9.
Air circulation systems which circulate air within an individual dwellinghouse with a floor more than
4.5m above ground level should meet the guidance given in paragraph 2.9.
Separate guidance applies to means of escape within the flat and within the common parts of the building that lead to a place of safety. Flats at ground level are treated similarly to dwellinghouses. With increasing height, more complex provisions are needed.
Separate guidance applies to means of escape within the flat and within the common parts of the building that lead to a place of safety. Flats at ground level are treated similarly to dwellinghouses. With increasing height, more complex provisions are needed.
A multi-storey flat with an independent external entrance at ground level is similar to a dwellinghouse and means of escape should be planned on the basis of Section 2, depending on the height of the top storey above ground level.
A multi-storey flat with an independent external entrance at ground level is similar to a dwellinghouse and means of escape should be planned on the basis of Section 2, depending on the height of the top storey above ground level.
dwelling (l2a)
In student residences that are designed and occupied as a block of flats, separate automatic detection should be provided in each self-contained flat where all of the following apply.
a. A group of up to six students shares the flat.
b. Each flat has its own entrance door.
c. The compartmentation principles for flats in Section 7 have been followed.
Where a total evacuation strategy is adopted, the alarm system should follow the guidance for buildings other than dwellings in Volume 2 of Approved Document B.
These provisions do not apply to the following.
a. The common parts of a sheltered housing development, such as communal lounges.
b. Sheltered accommodation in the 'residential (institutional)' or 'residential (other)' purpose groups (purpose group 2(a) or 2(b)).
In these parts, means of warning should follow the guidance for buildings other than dwellings in Volume 2 of Approved Document B.
NOTES:
1. If travel distance is measured to a stair lobby, the lobby must not provide direct access to any storage room, flat or other space containing a fire hazard.
2. In the case of a small single stair building in accordance with Diagram 3.9, this is reduced to 4.5m.
3. Does not apply if all flats on a storey have independent alternative means of escape.
4. Sheltered housing may require reduced maximum travel distances.
dwelling type
In student residences that are designed and occupied as a block of flats, separate automatic detection should be provided in each self-contained flat where all of the following apply.
a. A group of up to six students shares the flat.
b. Each flat has its own entrance door.
c. The compartmentation principles for flats in Section 7 have been followed.
Where a total evacuation strategy is adopted, the alarm system should follow the guidance for buildings other than dwellings in Volume 2 of Approved Document B.
Common corridors should be protected corridors. The wall between each flat and the corridor should be a compartment wall (minimum REI 30 where the top storey is up to 5m above ground level, otherwise REI 60).
A ramp forming part of an escape route should meet the provisions in Approved Document M. Any sloping floor or tier should have a pitch of not more than 35 degrees to the horizontal.
To limit potential damage to cables in protected circuits, all of the following should apply.
a. Cables should be sufficiently robust.
b. Cable routes should be carefully selected and/or physically protected in areas where cables may be exposed to damage.
c. Methods of cable support should be class A1 rated and offer at least the same integrity as the cable. They should maintain circuit integrity and hold cables in place when exposed to fire.
Except in buildings that comply with Diagram 3.9, the corridor or lobby next to each stair should have a smoke vent. The location of the vent should comply with both of the following.
a. Be as high as practicable.
b. Be positioned so the top edge is at least as high as the top of the door to the stair.
A vent to the outside with a minimum free area of 1m2 should be provided from the top storey of the stair.
dwellinghouse
In student residences that are designed and occupied as a block of flats, separate automatic detection should be provided in each self-contained flat where all of the following apply.
a. A group of up to six students shares the flat.
b. Each flat has its own entrance door.
c. The compartmentation principles for flats in Section 7 have been followed.
Where a total evacuation strategy is adopted, the alarm system should follow the guidance for buildings other than dwellings in Volume 2 of Approved Document B.
See paras 2.1 to 2.6
Single storey dwellinghouse(see paragraph 2.1)
Dwellinghouse with one storey more than 4.5m above ground level(see paragraph 2.5)
Dwellinghouse with two or more storeys more than 4.5m above ground level(see paragraph 2.6)
Dwellinghouses with one internal stair should comply with paragraphs 2.5 and 2.6. In dwellinghouses with more than one stair, the stairs should provide effective alternative means of escape. The stairs should be physically separated by either of the following.
a. Fire resisting construction (minimum REI 30).
b. More than one room.
Separate guidance applies to means of escape within the flat and within the common parts of the building that lead to a place of safety. Flats at ground level are treated similarly to dwellinghouses. With increasing height, more complex provisions are needed.
NOTES:
1. If travel distance is measured to a stair lobby, the lobby must not provide direct access to any storage room, flat or other space containing a fire hazard.
2. In the case of a small single stair building in accordance with Diagram 3.9, this is reduced to 4.5m.
3. Does not apply if all flats on a storey have independent alternative means of escape.
4. Sheltered housing may require reduced maximum travel distances.
All habitable rooms (excluding kitchens) should have either of the following.
a. An emergency escape window or external door, as described in paragraph 3.6.
b. In multi-storey flats, direct access to a protected internal stairway (minimum REI 30) leading to an exit from the flat.
See para 3.18
Flat entrance
Kitchen area
Bath
Flats may be served by an external stair if the provisions in paragraphs 3.66 to 3.69 are followed.
Access to an external escape stair may be via a flat roof, provided the flat roof meets the requirements of paragraph 3.30.
early warning system
Fire detection and alarm systems sometimes trigger other systems. The interface between systems
must be reliable. Particular care should be taken if the interface is facilitated via another system.
Where any part of BS 7273 applies to the triggering of other systems, the recommendations of that
part of BS 7273 should be followed.
easily accessible
See paras 2.1 to 2.6
Single storey dwellinghouse(see paragraph 2.1)
Dwellinghouse with one storey more than 4.5m above ground level(see paragraph 2.5)
Dwellinghouse with two or more storeys more than 4.5m above ground level(see paragraph 2.6)
A gallery should comply with one of the following.
a. It should be provided with an alternative exit.
b. It should be provided with an emergency escape window, as described in paragraph 2.10, where the gallery floor is a maximum of 4.5m above ground level.
c. It should meet all the conditions shown in Diagram 2.6.
See para 2.6
Example of alternative exit in para 2.6(a) (see definition in Appendix A)
A passenger lift serving any storey more than 4.5m above ground level should be in either of the following.
a. The enclosure to the protected stairway, as described in paragraph 2.5.
b. A fire resisting lift shaft (minimum REI 30).
Air circulation systems which circulate air within an individual dwellinghouse with a floor more than
4.5m above ground level should meet the guidance given in paragraph 2.9.
Separate guidance applies to means of escape within the flat and within the common parts of the building that lead to a place of safety. Flats at ground level are treated similarly to dwellinghouses. With increasing height, more complex provisions are needed.
For flats more than 4.5m above ground level, a balcony outside an alternative exit should be a common balcony meeting the conditions described in paragraph 3.22.
A gallery should comply with one of the following.
a. It should be provided with an alternative exit.
b. It should be provided with an emergency escape window, as described in paragraph 3.6, where the gallery floor is a maximum of 4.5m above ground level.
c. It should meet the conditions shown in Diagram 3.1.
A multi-storey flat with an independent external entrance at ground level is similar to a dwellinghouse and means of escape should be planned on the basis of Section 2, depending on the height of the top storey above ground level.
See para 3.21
NOTE: This only applies where at least one storey is more than 4.5m above ground level.
Alternative exit
Bathroom
ENTRANCE LEVEL
LEVEL(S) ABOVE OR BELOW ENTRANCE LEVEL
electrical installation*
Escape stair lighting should be on a separate circuit from the electricity supply to any other part of the escape route.
To limit potential damage to cables in protected circuits, all of the following should apply.
a. Cables should be sufficiently robust.
b. Cable routes should be carefully selected and/or physically protected in areas where cables may be exposed to damage.
c. Methods of cable support should be class A1 rated and offer at least the same integrity as the cable. They should maintain circuit integrity and hold cables in place when exposed to fire.
A protected stairway should not be used for anything else, except a lift well or electricity meters.
In single stair buildings, electricity meters should be in securely locked cupboards. Cupboards should be separated from the escape route by fire resisting construction.
element of structure
A gallery should comply with one of the following.
a. It should be provided with an alternative exit.
b. It should be provided with an emergency escape window, as described in paragraph 2.10, where the gallery floor is a maximum of 4.5m above ground level.
c. It should meet all the conditions shown in Diagram 2.6.
NOTES:
1. This diagram does not apply where the gallery is provided with one of the following:
i. An alternative escape route
ii. An emergency escape window (where the gallery floor is not more than 4.5m above ground level).
2. Any cooking facilities within a room containing a gallery should comply with one of the following conditions:
i. Be enclosed with fire resisting construction
ii. Be remote from the stair to the gallery and positioned such that they do not prejudice escape from the gallery.
See para 2.15
NOTES:
1. This diagram does not apply where the gallery is provided with one of the following:
i. An alternative escape route
ii. An emergency escape window (where the gallery floor is not more than 4.5m above ground level).
2. Any cooking facilities within a room containing a gallery should comply with one of the following conditions:
i. Be enclosed with fire resisting construction
ii. Be remote from the stair to the gallery and positioned such that they do not prejudice escape from the gallery.
See para 3.13
A gallery should comply with one of the following.
a. It should be provided with an alternative exit.
b. It should be provided with an emergency escape window, as described in paragraph 3.6, where the gallery floor is a maximum of 4.5m above ground level.
c. It should meet the conditions shown in Diagram 3.1.
With some configurations of external wall, a fire in one part of a building could subject the external wall of a protected stairway to heat (for example, where the two are adjacent at an internal angle in the façade, as shown in Diagram 3.10).
If a loadbearing wall is any of the following, guidance in other sections may also apply.
a. A compartment wall (including a wall common to two buildings): Section 7.
b. Enclosing a place of special fire hazard: Section 7.
c. Protecting a means of escape: Sections 2 and 3.
d. An external wall: Sections 10 and 11.
e. Enclosing a firefighting shaft: Section 15.
emergency escape lighting
All escape routes should have adequate artificial lighting. If the mains electricity power supply fails, escape lighting should illuminate the route (including external escape routes).
In addition, escape lighting should be provided to all of the following.
a. Toilet accommodation with a minimum floor area of 8m2.
b. Electricity and generator rooms.
c. Switch room/battery room for emergency lighting system.
d. Emergency control rooms.
Escape lighting should conform to BS 5266-1.
emergency lighting
All escape routes should have adequate artificial lighting. If the mains electricity power supply fails, escape lighting should illuminate the route (including external escape routes).
In addition, escape lighting should be provided to all of the following.
a. Toilet accommodation with a minimum floor area of 8m2.
b. Electricity and generator rooms.
c. Switch room/battery room for emergency lighting system.
d. Emergency control rooms.
Escape stair lighting should be on a separate circuit from the electricity supply to any other part of the escape route.
Escape lighting should conform to BS 5266-1.
entrance storey
See Diagram 2.1d. In addition to meeting the provisions in paragraph 2.5, the dwellinghouse should comply with either of the following.
a. Provide an alternative escape route from each storey more than 7.5m above ground level. At the first storey above 7.5m, the protected stairway should be separated from the lower storeys by fire resisting construction (minimum REI 30) if the alternative escape route is accessed via either of the following.
i. The protected stairway to an upper storey.
ii. A landing within the protected stairway enclosure to an alternative escape route on the same storey. The protected stairway at or about 7.5m above ground level should be separated from the lower storeys or levels by fire resisting construction (see Diagram 2.4).
b. Provide a sprinkler system throughout, designed and installed in accordance with BS 9251.
The internal arrangement of single storey or multi-storey flats should comply with paragraphs 3.15 to 3.17. Alternatively, the guidance in paragraphs 3.18 to 3.22 may be followed.
A flat accessed via the common parts of the building should also comply with the provisions for small single stair buildings in paragraph 3.28 and Diagram 3.9. A protected entrance hall may be required as a result.
One of the following approaches should be adopted, observing the inner room restrictions described in paragraphs 3.7 and 3.8.
a. Provide a protected entrance hall (minimum REI 30) serving all habitable rooms that meets the conditions shown in Diagram 3.2.
b. Plan the flat to meet the conditions shown in Diagram 3.3, so that both of the following apply.
i. The travel distance from the flat entrance door to any point in any habitable room is a maximum of 9m.
ii. Cooking facilities are remote from the main entrance door and do not impede the escape route from anywhere in the flat.
c. Provide an alternative exit from the flat complying with paragraph 3.22.
Where access from any habitable room to the entrance hall or flat entrance is impossible without passing through another room, all of the following conditions should be met (Diagram 3.4).
a. Bedrooms should be separated from living accommodation by fire resisting construction (minimum REI 30) and fire doorsets (minimum E 20).
b. The alternative exit should be in the part of the flat that contains the bedrooms.
A multi-storey flat with an independent external entrance at ground level is similar to a dwellinghouse and means of escape should be planned on the basis of Section 2, depending on the height of the top storey above ground level.
When multi-storey flats do not have their own external entrance at ground level, adopt one of the following approaches.
a. Approach 1 – provide at least one alternative exit from each habitable room that is not on the entrance storey of the flat (Diagram 3.5 and paragraph 3.22).
b. Approach 2 – provide at least one alternative exit from each storey that is not the entrance storey of the flat. All habitable rooms should have direct access to a protected landing (Diagram 3.6 and paragraph 3.22).
c. Approach 3 – provide a protected stairway plus a sprinkler system in accordance with Appendix E and provide smoke alarms in accordance with BS 5839-6.
d. Approach 4 – if the vertical distance between the entrance storey of the flat and any of the storeys above or below does not exceed 7.5m, provide all of the following.
i. A protected stairway.
ii. Additional smoke alarms in all habitable rooms.
iii. A heat alarm in any kitchen.
See para 3.18
Flat entrance
Kitchen area
Bath
The following paragraphs deal with means of escape from the entrance doors of flats to a final exit.
See para 3.21
NOTE: This only applies where at least one storey is more than 4.5m above ground level.
Alternative exit
Bathroom
ENTRANCE LEVEL
LEVEL(S) ABOVE OR BELOW ENTRANCE LEVEL
equivalent area
A vent to the outside with a minimum free area of 1m2 should be provided from the top storey of the stair.
escape lighting
See Diagram 2.1a. All habitable rooms (excluding kitchens) should have either of the following.
a. An opening directly onto a hall leading to a final exit.
b. An emergency escape window or door, as described in paragraph 2.10.
Windows or external doors providing emergency escape should comply with all of the following.
a. Windows should have an unobstructed openable area that complies with all of the following.
i. A minimum area of 0.33m2.
ii. A minimum height of 450mm and a minimum width of 450mm (the route through the window may be at an angle rather than straight through).
iii. The bottom of the openable area is a maximum of 1100mm above the floor.
b. People escaping should be able to reach a place free from danger from fire. Courtyards or inaccessible back gardens should comply with Diagram 2.5.
c. Locks (with or without removable keys) and opening stays (with child-resistant release catches) may be fitted to escape windows.
d. Windows should be capable of remaining open without being held.
Where a flat roof forms part of a means of escape, it should comply with all of the following.
a. It should be part of the same building from which escape is being made.
b. The route across the roof should lead to a storey exit or external escape route.
c. The part of the roof (including its supporting structure) forming the escape route, and any opening within 3m of the escape route, should be of fire resisting construction (minimum REI 30).
A balcony or flat roof intended to form part of an escape route should be provided with guarding etc. in accordance with Approved Document K.
A gallery should comply with one of the following.
a. It should be provided with an alternative exit.
b. It should be provided with an emergency escape window, as described in paragraph 2.10, where the gallery floor is a maximum of 4.5m above ground level.
c. It should meet all the conditions shown in Diagram 2.6.
Basement storeys containing habitable rooms should have one of the following.
a. An emergency escape window or external door providing escape from the basement (paragraph 2.10).
b. A protected stairway (paragraph 2.5a) leading from the basement to a final exit.
Where an existing window would be an escape window in a new dwellinghouse, and is big enough to be used for escape purposes, then the replacement should comply with one of the following.
a. The replacement window should be sized to provide at least the same potential for escape.
b. If the existing window was larger than required for escape purposes, the opening can be reduced to the minimum described in paragraph 2.10.
Where a new storey is added through conversion to create a storey above 4.5m, both of the following should apply.
a. The full extent of the escape route should be addressed.
b. Fire resisting doors (minimum E 20) and partitions (minimum REI 30) should be provided, including upgrading the existing doors where necessary.
NOTE: Where the layout is open plan, new partitions should be provided to enclose the escape route (Diagram 2.2).
NOTES:
1. This diagram does not apply where the gallery is provided with one of the following:
i. An alternative escape route
ii. An emergency escape window (where the gallery floor is not more than 4.5m above ground level).
2. Any cooking facilities within a room containing a gallery should comply with one of the following conditions:
i. Be enclosed with fire resisting construction
ii. Be remote from the stair to the gallery and positioned such that they do not prejudice escape from the gallery.
See para 2.15
NOTES:
1. This diagram does not apply where the gallery is provided with one of the following:
i. An alternative escape route
ii. An emergency escape window (where the gallery floor is not more than 4.5m above ground level).
2. Any cooking facilities within a room containing a gallery should comply with one of the following conditions:
i. Be enclosed with fire resisting construction
ii. Be remote from the stair to the gallery and positioned such that they do not prejudice escape from the gallery.
See para 3.13
Where a flat roof forms part of a means of escape, it should comply with all of the following.
a. It should be part of the same building from which escape is being made.
b. The route across the roof should lead to a storey exit or external escape route.
c. The part of the roof (including its supporting structure) forming the escape route, and any opening within 3m of the escape route, should be of fire resisting construction (minimum REI 30).
A balcony or flat roof intended to form part of an escape route should be provided with guarding etc. in accordance with Approved Document K.
A gallery should comply with one of the following.
a. It should be provided with an alternative exit.
b. It should be provided with an emergency escape window, as described in paragraph 3.6, where the gallery floor is a maximum of 4.5m above ground level.
c. It should meet the conditions shown in Diagram 3.1.
All habitable rooms (excluding kitchens) should have either of the following.
a. An opening directly onto a hall leading to a final exit.
b. An emergency escape window or door, as described in paragraph 3.6.
All habitable rooms (excluding kitchens) should have either of the following.
a. An emergency escape window or external door, as described in paragraph 3.6.
b. In multi-storey flats, direct access to a protected internal stairway (minimum REI 30) leading to an exit from the flat.
Two rooms may be served by a single escape window. A door between rooms should provide access to the escape window without passing through the stair enclosure. Both rooms should have their own access to the internal stair.
For flats serving as a workplace for both occupants and people who do not live on the premises, provide both of the following.
a. A maximum travel distance of 18m between any part of the working area and either of the following.
i. The flat entrance door.
ii. An alternative means of escape that is not a window.
If the travel distance is over 18m, the assumptions in paragraph 3.2 may not be valid. The design should be considered on a case-by-case basis.
b. Escape lighting to windowless accommodation in accordance with BS 5266-1.
A person escaping through the common area, if confronted by the effects of a fire in another flat, should be able to turn away from it and make a safe escape via an alternative route.
Provisions are recommended to support a stay put evacuation strategy for blocks of flats. It is based on the principle that a fire is contained in the flat of origin and common escape routes are maintained relatively free from smoke and heat. It allows occupants, some of whom may require assistance to escape in the event of a fire, in other flats that are not affected to remain.
Sufficient protection to common means of escape is necessary to allow occupants to escape should they choose to do so or are instructed/aided to by the fire service. A higher standard of protection is therefore needed to ensure common escape routes remain available for a longer period than is provided in other buildings.
Where a storey or part of a building has multiple escape routes available, one may be over a flat roof that complies with all of the following.
a. It should be part of the same building from which escape is being made.
b. The route across the roof should lead to a storey exit or external escape route.
c. The part of the roof (including its supporting structure) forming the escape route, and any opening within 3m of the escape route, should be of fire resisting construction (minimum REI 30).
d. The route should be clearly defined and guarded by walls and/or protective barriers to protect against falling.
Where a storey or part of a building has multiple escape routes available, one may be over a flat roof that complies with all of the following.
d. The route should be clearly defined and guarded by walls and/or protective barriers to protect against falling.
Escape route travel distances should comply with Table 3.1.
Escape routes should have a minimum clear headroom of 2m. The only projections allowed below this height are door frames.
A ramp forming part of an escape route should meet the provisions in Approved Document M. Any sloping floor or tier should have a pitch of not more than 35 degrees to the horizontal.
All escape routes should have adequate artificial lighting. If the mains electricity power supply fails, escape lighting should illuminate the route (including external escape routes).
In addition, escape lighting should be provided to all of the following.
a. Toilet accommodation with a minimum floor area of 8m2.
b. Electricity and generator rooms.
c. Switch room/battery room for emergency lighting system.
d. Emergency control rooms.
Escape stair lighting should be on a separate circuit from the electricity supply to any other part of the escape route.
Escape lighting should conform to BS 5266-1.
Windows or external doors providing emergency escape should comply with all of the following.
a. Windows should have an unobstructed openable area that complies with all of the following.
i. A minimum area of 0.33m2.
ii. A minimum height of 450mm and a minimum width of 450mm (the route through the window may be at an angle rather than straight through).
iii. The bottom of the openable area is a maximum of 1100mm above the floor.
b. People escaping should be able to reach a place free from danger from fire.
c. Locks (with or without removable keys) and opening stays (with child-resistant release catches) may be fitted to escape windows.
d. Windows should be capable of remaining open without being held.
Where more than one escape route is available from a storey (or part of a building), then some of the escape routes from that storey or part of the building may be by way of an external stair provided all of the following conditions are met:
a. There is a at least one internal escape stair from every part of each storey (excluding plant areas).
b. The stair serves a floor not more than 6m above either the ground level or a roof podium which is itself served by an independent protected stairway.
c. The stair meets the provisions in paragraph 3.68.
If a building does not meet the criteria of paragraph 3.28, an escape stair forming part of the only escape route from an upper storey should not continue down to serve a basement storey. The basement storey should be served by a separate escape stair.
Basement storeys containing habitable rooms should have one of the following.
a. An emergency escape window or external door providing escape from the basement (see paragraph 3.6).
b. A protected stairway (minimum REI 30) leading from the basement to a final exit.
escape route
In the Secretary of State’s view, requirement B1 is met by achieving all of the following.
a. There are sufficient means for giving early warning of fire to people in the building.
b. All people can escape to a place of safety without external assistance.
c. Escape routes are suitably located, sufficient in number and of adequate capacity.
d. Where necessary, escape routes are sufficiently protected from the effects of fire and smoke.
e. Escape routes are adequately lit and exits are suitably signed.
f. There are appropriate provisions to limit the ingress of smoke to the escape routes, or to
restrict the spread of fire and remove smoke.
g. For buildings containing flats, there are appropriate provisions to support a stay put evacuation
strategy.
The extent to which any of these measures are necessary is dependent on the use of the building,
its size and its height.
Building work and material changes of use subject to requirement B1 include both new and existing
buildings.
See Diagram 2.1a. All habitable rooms (excluding kitchens) should have either of the following.
a. An opening directly onto a hall leading to a final exit.
b. An emergency escape window or door, as described in paragraph 2.10.
Where a flat roof forms part of a means of escape, it should comply with all of the following.
a. It should be part of the same building from which escape is being made.
b. The route across the roof should lead to a storey exit or external escape route.
c. The part of the roof (including its supporting structure) forming the escape route, and any opening within 3m of the escape route, should be of fire resisting construction (minimum REI 30).
A balcony or flat roof intended to form part of an escape route should be provided with guarding etc. in accordance with Approved Document K.
Basement storeys containing habitable rooms should have one of the following.
a. An emergency escape window or external door providing escape from the basement (paragraph 2.10).
b. A protected stairway (paragraph 2.5a) leading from the basement to a final exit.
Where an existing window would be an escape window in a new dwellinghouse, and is big enough to be used for escape purposes, then the replacement should comply with one of the following.
a. The replacement window should be sized to provide at least the same potential for escape.
b. If the existing window was larger than required for escape purposes, the opening can be reduced to the minimum described in paragraph 2.10.
See para 2.5
Fire resisting construction minimum REI 30
Fd Fire doorset minimum E 20
Where a new storey is added through conversion to create a storey above 4.5m, both of the following should apply.
a. The full extent of the escape route should be addressed.
b. Fire resisting doors (minimum E 20) and partitions (minimum REI 30) should be provided, including upgrading the existing doors where necessary.
NOTE: Where the layout is open plan, new partitions should be provided to enclose the escape route (Diagram 2.2).
See Diagram 2.1c. The dwellinghouse should have either of the following. Cavity barriers or a fire resisting ceiling (minimum EI 30) should be provided above a protected stairway enclosure (Diagram 2.3). b. Alternative escape route – a top storey separated from lower storeys by fire resisting construction (minimum REI 30) and with an alternative escape route leading to its own final exit.
a. Protected stairway – a stair separated by fire resisting construction (minimum REI 30) at all storeys, that complies with one of the following.
i. Extends to a final exit (Diagram 2.2a).
ii. Gives access to a minimum of two ground level final exits that are separated from each other by fire resisting construction (minimum REI 30) and fire doorsets (minimum E 20) (Diagram 2.2b).
NOTES:
1. This diagram does not apply where the gallery is provided with one of the following:
i. An alternative escape route
ii. An emergency escape window (where the gallery floor is not more than 4.5m above ground level).
2. Any cooking facilities within a room containing a gallery should comply with one of the following conditions:
i. Be enclosed with fire resisting construction
ii. Be remote from the stair to the gallery and positioned such that they do not prejudice escape from the gallery.
See para 2.15
NOTES:
1. This diagram does not apply where the gallery is provided with one of the following:
i. An alternative escape route
ii. An emergency escape window (where the gallery floor is not more than 4.5m above ground level).
2. Any cooking facilities within a room containing a gallery should comply with one of the following conditions:
i. Be enclosed with fire resisting construction
ii. Be remote from the stair to the gallery and positioned such that they do not prejudice escape from the gallery.
See para 3.13
Where a flat roof forms part of a means of escape, it should comply with all of the following.
a. It should be part of the same building from which escape is being made.
b. The route across the roof should lead to a storey exit or external escape route.
c. The part of the roof (including its supporting structure) forming the escape route, and any opening within 3m of the escape route, should be of fire resisting construction (minimum REI 30).
A balcony or flat roof intended to form part of an escape route should be provided with guarding etc. in accordance with Approved Document K.
All habitable rooms (excluding kitchens) should have either of the following.
a. An opening directly onto a hall leading to a final exit.
b. An emergency escape window or door, as described in paragraph 3.6.
Any alternative exit from a flat should comply with all of the following.
a. It should be remote from the main entrance door to the flat.
b. It should lead to a final exit, via a common stair if necessary, through one of the following.
i. A door to an access corridor, access lobby or common balcony.
ii. An internal private stair leading to an access corridor, access lobby or common balcony at another level.
iii. A door to a common stair.
iv. A door to an external stair.
v. A door to an escape route over a flat roof.
Any access route leading to a final exit or common stair should comply with the provisions for means of escape in the common parts of a flat (see paragraph 3.25).
A person escaping through the common area, if confronted by the effects of a fire in another flat, should be able to turn away from it and make a safe escape via an alternative route.
Provisions are recommended to support a stay put evacuation strategy for blocks of flats. It is based on the principle that a fire is contained in the flat of origin and common escape routes are maintained relatively free from smoke and heat. It allows occupants, some of whom may require assistance to escape in the event of a fire, in other flats that are not affected to remain.
Sufficient protection to common means of escape is necessary to allow occupants to escape should they choose to do so or are instructed/aided to by the fire service. A higher standard of protection is therefore needed to ensure common escape routes remain available for a longer period than is provided in other buildings.
Where a storey or part of a building has multiple escape routes available, one may be over a flat roof that complies with all of the following.
a. It should be part of the same building from which escape is being made.
b. The route across the roof should lead to a storey exit or external escape route.
c. The part of the roof (including its supporting structure) forming the escape route, and any opening within 3m of the escape route, should be of fire resisting construction (minimum REI 30).
d. The route should be clearly defined and guarded by walls and/or protective barriers to protect against falling.
Where a storey or part of a building has multiple escape routes available, one may be over a flat roof that complies with all of the following.
d. The route should be clearly defined and guarded by walls and/or protective barriers to protect against falling.
The following paragraphs deal with means of escape from the entrance doors of flats to a final exit.
Escape route travel distances should comply with Table 3.1.
Ancillary accommodation should not be located in, or entered from, a protected lobby or protected corridor forming the only common escape route on that storey.
Escape routes should have a minimum clear headroom of 2m. The only projections allowed below this height are door frames.
Escape route floor finishes should minimise their slipperiness when wet. Finishes include the treads of steps and surfaces of ramps and landings.
A ramp forming part of an escape route should meet the provisions in Approved Document M. Any sloping floor or tier should have a pitch of not more than 35 degrees to the horizontal.
All escape routes should have adequate artificial lighting. If the mains electricity power supply fails, escape lighting should illuminate the route (including external escape routes).
Escape stair lighting should be on a separate circuit from the electricity supply to any other part of the escape route.
Escape lighting should conform to BS 5266-1.
Every doorway or other exit providing access to a means of escape, other than exits in ordinary use (e.g. main entrances), should be distinctively and conspicuously marked by an exit sign in accordance with BS ISO 3864-1 and BS 5499-4. For this reason, blocks of flats with a single stair in regular use would not usually require any fire exit signage.
Advice on fire safety signs, including emergency escape signs, is given in the HSE publication Safety Signs and Signals: Guidance on Regulations.
Some buildings may require additional signs to comply with other legislation.
Access openings to refuse storage chambers should not be sited in the following areas.
a. Next to escape routes or final exits.
b. Near the windows of flats.
Where more than one escape route is available from a storey (or part of a building), then some of the escape routes from that storey or part of the building may be by way of an external stair provided all of the following conditions are met:
a. There is a at least one internal escape stair from every part of each storey (excluding plant areas).
b. The stair serves a floor not more than 6m above either the ground level or a roof podium which is itself served by an independent protected stairway.
c. The stair meets the provisions in paragraph 3.68.
The construction separating two adjacent protected stairways (or exit passageways leading to different final exits) should be imperforate.
If a building does not meet the criteria of paragraph 3.28, an escape stair forming part of the only escape route from an upper storey should not continue down to serve a basement storey. The basement storey should be served by a separate escape stair.
Except in buildings described in paragraph 3.28, common stairs forming part of the only escape route from a flat should not serve any of the following.
a. Covered car park.
b. Boiler room.
c. Fuel storage space.
d. Other ancillary accommodation of similar fire risk.
Where a common stair is not part of the only escape route from a flat, it may also serve ancillary accommodation from which it is separated by a protected lobby or protected corridor (minimum REI 30).
In single stair buildings, electricity meters should be in securely locked cupboards. Cupboards should be separated from the escape route by fire resisting construction.
Basement storeys containing habitable rooms should have one of the following.
a. An emergency escape window or external door providing escape from the basement (see paragraph 3.6).
b. A protected stairway (minimum REI 30) leading from the basement to a final exit.
evacuation lift
A passenger lift serving any storey more than 4.5m above ground level should be in either of the following.
a. The enclosure to the protected stairway, as described in paragraph 2.5.
b. A fire resisting lift shaft (minimum REI 30).
A protected stairway should not be used for anything else, except a lift well or electricity meters.
exempt buildings and work
Work should comply with Parts K and L of Schedule 1 to the Building Regulations. When complete, the building should comply with other applicable parts of Schedule 1 to at least the same level as before.
Where escape from a dwellinghouse is to an enclosed space with exit only possible through other buildings (e.g. a courtyard or back garden), the length of the space should exceed whichever is the greater of the following.
a. The height of the dwellinghouse above ground level (x).
b. Where a rear extension is provided, the height of the extension (y).
See para 2.10
exit passageway
Basement storeys containing habitable rooms should have one of the following.
a. An emergency escape window or external door providing escape from the basement (paragraph 2.10).
b. A protected stairway (paragraph 2.5a) leading from the basement to a final exit.
See para 2.5
Fire resisting construction minimum REI 30
Fd Fire doorset minimum E 20
See para 2.5
Alternative cavity barrier arrangements in roof space over protected stairway in a house with a storey more than 4.5m above ground level
See Diagram 2.1c. The dwellinghouse should have either of the following. Cavity barriers or a fire resisting ceiling (minimum EI 30) should be provided above a protected stairway enclosure (Diagram 2.3). b. Alternative escape route – a top storey separated from lower storeys by fire resisting construction (minimum REI 30) and with an alternative escape route leading to its own final exit.
a. Protected stairway – a stair separated by fire resisting construction (minimum REI 30) at all storeys, that complies with one of the following.
i. Extends to a final exit (Diagram 2.2a).
ii. Gives access to a minimum of two ground level final exits that are separated from each other by fire resisting construction (minimum REI 30) and fire doorsets (minimum E 20) (Diagram 2.2b).
All habitable rooms (excluding kitchens) should have either of the following.
a. An emergency escape window or external door, as described in paragraph 3.6.
b. In multi-storey flats, direct access to a protected internal stairway (minimum REI 30) leading to an exit from the flat.
Every common stair should be a protected stairway, within a fire resisting enclosure (minimum REI 30).
The construction separating two adjacent protected stairways (or exit passageways leading to different final exits) should be imperforate.
A protected stairway should not be used for anything else, except a lift well or electricity meters.
Every protected stairway should lead to a final exit, either directly or via a protected exit passageway. Any protected exit corridor or stair should have the same standard of fire resistance and lobby protection as the stair it serves.
Basement storeys containing habitable rooms should have one of the following.
a. An emergency escape window or external door providing escape from the basement (see paragraph 3.6).
b. A protected stairway (minimum REI 30) leading from the basement to a final exit.
explanation of terms used
In student residences that are designed and occupied as a block of flats, separate automatic detection should be provided in each self-contained flat where all of the following apply.
a. A group of up to six students shares the flat.
b. Each flat has its own entrance door.
c. The compartmentation principles for flats in Section 7 have been followed.
Where a total evacuation strategy is adopted, the alarm system should follow the guidance for buildings other than dwellings in Volume 2 of Approved Document B.
external wall
These provisions do not apply to the following.
a. The common parts of a sheltered housing development, such as communal lounges.
b. Sheltered accommodation in the 'residential (institutional)' or 'residential (other)' purpose groups (purpose group 2(a) or 2(b)).
In these parts, means of warning should follow the guidance for buildings other than dwellings in Volume 2 of Approved Document B.
Fire detection and alarm systems sometimes trigger other systems. The interface between systems
must be reliable. Particular care should be taken if the interface is facilitated via another system.
Where any part of BS 7273 applies to the triggering of other systems, the recommendations of that
part of BS 7273 should be followed.
Where a flat roof forms part of a means of escape, it should comply with all of the following.
a. It should be part of the same building from which escape is being made.
b. The route across the roof should lead to a storey exit or external escape route.
c. The part of the roof (including its supporting structure) forming the escape route, and any opening within 3m of the escape route, should be of fire resisting construction (minimum REI 30).
Any external escape stair should meet all of the following conditions (Diagram 2.7).
a. Doors to the stair should be fire resisting (minimum E 30), except for a single exit door from the building to the top landing of a downward-leading external stair.
b. Fire resisting construction (minimum RE 30) is required for the building envelope within the following zones, measured from the flights and landings of the external stair.
i. 1800mm horizontally.
ii. 9m vertically below.
iii. 1100mm above the top landing of the stair (except where the stair leads from basement to ground level).
c. Fire resisting construction (minimum RE 30) should be provided for any part of the building (including doors) within 1800mm of the escape route from the foot of the stair to a place of safety. This does not apply if there are alternative escape routes from the foot of the external escape stair.
d. Stairs more than 6m in height should be protected from adverse weather. Protection should prevent the build-up of snow or ice but does not require full enclosure.
e. Glazing in areas of fire resisting construction should be fixed shut and fire resisting (in terms of integrity, but not insulation) (minimum E 30).
Where escape from a dwellinghouse is to an enclosed space with exit only possible through other buildings (e.g. a courtyard or back garden), the length of the space should exceed whichever is the greater of the following.
a. The height of the dwellinghouse above ground level (x).
b. Where a rear extension is provided, the height of the extension (y).
See para 2.10
Where a flat roof forms part of a means of escape, it should comply with all of the following.
a. It should be part of the same building from which escape is being made.
b. The route across the roof should lead to a storey exit or external escape route.
c. The part of the roof (including its supporting structure) forming the escape route, and any opening within 3m of the escape route, should be of fire resisting construction (minimum REI 30).
For systems circulating air only within an individual flat, take all of the following precautions.
a. Transfer grilles should not be fitted in any wall, door, floor or ceiling of the enclosure.
b. Any duct passing through the enclosure should be rigid steel. Joints between the ductwork and enclosure should be fire-stopped.
c. Ventilation ducts serving the enclosure should not serve any other areas.
d. Any system of mechanical ventilation which recirculates air and which serves both the stair and other areas should be designed to shut down on the detection of smoke within the system.
e. For ducted warm air heating systems, a room thermostat should be sited in the living room. It should be mounted at a height between 1370mm and 1830mm above the floor. The maximum setting should be 27°C.
NOTE: Ventilation ducts passing through compartment walls should comply with the guidance in Section 9.
For flats serving as a workplace for both occupants and people who do not live on the premises, provide both of the following.
a. A maximum travel distance of 18m between any part of the working area and either of the following.
i. The flat entrance door.
ii. An alternative means of escape that is not a window.
If the travel distance is over 18m, the assumptions in paragraph 3.2 may not be valid. The design should be considered on a case-by-case basis.
b. Escape lighting to windowless accommodation in accordance with BS 5266-1.
Where a storey or part of a building has multiple escape routes available, one may be over a flat roof that complies with all of the following.
a. It should be part of the same building from which escape is being made.
b. The route across the roof should lead to a storey exit or external escape route.
c. The part of the roof (including its supporting structure) forming the escape route, and any opening within 3m of the escape route, should be of fire resisting construction (minimum REI 30).
d. The route should be clearly defined and guarded by walls and/or protective barriers to protect against falling.
Where a storey or part of a building has multiple escape routes available, one may be over a flat roof that complies with all of the following.
d. The route should be clearly defined and guarded by walls and/or protective barriers to protect against falling.
A ramp forming part of an escape route should meet the provisions in Approved Document M. Any sloping floor or tier should have a pitch of not more than 35 degrees to the horizontal.
Smoke vents should comply with one of the following.
a. They should be located on an external wall with minimum free area of 1.5m2.
b. They should discharge into a vertical smoke shaft, closed at the base, that meets all of the following criteria.
i. The shaft should conform to the following conditions.
• Have a minimum cross-sectional area of 1.5m2 (minimum dimension 0.85m in any direction).
• Open at roof level, minimum 0.5m above any surrounding structures within 2m of it horizontally.
• Extend a minimum of 2.5m above the ceiling of the highest storey served by the shaft.
ii. The free area of all the following vents should be a minimum of 1m2 in the following places.
• From the corridor or lobby into the shaft.
• At the opening at the head of the shaft.
• At all internal locations within the shaft (e.g. safety grilles).
iii. The smoke shaft should be constructed from a class A1 material. All vents should either be a fire doorset (see Appendix C, Table C1, item 2.e for minimum fire resistance) or fitted with a smoke control damper achieving the same period of fire resistance and designed to operate as described below. The shaft should be vertical from base to head, with a maximum of 4m at a maximum inclined angle of 30 degrees.
iv. If smoke is detected in the common corridor or lobby, both of the following should occur.
• Simultaneous opening of vents on the storey where the fire is located, at the top of the smoke shaft and to the stair.
• Vents from the corridors or lobbies on all other storeys should remain closed, even if smoke is subsequently detected on storeys other than where the fire is located.
With some configurations of external wall, a fire in one part of a building could subject the external wall of a protected stairway to heat (for example, where the two are adjacent at an internal angle in the façade, as shown in Diagram 3.10).
If a protected stairway projects beyond, is recessed from or is in an internal angle of the adjoining external wall of the building, then the minimum distance between an unprotected area of the building enclosure and an unprotected area of the stair enclosure should be 1800mm.
Any external escape stair should meet all of the following conditions (Diagram 3.11).
a. Doors to the stair should be fire resisting (minimum E 30) and be fitted with a self-closing device, except for a single exit door from the building to the top landing of a downward-leading external stair, provided it is the only door onto the landing.
b. Fire resisting construction (minimum RE 30) is required for the building envelope within the following zones, measured from the flights and landings of the external stair.
i. 1800mm above and horizontally.
ii. 9m vertically below.
iii. 1100mm above the top landing of the stair (except where the stair leads from basement to ground level).
c. Fire resisting construction (minimum RE 30) should be provided for any part of the building (including doors) within 1800mm of the escape route from the foot of the stair to a place of safety. This does not apply if there are alternative escape routes from the foot of the external escape stair.
d. Glazing in areas of fire resisting construction should be fixed shut and fire resisting (in terms of integrity but not insulation) (minimum E 30).
e. Stairs more than 6m in height above ground level (e.g. where they are provided above a podium) should be protected from adverse weather. Protection should prevent the build-up of snow or ice but does not require full enclosure.
Access to an external escape stair may be via a flat roof, provided the flat roof meets the requirements of paragraph 3.30.
Except in buildings described in paragraph 3.28, common stairs forming part of the only escape route from a flat should not serve any of the following.
a. Covered car park.
b. Boiler room.
c. Fuel storage space.
d. Other ancillary accommodation of similar fire risk.
If a loadbearing wall is any of the following, guidance in other sections may also apply.
a. A compartment wall (including a wall common to two buildings): Section 7.
b. Enclosing a place of special fire hazard: Section 7.
c. Protecting a means of escape: Sections 2 and 3.
d. An external wall: Sections 10 and 11.
e. Enclosing a firefighting shaft: Section 15.
final certificate
Work should comply with Parts K and L of Schedule 1 to the Building Regulations. When complete, the building should comply with other applicable parts of Schedule 1 to at least the same level as before.
One of the following approaches should be adopted, observing the inner room restrictions described in paragraphs 3.7 and 3.8.
a. Provide a protected entrance hall (minimum REI 30) serving all habitable rooms that meets the conditions shown in Diagram 3.2.
b. Plan the flat to meet the conditions shown in Diagram 3.3, so that both of the following apply.
i. The travel distance from the flat entrance door to any point in any habitable room is a maximum of 9m.
ii. Cooking facilities are remote from the main entrance door and do not impede the escape route from anywhere in the flat.
c. Provide an alternative exit from the flat complying with paragraph 3.22.
The following paragraphs deal with means of escape from the entrance doors of flats to a final exit. They do not apply to flats with a top storey that is a maximum of 4.5m above ground level (designed in accordance with paragraphs 3.16 and 3.17).
Reference should also be made to the following.
a. Requirement B3 regarding compartment walls and protected shafts.
b. Requirement B5 regarding access for the fire and rescue service.
Except in buildings that comply with Diagram 3.9, the corridor or lobby next to each stair should have a smoke vent. The location of the vent should comply with both of the following.
a. Be as high as practicable.
b. Be positioned so the top edge is at least as high as the top of the door to the stair.
In single stair buildings, smoke vents on the storey where the fire is initiated, and the vent at the head of the stair, should be activated by smoke detectors in the common parts.
In buildings with more than one stair, smoke vents may be activated manually. The control system should open the vent at the head of the stair before, or at the same time as, the vent on the storey where the fire is located. Smoke detection is not required for ventilation purposes in this instance.
final exit
In the Secretary of State’s view, requirement B1 is met by achieving all of the following.
a. There are sufficient means for giving early warning of fire to people in the building.
b. All people can escape to a place of safety without external assistance.
c. Escape routes are suitably located, sufficient in number and of adequate capacity.
d. Where necessary, escape routes are sufficiently protected from the effects of fire and smoke.
e. Escape routes are adequately lit and exits are suitably signed.
f. There are appropriate provisions to limit the ingress of smoke to the escape routes, or to
restrict the spread of fire and remove smoke.
g. For buildings containing flats, there are appropriate provisions to support a stay put evacuation
strategy.
The extent to which any of these measures are necessary is dependent on the use of the building,
its size and its height.
Building work and material changes of use subject to requirement B1 include both new and existing
buildings.
A person escaping through the common area, if confronted by the effects of a fire in another flat, should be able to turn away from it and make a safe escape via an alternative route.
Provisions are recommended to support a stay put evacuation strategy for blocks of flats. It is based on the principle that a fire is contained in the flat of origin and common escape routes are maintained relatively free from smoke and heat. It allows occupants, some of whom may require assistance to escape in the event of a fire, in other flats that are not affected to remain.
Sufficient protection to common means of escape is necessary to allow occupants to escape should they choose to do so or are instructed/aided to by the fire service. A higher standard of protection is therefore needed to ensure common escape routes remain available for a longer period than is provided in other buildings.
The following paragraphs deal with means of escape from the entrance doors of flats to a final exit.
Access openings to refuse storage chambers should not be sited in the following areas.
a. Next to escape routes or final exits.
b. Near the windows of flats.
The construction separating two adjacent protected stairways (or exit passageways leading to different final exits) should be imperforate.
fire alarm system
All dwellings should have a fire detection and alarm system, minimum Grade D2 Category LD3
standard, in accordance with the relevant recommendations of BS 5839-6.
A higher standard of protection should be considered where occupants of a proposed dwelling
would be at special risk from fire. Further advice on this is also given in BS 5839-6.
Each flat in a block should have alarms as set out in paragraphs 1.1 to 1.4. With effective compartmentation, a communal fire alarm system is not normally needed. In some buildings, detectors in common parts of the building may need to operate smoke control or other fire protection systems but do not usually sound an audible warning.
The fire detection and alarm systems in flats should connect to a central monitoring point or alarm
receiving centre. The systems should alert the warden or supervisor and identify the individual flat
where a fire has been detected.
Fire detection and alarm systems must be properly designed, installed and maintained. A design,
installation and commissioning certificate should be provided for fire detection and alarm systems.
Third party certification schemes for fire protection products and related services are an effective
means of providing assurances of quality, reliability and safety.
Fire detection and alarm systems sometimes trigger other systems. The interface between systems
must be reliable. Particular care should be taken if the interface is facilitated via another system.
Where any part of BS 7273 applies to the triggering of other systems, the recommendations of that
part of BS 7273 should be followed.
Smoke alarms should be mains operated and conform to BS EN 14604.
Heat alarms should be mains operated and conform to BS 5446-2.
Smoke and heat alarms should have a standby power supply, such as a battery (rechargeable
or non-rechargeable) or capacitor. More information on power supplies is given in clause 15 of
BS 5839-6.
NOTE: The term ‘fire alarm system’ describes the combination of components for giving an audible
and/or other perceptible warning of fire.
NOTE: In this document, the term ‘fire detection system’ describes any type of automatic sensor
network and associated control and indicating equipment. Sensors may be sensitive to smoke,
heat, gaseous combustion products or radiation. Automatic sprinkler systems can also be used to
operate a fire alarm system.
A large dwellinghouse of two storeys (excluding basement storeys) should be fitted with a Grade A
Category LD3 fire detection and alarm system, as described in BS 5839-6.
A large dwellinghouse of three or more storeys (excluding basement storeys) should be fitted with
a Grade A Category LD2 fire detection and alarm system as described in BS 5839-6.
fire and smoke damper
Smoke alarms should be mains operated and conform to BS EN 14604.
Smoke and heat alarms should have a standby power supply, such as a battery (rechargeable
or non-rechargeable) or capacitor. More information on power supplies is given in clause 15 of
BS 5839-6.
NOTE: The term ‘fire alarm system’ describes the combination of components for giving an audible
and/or other perceptible warning of fire.
NOTE: In this document, the term ‘fire detection system’ describes any type of automatic sensor
network and associated control and indicating equipment. Sensors may be sensitive to smoke,
heat, gaseous combustion products or radiation. Automatic sprinkler systems can also be used to
operate a fire alarm system.
Fire resisting window(minimum RE30)
No fire resistance required for door
1100mm zone above top landing
6m max. height without weather protection
1800mm zone of fire resisting construction at side of stairway
Fire doorset(minimum E30)
See para 2.17
Despite the provisions described, it is probable that some smoke will get into the common corridor or lobby from a fire in a flat.
There should therefore be some means of ventilating the common corridors/lobbies to control smoke and so protect the common stairs. This means of ventilation offers additional protection to that provided by the fire doors to the stair, as well as some protection to the corridors/lobbies.
Ventilation can be natural (paragraphs 3.50 to 3.53) or mechanical (paragraph 3.54).
Smoke vents should comply with one of the following.
a. They should be located on an external wall with minimum free area of 1.5m2.
b. They should discharge into a vertical smoke shaft, closed at the base, that meets all of the following criteria.
i. The shaft should conform to the following conditions.
• Have a minimum cross-sectional area of 1.5m2 (minimum dimension 0.85m in any direction).
• Open at roof level, minimum 0.5m above any surrounding structures within 2m of it horizontally.
• Extend a minimum of 2.5m above the ceiling of the highest storey served by the shaft.
ii. The free area of all the following vents should be a minimum of 1m2 in the following places.
• From the corridor or lobby into the shaft.
• At the opening at the head of the shaft.
• At all internal locations within the shaft (e.g. safety grilles).
iii. The smoke shaft should be constructed from a class A1 material. All vents should either be a fire doorset (see Appendix C, Table C1, item 2.e for minimum fire resistance) or fitted with a smoke control damper achieving the same period of fire resistance and designed to operate as described below. The shaft should be vertical from base to head, with a maximum of 4m at a maximum inclined angle of 30 degrees.
iv. If smoke is detected in the common corridor or lobby, both of the following should occur.
• Simultaneous opening of vents on the storey where the fire is located, at the top of the smoke shaft and to the stair.
• Vents from the corridors or lobbies on all other storeys should remain closed, even if smoke is subsequently detected on storeys other than where the fire is located.
In single stair buildings, smoke vents on the storey where the fire is initiated, and the vent at the head of the stair, should be activated by smoke detectors in the common parts.
In buildings with more than one stair, smoke vents may be activated manually. The control system should open the vent at the head of the stair before, or at the same time as, the vent on the storey where the fire is located. Smoke detection is not required for ventilation purposes in this instance.
Guidance on the design of smoke control systems that use pressure differentials is available in BS EN 12101-6.
Where a stair serves an enclosed car park or place of special fire hazard, the lobby or corridor should have a minimum 0.4m2 of permanent ventilation or be protected from the ingress of smoke by a mechanical smoke control system.
NOTE: For refuse chutes and storage see paragraphs 3.55 to 3.58.
fire compartment
A large dwellinghouse has more than one storey, and at least one storey exceeds 200m2.
A large dwellinghouse of two storeys (excluding basement storeys) should be fitted with a Grade A
Category LD3 fire detection and alarm system, as described in BS 5839-6.
A large dwellinghouse of three or more storeys (excluding basement storeys) should be fitted with
a Grade A Category LD2 fire detection and alarm system as described in BS 5839-6.
Where new habitable rooms are provided, a fire detection and alarm system should be installed
where either of the following applies.
a. The room is provided above or below the ground storey.
b. The room is provided at the ground storey, without a final exit.
An alternative approach to that described in paragraph 2.21 would be to comply with all of the following.
a. Provide sprinkler protection to the open-plan areas.
b. Provide a fire resisting partition (minimum REI 30) and door (minimum E 20) to separate the ground storey from the upper storeys. The door should allow occupants of the loft room access to a first storey escape window.
c. Separate cooking facilities from the open-plan area with fire resisting construction (minimum REI 30).
See para 2.6
Example of alternative exit in para 2.6(a) (see definition in Appendix A)
See Diagram 2.1c. The dwellinghouse should have either of the following. Cavity barriers or a fire resisting ceiling (minimum EI 30) should be provided above a protected stairway enclosure (Diagram 2.3). b. Alternative escape route – a top storey separated from lower storeys by fire resisting construction (minimum REI 30) and with an alternative escape route leading to its own final exit.
a. Protected stairway – a stair separated by fire resisting construction (minimum REI 30) at all storeys, that complies with one of the following.
i. Extends to a final exit (Diagram 2.2a).
ii. Gives access to a minimum of two ground level final exits that are separated from each other by fire resisting construction (minimum REI 30) and fire doorsets (minimum E 20) (Diagram 2.2b).
Where escape from a dwellinghouse is to an enclosed space with exit only possible through other buildings (e.g. a courtyard or back garden), the length of the space should exceed whichever is the greater of the following.
a. The height of the dwellinghouse above ground level (x).
b. Where a rear extension is provided, the height of the extension (y).
See para 2.10
See Diagram 2.1d. In addition to meeting the provisions in paragraph 2.5, the dwellinghouse should comply with either of the following.
a. Provide an alternative escape route from each storey more than 7.5m above ground level. At the first storey above 7.5m, the protected stairway should be separated from the lower storeys by fire resisting construction (minimum REI 30) if the alternative escape route is accessed via either of the following.
i. The protected stairway to an upper storey.
ii. A landing within the protected stairway enclosure to an alternative escape route on the same storey. The protected stairway at or about 7.5m above ground level should be separated from the lower storeys or levels by fire resisting construction (see Diagram 2.4).
b. Provide a sprinkler system throughout, designed and installed in accordance with BS 9251.
A passenger lift serving any storey more than 4.5m above ground level should be in either of the following.
a. The enclosure to the protected stairway, as described in paragraph 2.5.
b. A fire resisting lift shaft (minimum REI 30).
Fire resisting window(minimum RE30)
No fire resistance required for door
1100mm zone above top landing
6m max. height without weather protection
1800mm zone of fire resisting construction at side of stairway
Fire doorset(minimum E30)
See para 2.17
No fire resistance required for door
1100mm zone above top landing
1100mm zone above top landing
6m maximum height of stair
Fire resisting window (minimum RE30)
1800mm zone of fire resisting construction at side of stair
Fire doorset (minimum E30)
Ground level or a roof or podium served by an independent stairway
6m maximum height of stair without weather protection
9m zone of fire resisting construction below stair
Ground level or a roof or podium served by an independent stairway
See para 3.68
See para 3.18
NOTE: Bathrooms do not need to have fire doorsets provided that the bathroom is separated by fire resisting construction from the adjacent rooms.
Common corridors should be protected corridors. The wall between each flat and the corridor should be a compartment wall (minimum REI 30 where the top storey is up to 5m above ground level, otherwise REI 60).
Divide a common corridor connecting two or more storey exits with a fire doorset fitted with a self-closing device (minimum E 30 Sa). See Diagram 3.8. Associated screens should be fire resisting. Site doors so that smoke does not affect access to more than one stair.
A protected circuit to operate equipment during a fire should achieve all of the following.
a. Cables should achieve PH 30 classification when tested in accordance with BS EN 50200 (incorporating Annex E) or an equivalent standard.
b. It should only pass through parts of the building in which the fire risk is negligible.
c. It should be separate from any circuit provided for another purpose.
Refuse chutes and rooms for storing refuse should meet both of the following conditions.
a. Be separated from other parts of the building by fire resisting construction (minimum REI 30 in buildings with a top storey up to 5m above ground level; otherwise REI 60).
b. Not be situated within a protected stairway or protected lobby.
See para 3.21
NOTE: This only applies where at least one storey is more than 4.5m above ground level.
Fire doorset
Fire resisting stair enclosure(minimum REI 30)
Alternative exit
Where more than one escape route is available from a storey (or part of a building), then some of the escape routes from that storey or part of the building may be by way of an external stair provided all of the following conditions are met:
a. There is a at least one internal escape stair from every part of each storey (excluding plant areas).
b. The stair serves a floor not more than 6m above either the ground level or a roof podium which is itself served by an independent protected stairway.
c. The stair meets the provisions in paragraph 3.68.
In buildings with a maximum of three storeys above the ground storey, stairs may serve both flats and other occupancies, provided that the stairs are separated from each occupancy by protected lobbies (minimum REI 30) at each storey.
In buildings with more than three storeys above the ground storey, stairs may serve the flats and other occupancies if all of the following apply.
a. The flat is ancillary to the main use of the building.
b. The flat has an independent alternative escape route.
c. The stair is separated from occupancies on lower storeys by a protected lobby (minimum REI 30) at each of those storeys.
d. The stair enclosure has at least the same standard of fire resistance as the structural elements of the building (see Appendix B, Table B4); if the stair is a firefighting stair, it should comply with the provisions in Section 15 (see also paragraph 3.60).
e. Any automatic fire detection and alarm system fitted in the main part of the building also covers all flats.
f. Any security measures in any parts of the building do not prevent escape at all material times.
In a converted building with a maximum of three storeys, a minimum REI 30 fire resistance could be accepted for elements of structure if the means of escape conform to the provisions of Section 3.
fire damper
Fire resisting window(minimum RE30)
No fire resistance required for door
1100mm zone above top landing
6m max. height without weather protection
1800mm zone of fire resisting construction at side of stairway
Fire doorset(minimum E30)
See para 2.17
A fire doorset (minimum E 30 Sa) fitted with a self-closing device (and fire resisting screen, where required) should separate the dead-end portion of a common corridor from the rest of the corridor (Diagrams 3.7a, 3.8b and 3.8c).
Every common stair should be a protected stairway, within a fire resisting enclosure (minimum REI 30).
fire doorset
Fire detection and alarm systems must be properly designed, installed and maintained. A design,
installation and commissioning certificate should be provided for fire detection and alarm systems.
Third party certification schemes for fire protection products and related services are an effective
means of providing assurances of quality, reliability and safety.
A fire doorset (minimum E 30 Sa) fitted with a self-closing device (and fire resisting screen, where required) should separate the dead-end portion of a common corridor from the rest of the corridor (Diagrams 3.7a, 3.8b and 3.8c).
a. CORRIDOR ACCESS WITHOUT DEAD ENDS
b. CORRIDOR ACCESS WITH DEAD ENDS
The central door may be omitted if maximum travel distance is not more than 15m.
1. The arrangements shown also apply to the top storey.
2. For further guidance on the fire rating of the fire doorsets from the corridor to the flat and/or stairway refer to Appendix C ,Table C1.
Fire doorset provided in accordance with paragraphs 3.50 to 3.53(An external wall vent or smoke shaft located anywhere in the shaded area)
See paras 3.27 and 3.36
fire resistance
Smoke and heat alarms should have a standby power supply, such as a battery (rechargeable
or non-rechargeable) or capacitor. More information on power supplies is given in clause 15 of
BS 5839-6.
NOTE: The term ‘fire alarm system’ describes the combination of components for giving an audible
and/or other perceptible warning of fire.
NOTE: In this document, the term ‘fire detection system’ describes any type of automatic sensor
network and associated control and indicating equipment. Sensors may be sensitive to smoke,
heat, gaseous combustion products or radiation. Automatic sprinkler systems can also be used to
operate a fire alarm system.
See para 2.5
Fire resisting construction minimum REI 30
Fd Fire doorset minimum E 20
See para 2.6
Example of alternative exit in para 2.6(a) (see definition in Appendix A)
See Diagram 2.1c. The dwellinghouse should have either of the following. Cavity barriers or a fire resisting ceiling (minimum EI 30) should be provided above a protected stairway enclosure (Diagram 2.3). b. Alternative escape route – a top storey separated from lower storeys by fire resisting construction (minimum REI 30) and with an alternative escape route leading to its own final exit.
a. Protected stairway – a stair separated by fire resisting construction (minimum REI 30) at all storeys, that complies with one of the following.
i. Extends to a final exit (Diagram 2.2a).
ii. Gives access to a minimum of two ground level final exits that are separated from each other by fire resisting construction (minimum REI 30) and fire doorsets (minimum E 20) (Diagram 2.2b).
Fire resisting window(minimum RE30)
No fire resistance required for door
1100mm zone above top landing
6m max. height without weather protection
1800mm zone of fire resisting construction at side of stairway
Fire doorset(minimum E30)
See para 2.17
Configurations of stairs and external wall
Fire resisting construction
Fire resisting construction of adjacent building enclosure of protected stairway
Non-fire resisting construction
See para 3.63
No fire resistance required for door
1100mm zone above top landing
1100mm zone above top landing
6m maximum height of stair
Fire resisting window (minimum RE30)
1800mm zone of fire resisting construction at side of stair
Fire doorset (minimum E30)
Ground level or a roof or podium served by an independent stairway
6m maximum height of stair without weather protection
9m zone of fire resisting construction below stair
Ground level or a roof or podium served by an independent stairway
See para 3.68
See para 3.18
NOTE: Bathrooms do not need to have fire doorsets provided that the bathroom is separated by fire resisting construction from the adjacent rooms.
Divide a common corridor connecting two or more storey exits with a fire doorset fitted with a self-closing device (minimum E 30 Sa). See Diagram 3.8. Associated screens should be fire resisting. Site doors so that smoke does not affect access to more than one stair.
See para 3.19
NOTE: The bedrooms are not classified as inner rooms because escape is possible in two directions.
Fire doorset
Fire resisting construction (minimum REI 30) between living and bedroom accommodation
Alternative exit
See para 3.21
NOTE: This only applies where at least one storey is more than 4.5m above ground level.
Fire doorset
Fire resisting stair enclosure(minimum REI 30)
Alternative exit
Every common stair should be a protected stairway, within a fire resisting enclosure (minimum REI 30).
In single stair buildings, electricity meters should be in securely locked cupboards. Cupboards should be separated from the escape route by fire resisting construction.
fire resisting (Fire resistance)
All dwellings should have a fire detection and alarm system, minimum Grade D2 Category LD3
standard, in accordance with the relevant recommendations of BS 5839-6.
A higher standard of protection should be considered where occupants of a proposed dwelling
would be at special risk from fire. Further advice on this is also given in BS 5839-6.
Any external escape stair should meet all of the following conditions (Diagram 2.7).
a. Doors to the stair should be fire resisting (minimum E 30), except for a single exit door from the building to the top landing of a downward-leading external stair.
b. Fire resisting construction (minimum RE 30) is required for the building envelope within the following zones, measured from the flights and landings of the external stair.
i. 1800mm horizontally.
ii. 9m vertically below.
iii. 1100mm above the top landing of the stair (except where the stair leads from basement to ground level).
c. Fire resisting construction (minimum RE 30) should be provided for any part of the building (including doors) within 1800mm of the escape route from the foot of the stair to a place of safety. This does not apply if there are alternative escape routes from the foot of the external escape stair.
d. Stairs more than 6m in height should be protected from adverse weather. Protection should prevent the build-up of snow or ice but does not require full enclosure.
e. Glazing in areas of fire resisting construction should be fixed shut and fire resisting (in terms of integrity, but not insulation) (minimum E 30).
Fire resisting window(minimum RE30)
No fire resistance required for door
1100mm zone above top landing
6m max. height without weather protection
1800mm zone of fire resisting construction at side of stairway
Fire doorset(minimum E30)
See para 2.17
Configurations of stairs and external wall
Fire resisting construction
Fire resisting construction of adjacent building enclosure of protected stairway
Non-fire resisting construction
See para 3.63
No fire resistance required for door
1100mm zone above top landing
1100mm zone above top landing
6m maximum height of stair
Fire resisting window (minimum RE30)
1800mm zone of fire resisting construction at side of stair
Fire doorset (minimum E30)
Ground level or a roof or podium served by an independent stairway
6m maximum height of stair without weather protection
9m zone of fire resisting construction below stair
Ground level or a roof or podium served by an independent stairway
See para 3.68
Every common stair should be a protected stairway, within a fire resisting enclosure (minimum REI 30).
In a converted building with a maximum of three storeys, a minimum REI 30 fire resistance could be accepted for elements of structure if the means of escape conform to the provisions of Section 3.
fire risk assessment
All dwellings should have a fire detection and alarm system, minimum Grade D2 Category LD3
standard, in accordance with the relevant recommendations of BS 5839-6.
A higher standard of protection should be considered where occupants of a proposed dwelling
would be at special risk from fire. Further advice on this is also given in BS 5839-6.
The fire detection and alarm systems in flats should connect to a central monitoring point or alarm
receiving centre. The systems should alert the warden or supervisor and identify the individual flat
where a fire has been detected.
Fire detection and alarm systems must be properly designed, installed and maintained. A design,
installation and commissioning certificate should be provided for fire detection and alarm systems.
Third party certification schemes for fire protection products and related services are an effective
means of providing assurances of quality, reliability and safety.
Smoke and heat alarms should have a standby power supply, such as a battery (rechargeable
or non-rechargeable) or capacitor. More information on power supplies is given in clause 15 of
BS 5839-6.
NOTE: The term ‘fire alarm system’ describes the combination of components for giving an audible
and/or other perceptible warning of fire.
NOTE: In this document, the term ‘fire detection system’ describes any type of automatic sensor
network and associated control and indicating equipment. Sensors may be sensitive to smoke,
heat, gaseous combustion products or radiation. Automatic sprinkler systems can also be used to
operate a fire alarm system.
The provisions in this section make the following assumptions.
a. Any fire is likely to be in a flat.
b. There is no reliance on external rescue.
c. Simultaneous evacuation of all flats is unlikely to be necessary due to compartmentation.
d. Fires in common parts of the building should not spread beyond the fabric in the immediate vicinity. In some cases, however, communal facilities exist that require additional measures to be taken.
See para 3.18
NOTE: Bathrooms do not need to have fire doorsets provided that the bathroom is separated by fire resisting construction from the adjacent rooms.
A fire doorset (minimum E 30 Sa) fitted with a self-closing device (and fire resisting screen, where required) should separate the dead-end portion of a common corridor from the rest of the corridor (Diagrams 3.7a, 3.8b and 3.8c).
A protected circuit to operate equipment during a fire should achieve all of the following.
a. Cables should achieve PH 30 classification when tested in accordance with BS EN 50200 (incorporating Annex E) or an equivalent standard.
b. It should only pass through parts of the building in which the fire risk is negligible.
c. It should be separate from any circuit provided for another purpose.
Smoke vents should comply with one of the following.
a. They should be located on an external wall with minimum free area of 1.5m2.
b. They should discharge into a vertical smoke shaft, closed at the base, that meets all of the following criteria.
i. The shaft should conform to the following conditions.
• Have a minimum cross-sectional area of 1.5m2 (minimum dimension 0.85m in any direction).
• Open at roof level, minimum 0.5m above any surrounding structures within 2m of it horizontally.
• Extend a minimum of 2.5m above the ceiling of the highest storey served by the shaft.
ii. The free area of all the following vents should be a minimum of 1m2 in the following places.
• From the corridor or lobby into the shaft.
• At the opening at the head of the shaft.
• At all internal locations within the shaft (e.g. safety grilles).
iii. The smoke shaft should be constructed from a class A1 material. All vents should either be a fire doorset (see Appendix C, Table C1, item 2.e for minimum fire resistance) or fitted with a smoke control damper achieving the same period of fire resistance and designed to operate as described below. The shaft should be vertical from base to head, with a maximum of 4m at a maximum inclined angle of 30 degrees.
iv. If smoke is detected in the common corridor or lobby, both of the following should occur.
• Simultaneous opening of vents on the storey where the fire is located, at the top of the smoke shaft and to the stair.
• Vents from the corridors or lobbies on all other storeys should remain closed, even if smoke is subsequently detected on storeys other than where the fire is located.
In single stair buildings, smoke vents on the storey where the fire is initiated, and the vent at the head of the stair, should be activated by smoke detectors in the common parts.
In buildings with more than one stair, smoke vents may be activated manually. The control system should open the vent at the head of the stair before, or at the same time as, the vent on the storey where the fire is located. Smoke detection is not required for ventilation purposes in this instance.
See paras 3.27 and 3.36
NOTES:
1. The arrangements shown also apply to the top storey.
2. See Diagram 3.9 for small single stair buildings.
3. All doors shown are fire doorsets.
4. Where travel distance is measured to a stair lobby, the lobby must not provide direct access to any storage room, flat or other space containing a potential fire hazard.
5. For further guidance on the fire rating of the fire doorsets from the corridor to the flat and/or stairway refer to Appendix C ,Table C1.
F Flat
Shaded areas indicate zones where ventilation should be provided in accordance with paragraphs 3.50 to 3.53(An external wall vent or smoke shaft located anywhere in the shaded area)
a. CORRIDOR ACCESS WITHOUT DEAD ENDS
b. CORRIDOR ACCESS WITH DEAD ENDS
The central door may be omitted if maximum travel distance is not more than 15m.
1. The arrangements shown also apply to the top storey.
2. For further guidance on the fire rating of the fire doorsets from the corridor to the flat and/or stairway refer to Appendix C ,Table C1.
Fire doorset provided in accordance with paragraphs 3.50 to 3.53(An external wall vent or smoke shaft located anywhere in the shaded area)
See paras 3.27 and 3.36
In a converted building with a maximum of three storeys, a minimum REI 30 fire resistance could be accepted for elements of structure if the means of escape conform to the provisions of Section 3.
fire safety - volume 1: dwellings. 2019 edition - for use in england
Means of warning and escape
B1.The building shall be designed and constructed so that there are appropriate provisions for the early warning of fire, and appropriate means of escape in case of fire from the building to a place of safety outside the building capable of being safely and effectively used at all material times.
Requirement B1 does not apply to any prison provided under section 33 of the Prison Act 1952
(a) (power to provide prisons, etc.).
(a) 1952 c. 52; section 33 was amended by section 100 of the Criminal Justice and Public Order Act 1994 (c. 33) and by S.I. 1963/597.
In the Secretary of State’s view, requirement B1 is met by achieving all of the following.
a. There are sufficient means for giving early warning of fire to people in the building.
b. All people can escape to a place of safety without external assistance.
c. Escape routes are suitably located, sufficient in number and of adequate capacity.
d. Where necessary, escape routes are sufficiently protected from the effects of fire and smoke.
e. Escape routes are adequately lit and exits are suitably signed.
f. There are appropriate provisions to limit the ingress of smoke to the escape routes, or to
restrict the spread of fire and remove smoke.
g. For buildings containing flats, there are appropriate provisions to support a stay put evacuation
strategy.
The extent to which any of these measures are necessary is dependent on the use of the building,
its size and its height.
Building work and material changes of use subject to requirement B1 include both new and existing
buildings.
All dwellings should have a fire detection and alarm system, minimum Grade D2 Category LD3
standard, in accordance with the relevant recommendations of BS 5839-6.
A higher standard of protection should be considered where occupants of a proposed dwelling
would be at special risk from fire. Further advice on this is also given in BS 5839-6.
Each flat in a block should have alarms as set out in paragraphs 1.1 to 1.4. With effective compartmentation, a communal fire alarm system is not normally needed. In some buildings, detectors in common parts of the building may need to operate smoke control or other fire protection systems but do not usually sound an audible warning.
The fire detection and alarm systems in flats should connect to a central monitoring point or alarm
receiving centre. The systems should alert the warden or supervisor and identify the individual flat
where a fire has been detected.
Fire detection and alarm systems must be properly designed, installed and maintained. A design,
installation and commissioning certificate should be provided for fire detection and alarm systems.
Third party certification schemes for fire protection products and related services are an effective
means of providing assurances of quality, reliability and safety.
Smoke and heat alarms should have a standby power supply, such as a battery (rechargeable
or non-rechargeable) or capacitor. More information on power supplies is given in clause 15 of
BS 5839-6.
NOTE: The term ‘fire alarm system’ describes the combination of components for giving an audible
and/or other perceptible warning of fire.
NOTE: In this document, the term ‘fire detection system’ describes any type of automatic sensor
network and associated control and indicating equipment. Sensors may be sensitive to smoke,
heat, gaseous combustion products or radiation. Automatic sprinkler systems can also be used to
operate a fire alarm system.
A large dwellinghouse of two storeys (excluding basement storeys) should be fitted with a Grade A
Category LD3 fire detection and alarm system, as described in BS 5839-6.
The provisions in this section make the following assumptions.
a. Any fire is likely to be in a flat.
b. There is no reliance on external rescue.
c. Simultaneous evacuation of all flats is unlikely to be necessary due to compartmentation.
d. Fires in common parts of the building should not spread beyond the fabric in the immediate vicinity. In some cases, however, communal facilities exist that require additional measures to be taken.
The following paragraphs deal with means of escape from the entrance doors of flats to a final exit. They do not apply to flats with a top storey that is a maximum of 4.5m above ground level (designed in accordance with paragraphs 3.16 and 3.17).
Reference should also be made to the following.
a. Requirement B3 regarding compartment walls and protected shafts.
b. Requirement B5 regarding access for the fire and rescue service.
A fire doorset (minimum E 30 Sa) fitted with a self-closing device (and fire resisting screen, where required) should separate the dead-end portion of a common corridor from the rest of the corridor (Diagrams 3.7a, 3.8b and 3.8c).
Paragraphs 3.6 to 3.23 deal with the means of escape within each flat. Paragraphs 3.25 to 3.89 deal with the means of escape in common areas of the building (including mixed use buildings in paragraphs 3.76 and 3.77). Guidance for live/work units is given in paragraph 3.24.
See para 3.19
NOTE: The bedrooms are not classified as inner rooms because escape is possible in two directions.
Fire doorset
Fire resisting construction (minimum REI 30) between living and bedroom accommodation
Alternative exit
Every doorway or other exit providing access to a means of escape, other than exits in ordinary use (e.g. main entrances), should be distinctively and conspicuously marked by an exit sign in accordance with BS ISO 3864-1 and BS 5499-4. For this reason, blocks of flats with a single stair in regular use would not usually require any fire exit signage.
Advice on fire safety signs, including emergency escape signs, is given in the HSE publication Safety Signs and Signals: Guidance on Regulations.
Some buildings may require additional signs to comply with other legislation.
See paras 3.27 and 3.36
NOTES:
1. The arrangements shown also apply to the top storey.
2. See Diagram 3.9 for small single stair buildings.
3. All doors shown are fire doorsets.
4. Where travel distance is measured to a stair lobby, the lobby must not provide direct access to any storage room, flat or other space containing a potential fire hazard.
5. For further guidance on the fire rating of the fire doorsets from the corridor to the flat and/or stairway refer to Appendix C ,Table C1.
F Flat
Shaded areas indicate zones where ventilation should be provided in accordance with paragraphs 3.50 to 3.53(An external wall vent or smoke shaft located anywhere in the shaded area)
a. CORRIDOR ACCESS WITHOUT DEAD ENDS
b. CORRIDOR ACCESS WITH DEAD ENDS
The central door may be omitted if maximum travel distance is not more than 15m.
1. The arrangements shown also apply to the top storey.
2. For further guidance on the fire rating of the fire doorsets from the corridor to the flat and/or stairway refer to Appendix C ,Table C1.
Fire doorset provided in accordance with paragraphs 3.50 to 3.53(An external wall vent or smoke shaft located anywhere in the shaded area)
See paras 3.27 and 3.36
Gas service and installation pipes and meters should not be within a protected stairway, unless installed in accordance with the Pipelines Safety Regulations 1996 and the Gas Safety (Installation and Use) Regulations 1998.
In a converted building with a maximum of three storeys, a minimum REI 30 fire resistance could be accepted for elements of structure if the means of escape conform to the provisions of Section 3.
fire safety - volume 2: buildings other than dwellings. 2019 edition - for use in england
Means of warning and escape
B1.The building shall be designed and constructed so that there are appropriate provisions for the early warning of fire, and appropriate means of escape in case of fire from the building to a place of safety outside the building capable of being safely and effectively used at all material times.
Requirement B1 does not apply to any prison provided under section 33 of the Prison Act 1952
(a) (power to provide prisons, etc.).
(a) 1952 c. 52; section 33 was amended by section 100 of the Criminal Justice and Public Order Act 1994 (c. 33) and by S.I. 1963/597.
In the Secretary of State’s view, requirement B1 is met by achieving all of the following.
a. There are sufficient means for giving early warning of fire to people in the building.
b. All people can escape to a place of safety without external assistance.
c. Escape routes are suitably located, sufficient in number and of adequate capacity.
d. Where necessary, escape routes are sufficiently protected from the effects of fire and smoke.
e. Escape routes are adequately lit and exits are suitably signed.
f. There are appropriate provisions to limit the ingress of smoke to the escape routes, or to
restrict the spread of fire and remove smoke.
g. For buildings containing flats, there are appropriate provisions to support a stay put evacuation
strategy.
The extent to which any of these measures are necessary is dependent on the use of the building,
its size and its height.
Building work and material changes of use subject to requirement B1 include both new and existing
buildings.
All dwellings should have a fire detection and alarm system, minimum Grade D2 Category LD3
standard, in accordance with the relevant recommendations of BS 5839-6.
A higher standard of protection should be considered where occupants of a proposed dwelling
would be at special risk from fire. Further advice on this is also given in BS 5839-6.
Each flat in a block should have alarms as set out in paragraphs 1.1 to 1.4. With effective compartmentation, a communal fire alarm system is not normally needed. In some buildings, detectors in common parts of the building may need to operate smoke control or other fire protection systems but do not usually sound an audible warning.
The fire detection and alarm systems in flats should connect to a central monitoring point or alarm
receiving centre. The systems should alert the warden or supervisor and identify the individual flat
where a fire has been detected.
These provisions do not apply to the following.
a. The common parts of a sheltered housing development, such as communal lounges.
b. Sheltered accommodation in the 'residential (institutional)' or 'residential (other)' purpose groups (purpose group 2(a) or 2(b)).
In these parts, means of warning should follow the guidance for buildings other than dwellings in Volume 2 of Approved Document B.
Fire detection and alarm systems must be properly designed, installed and maintained. A design,
installation and commissioning certificate should be provided for fire detection and alarm systems.
Third party certification schemes for fire protection products and related services are an effective
means of providing assurances of quality, reliability and safety.
Smoke and heat alarms should have a standby power supply, such as a battery (rechargeable
or non-rechargeable) or capacitor. More information on power supplies is given in clause 15 of
BS 5839-6.
NOTE: The term ‘fire alarm system’ describes the combination of components for giving an audible
and/or other perceptible warning of fire.
NOTE: In this document, the term ‘fire detection system’ describes any type of automatic sensor
network and associated control and indicating equipment. Sensors may be sensitive to smoke,
heat, gaseous combustion products or radiation. Automatic sprinkler systems can also be used to
operate a fire alarm system.
The provisions in this section make the following assumptions.
a. Any fire is likely to be in a flat.
b. There is no reliance on external rescue.
c. Simultaneous evacuation of all flats is unlikely to be necessary due to compartmentation.
d. Fires in common parts of the building should not spread beyond the fabric in the immediate vicinity. In some cases, however, communal facilities exist that require additional measures to be taken.
The following paragraphs deal with means of escape from the entrance doors of flats to a final exit. They do not apply to flats with a top storey that is a maximum of 4.5m above ground level (designed in accordance with paragraphs 3.16 and 3.17).
Reference should also be made to the following.
a. Requirement B3 regarding compartment walls and protected shafts.
b. Requirement B5 regarding access for the fire and rescue service.
For some low rise buildings, the provisions in paragraphs 3.26 and 3.27 may be modified and the use of a single stair, protected in accordance with Diagram 3.9, may be permitted where all of the following apply.
a. The top storey of the building is a maximum of 11m above ground level.
b. No more than three storeys are above the ground storey.
c. The stair does not connect to a covered car park, unless the car park is open sided (as defined in Section 11 of Approved Document B Volume 2).
d. The stair does not serve offices, stores or other ancillary accommodation. If it does, they should be separated from the stair by a protected lobby or protected corridor (minimum REI 30) with a minimum 0.4m2 of permanent ventilation, or be protected from the ingress of smoke by a mechanical smoke control system.
NOTE: For refuse chutes and storage see paragraphs 3.55 to 3.58.
e. Either of the following is provided for the fire and rescue service.
i. A high-level openable vent with a free area of at least 1m2 at each storey.
ii. A single openable vent with a free area of at least 1m2 at the head of the stair, operable remotely at the fire and rescue service access level.
Provisions are recommended to support a stay put evacuation strategy for blocks of flats. It is based on the principle that a fire is contained in the flat of origin and common escape routes are maintained relatively free from smoke and heat. It allows occupants, some of whom may require assistance to escape in the event of a fire, in other flats that are not affected to remain.
Sufficient protection to common means of escape is necessary to allow occupants to escape should they choose to do so or are instructed/aided to by the fire service. A higher standard of protection is therefore needed to ensure common escape routes remain available for a longer period than is provided in other buildings.
A fire doorset (minimum E 30 Sa) fitted with a self-closing device (and fire resisting screen, where required) should separate the dead-end portion of a common corridor from the rest of the corridor (Diagrams 3.7a, 3.8b and 3.8c).
Paragraphs 3.6 to 3.23 deal with the means of escape within each flat. Paragraphs 3.25 to 3.89 deal with the means of escape in common areas of the building (including mixed use buildings in paragraphs 3.76 and 3.77). Guidance for live/work units is given in paragraph 3.24.
Every doorway or other exit providing access to a means of escape, other than exits in ordinary use (e.g. main entrances), should be distinctively and conspicuously marked by an exit sign in accordance with BS ISO 3864-1 and BS 5499-4. For this reason, blocks of flats with a single stair in regular use would not usually require any fire exit signage.
Advice on fire safety signs, including emergency escape signs, is given in the HSE publication Safety Signs and Signals: Guidance on Regulations.
Some buildings may require additional signs to comply with other legislation.
Guidance on cables for large and complex buildings is given in BS 5839-1, BS 5266-1 and BS 8519.
See paras 3.27 and 3.36
NOTES:
1. The arrangements shown also apply to the top storey.
2. See Diagram 3.9 for small single stair buildings.
3. All doors shown are fire doorsets.
4. Where travel distance is measured to a stair lobby, the lobby must not provide direct access to any storage room, flat or other space containing a potential fire hazard.
5. For further guidance on the fire rating of the fire doorsets from the corridor to the flat and/or stairway refer to Appendix C ,Table C1.
F Flat
Shaded areas indicate zones where ventilation should be provided in accordance with paragraphs 3.50 to 3.53(An external wall vent or smoke shaft located anywhere in the shaded area)
In buildings with more than three storeys above the ground storey, stairs may serve the flats and other occupancies if all of the following apply.
a. The flat is ancillary to the main use of the building.
b. The flat has an independent alternative escape route.
c. The stair is separated from occupancies on lower storeys by a protected lobby (minimum REI 30) at each of those storeys.
d. The stair enclosure has at least the same standard of fire resistance as the structural elements of the building (see Appendix B, Table B4); if the stair is a firefighting stair, it should comply with the provisions in Section 15 (see also paragraph 3.60).
e. Any automatic fire detection and alarm system fitted in the main part of the building also covers all flats.
f. Any security measures in any parts of the building do not prevent escape at all material times.
a. CORRIDOR ACCESS WITHOUT DEAD ENDS
b. CORRIDOR ACCESS WITH DEAD ENDS
The central door may be omitted if maximum travel distance is not more than 15m.
1. The arrangements shown also apply to the top storey.
2. For further guidance on the fire rating of the fire doorsets from the corridor to the flat and/or stairway refer to Appendix C ,Table C1.
Fire doorset provided in accordance with paragraphs 3.50 to 3.53(An external wall vent or smoke shaft located anywhere in the shaded area)
See paras 3.27 and 3.36
Gas service and installation pipes and meters should not be within a protected stairway, unless installed in accordance with the Pipelines Safety Regulations 1996 and the Gas Safety (Installation and Use) Regulations 1998.
In a converted building with a maximum of three storeys, a minimum REI 30 fire resistance could be accepted for elements of structure if the means of escape conform to the provisions of Section 3.
fire-separating element
All dwellings should have a fire detection and alarm system, minimum Grade D2 Category LD3
standard, in accordance with the relevant recommendations of BS 5839-6.
A higher standard of protection should be considered where occupants of a proposed dwelling
would be at special risk from fire. Further advice on this is also given in BS 5839-6.
If windows are replaced, it may be necessary to provide cavity barriers around the opening in accordance with Section 5.
See para 2.5
Alternative cavity barrier arrangements in roof space over protected stairway in a house with a storey more than 4.5m above ground level
See Diagram 2.1c. The dwellinghouse should have either of the following. Cavity barriers or a fire resisting ceiling (minimum EI 30) should be provided above a protected stairway enclosure (Diagram 2.3). b. Alternative escape route – a top storey separated from lower storeys by fire resisting construction (minimum REI 30) and with an alternative escape route leading to its own final exit.
a. Protected stairway – a stair separated by fire resisting construction (minimum REI 30) at all storeys, that complies with one of the following.
i. Extends to a final exit (Diagram 2.2a).
ii. Gives access to a minimum of two ground level final exits that are separated from each other by fire resisting construction (minimum REI 30) and fire doorsets (minimum E 20) (Diagram 2.2b).
Where a storey or part of a building has multiple escape routes available, one may be over a flat roof that complies with all of the following.
a. It should be part of the same building from which escape is being made.
b. The route across the roof should lead to a storey exit or external escape route.
c. The part of the roof (including its supporting structure) forming the escape route, and any opening within 3m of the escape route, should be of fire resisting construction (minimum REI 30).
d. The route should be clearly defined and guarded by walls and/or protective barriers to protect against falling.
Where a storey or part of a building has multiple escape routes available, one may be over a flat roof that complies with all of the following.
d. The route should be clearly defined and guarded by walls and/or protective barriers to protect against falling.
To limit potential damage to cables in protected circuits, all of the following should apply.
a. Cables should be sufficiently robust.
b. Cable routes should be carefully selected and/or physically protected in areas where cables may be exposed to damage.
c. Methods of cable support should be class A1 rated and offer at least the same integrity as the cable. They should maintain circuit integrity and hold cables in place when exposed to fire.
Where a stair serves an enclosed car park or place of special fire hazard, the lobby or corridor should have a minimum 0.4m2 of permanent ventilation or be protected from the ingress of smoke by a mechanical smoke control system.
NOTE: For refuse chutes and storage see paragraphs 3.55 to 3.58.
In single stair buildings, electricity meters should be in securely locked cupboards. Cupboards should be separated from the escape route by fire resisting construction.
If a loadbearing wall is any of the following, guidance in other sections may also apply.
a. A compartment wall (including a wall common to two buildings): Section 7.
b. Enclosing a place of special fire hazard: Section 7.
c. Protecting a means of escape: Sections 2 and 3.
d. An external wall: Sections 10 and 11.
e. Enclosing a firefighting shaft: Section 15.
fire-stop (Fire-stopping)
Fire detection and alarm systems must be properly designed, installed and maintained. A design,
installation and commissioning certificate should be provided for fire detection and alarm systems.
Third party certification schemes for fire protection products and related services are an effective
means of providing assurances of quality, reliability and safety.
Smoke and heat alarms should have a standby power supply, such as a battery (rechargeable
or non-rechargeable) or capacitor. More information on power supplies is given in clause 15 of
BS 5839-6.
NOTE: The term ‘fire alarm system’ describes the combination of components for giving an audible
and/or other perceptible warning of fire.
NOTE: In this document, the term ‘fire detection system’ describes any type of automatic sensor
network and associated control and indicating equipment. Sensors may be sensitive to smoke,
heat, gaseous combustion products or radiation. Automatic sprinkler systems can also be used to
operate a fire alarm system.
Where a stair serves an enclosed car park or place of special fire hazard, the lobby or corridor should have a minimum 0.4m2 of permanent ventilation or be protected from the ingress of smoke by a mechanical smoke control system.
NOTE: For refuse chutes and storage see paragraphs 3.55 to 3.58.
firefighting lift
A passenger lift serving any storey more than 4.5m above ground level should be in either of the following.
a. The enclosure to the protected stairway, as described in paragraph 2.5.
b. A fire resisting lift shaft (minimum REI 30).
A passenger lift serving any storey more than 4.5m above ground level should be in either of the following.
a. The enclosure to the protected stairway, as described in paragraph 2.5.
b. A fire resisting lift shaft (minimum REI 30).
The following paragraphs deal with means of escape from the entrance doors of flats to a final exit. They do not apply to flats with a top storey that is a maximum of 4.5m above ground level (designed in accordance with paragraphs 3.16 and 3.17).
Reference should also be made to the following.
a. Requirement B3 regarding compartment walls and protected shafts.
b. Requirement B5 regarding access for the fire and rescue service.
The following paragraphs deal with means of escape from the entrance doors of flats to a final exit. They do not apply to flats with a top storey that is a maximum of 4.5m above ground level (designed in accordance with paragraphs 3.16 and 3.17).
Reference should also be made to the following.
a. Requirement B3 regarding compartment walls and protected shafts.
b. Requirement B5 regarding access for the fire and rescue service.
For some low rise buildings, the provisions in paragraphs 3.26 and 3.27 may be modified and the use of a single stair, protected in accordance with Diagram 3.9, may be permitted where all of the following apply.
a. The top storey of the building is a maximum of 11m above ground level.
b. No more than three storeys are above the ground storey.
c. The stair does not connect to a covered car park, unless the car park is open sided (as defined in Section 11 of Approved Document B Volume 2).
d. The stair does not serve offices, stores or other ancillary accommodation. If it does, they should be separated from the stair by a protected lobby or protected corridor (minimum REI 30) with a minimum 0.4m2 of permanent ventilation, or be protected from the ingress of smoke by a mechanical smoke control system.
NOTE: For refuse chutes and storage see paragraphs 3.55 to 3.58.
e. Either of the following is provided for the fire and rescue service.
i. A high-level openable vent with a free area of at least 1m2 at each storey.
ii. A single openable vent with a free area of at least 1m2 at the head of the stair, operable remotely at the fire and rescue service access level.
For some low rise buildings, the provisions in paragraphs 3.26 and 3.27 may be modified and the use of a single stair, protected in accordance with Diagram 3.9, may be permitted where all of the following apply.
a. The top storey of the building is a maximum of 11m above ground level.
b. No more than three storeys are above the ground storey.
c. The stair does not connect to a covered car park, unless the car park is open sided (as defined in Section 11 of Approved Document B Volume 2).
d. The stair does not serve offices, stores or other ancillary accommodation. If it does, they should be separated from the stair by a protected lobby or protected corridor (minimum REI 30) with a minimum 0.4m2 of permanent ventilation, or be protected from the ingress of smoke by a mechanical smoke control system.
NOTE: For refuse chutes and storage see paragraphs 3.55 to 3.58.
e. Either of the following is provided for the fire and rescue service.
i. A high-level openable vent with a free area of at least 1m2 at each storey.
ii. A single openable vent with a free area of at least 1m2 at the head of the stair, operable remotely at the fire and rescue service access level.
Section 7 provides guidance on avoiding the spread of fire between storeys. For a stair that is also a firefighting stair, guidance in Section 15 should be followed.
Section 7 provides guidance on avoiding the spread of fire between storeys. For a stair that is also a firefighting stair, guidance in Section 15 should be followed.
A protected stairway should not be used for anything else, except a lift well or electricity meters.
A protected stairway should not be used for anything else, except a lift well or electricity meters.
If a loadbearing wall is any of the following, guidance in other sections may also apply.
a. A compartment wall (including a wall common to two buildings): Section 7.
b. Enclosing a place of special fire hazard: Section 7.
c. Protecting a means of escape: Sections 2 and 3.
d. An external wall: Sections 10 and 11.
e. Enclosing a firefighting shaft: Section 15.
If a loadbearing wall is any of the following, guidance in other sections may also apply.
a. A compartment wall (including a wall common to two buildings): Section 7.
b. Enclosing a place of special fire hazard: Section 7.
c. Protecting a means of escape: Sections 2 and 3.
d. An external wall: Sections 10 and 11.
e. Enclosing a firefighting shaft: Section 15.
firefighting lobby
NOTES:
1. If travel distance is measured to a stair lobby, the lobby must not provide direct access to any storage room, flat or other space containing a fire hazard.
2. In the case of a small single stair building in accordance with Diagram 3.9, this is reduced to 4.5m.
3. Does not apply if all flats on a storey have independent alternative means of escape.
4. Sheltered housing may require reduced maximum travel distances.
An escape route should not pass through one stair enclosure to reach another. It may pass through a protected lobby (minimum REI 30) of one stair to reach another.
Ancillary accommodation should not be located in, or entered from, a protected lobby or protected corridor forming the only common escape route on that storey.
Despite the provisions described, it is probable that some smoke will get into the common corridor or lobby from a fire in a flat.
There should therefore be some means of ventilating the common corridors/lobbies to control smoke and so protect the common stairs. This means of ventilation offers additional protection to that provided by the fire doors to the stair, as well as some protection to the corridors/lobbies.
Ventilation can be natural (paragraphs 3.50 to 3.53) or mechanical (paragraph 3.54).
Section 7 provides guidance on avoiding the spread of fire between storeys. For a stair that is also a firefighting stair, guidance in Section 15 should be followed.
Where a common stair is not part of the only escape route from a flat, it may also serve ancillary accommodation from which it is separated by a protected lobby or protected corridor (minimum REI 30).
Where a stair serves an enclosed car park or place of special fire hazard, the lobby or corridor should have a minimum 0.4m2 of permanent ventilation or be protected from the ingress of smoke by a mechanical smoke control system.
NOTE: For refuse chutes and storage see paragraphs 3.55 to 3.58.
In buildings with a maximum of three storeys above the ground storey, stairs may serve both flats and other occupancies, provided that the stairs are separated from each occupancy by protected lobbies (minimum REI 30) at each storey.
a. SMALL SINGLE STAIR BUILDING
*If smoke control is provided in the lobby, the travel distance can be increased to 7.5m maximum(see Diagram 3.7, example b).
b. SMALL SINGLE STAIR BUILDING WITH NO MORE THAN TWO FLATS PER STOREY
The door between stair and lobby should be free from security fastenings.
If the flats have protected entrance halls, the lobby between the common stair and flat entrance is not essential.
NOTES:
1. The arrangements shown also apply to the top storey.
2. If the travel distance across the lobby in diagram (a) exceeds 4.5m, Diagram 3.7 applies.
3. Where,in Diagram (b), the lobby between the common stair and the dwelling is omitted in smal lsingle stair buildings, an automatic opening vent with a free area of at least 1m2 is required at the top of the stair,which is operated automatically on detection of smoke at any storey in the stair.
4. For further guidance on the fire rating of the fire doorsets from the corridor to the flat and/or stairway refer to Appendix C, Table C1.
Fire resisting construction
Openable vent at high level for fire service use (1.0m2 minimum free area); see paragraph 3.28eSee para 3.28
Diagram 3.9
firefighting shaft
Section 7 provides guidance on avoiding the spread of fire between storeys. For a stair that is also a firefighting stair, guidance in Section 15 should be followed.
firefighting stair
See Diagram 2.1b. Where served by only one stair, all habitable rooms (excluding kitchens) should have either of the following.
a. An emergency escape window or external door, as described in paragraph 2.10.
b. Direct access to a protected stairway, as described in paragraph 2.5a.
See para 2.5
Alternative cavity barrier arrangements in roof space over protected stairway in a house with a storey more than 4.5m above ground level
An escape route should not pass through one stair enclosure to reach another. It may pass through a protected lobby (minimum REI 30) of one stair to reach another.
Ancillary accommodation should not be located in, or entered from, a protected lobby or protected corridor forming the only common escape route on that storey.
Despite the provisions described, it is probable that some smoke will get into the common corridor or lobby from a fire in a flat.
There should therefore be some means of ventilating the common corridors/lobbies to control smoke and so protect the common stairs. This means of ventilation offers additional protection to that provided by the fire doors to the stair, as well as some protection to the corridors/lobbies.
Ventilation can be natural (paragraphs 3.50 to 3.53) or mechanical (paragraph 3.54).
Refuse chutes and rooms for storing refuse should meet both of the following conditions.
a. Be separated from other parts of the building by fire resisting construction (minimum REI 30 in buildings with a top storey up to 5m above ground level; otherwise REI 60).
b. Not be situated within a protected stairway or protected lobby.
Section 7 provides guidance on avoiding the spread of fire between storeys. For a stair that is also a firefighting stair, guidance in Section 15 should be followed.
Every common stair should be a protected stairway, within a fire resisting enclosure (minimum REI 30).
Where multiple escape stairs serve the upper storeys, only one needs to end at ground level. Other stairs may connect with the basement storeys if there is a protected lobby or a protected corridor between the stairs and accommodation at each basement level.
Where a common stair is not part of the only escape route from a flat, it may also serve ancillary accommodation from which it is separated by a protected lobby or protected corridor (minimum REI 30).
A protected stairway should not be used for anything else, except a lift well or electricity meters.
Every protected stairway should lead to a final exit, either directly or via a protected exit passageway. Any protected exit corridor or stair should have the same standard of fire resistance and lobby protection as the stair it serves.
a. SMALL SINGLE STAIR BUILDING
*If smoke control is provided in the lobby, the travel distance can be increased to 7.5m maximum(see Diagram 3.7, example b).
b. SMALL SINGLE STAIR BUILDING WITH NO MORE THAN TWO FLATS PER STOREY
The door between stair and lobby should be free from security fastenings.
If the flats have protected entrance halls, the lobby between the common stair and flat entrance is not essential.
NOTES:
1. The arrangements shown also apply to the top storey.
2. If the travel distance across the lobby in diagram (a) exceeds 4.5m, Diagram 3.7 applies.
3. Where,in Diagram (b), the lobby between the common stair and the dwelling is omitted in smal lsingle stair buildings, an automatic opening vent with a free area of at least 1m2 is required at the top of the stair,which is operated automatically on detection of smoke at any storey in the stair.
4. For further guidance on the fire rating of the fire doorsets from the corridor to the flat and/or stairway refer to Appendix C, Table C1.
Fire resisting construction
Openable vent at high level for fire service use (1.0m2 minimum free area); see paragraph 3.28eSee para 3.28
Diagram 3.9
fireplace recess
Windows or external doors providing emergency escape should comply with all of the following.
a. Windows should have an unobstructed openable area that complies with all of the following.
i. A minimum area of 0.33m2.
ii. A minimum height of 450mm and a minimum width of 450mm (the route through the window may be at an angle rather than straight through).
iii. The bottom of the openable area is a maximum of 1100mm above the floor.
b. People escaping should be able to reach a place free from danger from fire. Courtyards or inaccessible back gardens should comply with Diagram 2.5.
c. Locks (with or without removable keys) and opening stays (with child-resistant release catches) may be fitted to escape windows.
d. Windows should be capable of remaining open without being held.
If windows are replaced, it may be necessary to provide cavity barriers around the opening in accordance with Section 5.
Windows or external doors providing emergency escape should comply with all of the following.
a. Windows should have an unobstructed openable area that complies with all of the following.
i. A minimum area of 0.33m2.
ii. A minimum height of 450mm and a minimum width of 450mm (the route through the window may be at an angle rather than straight through).
iii. The bottom of the openable area is a maximum of 1100mm above the floor.
b. People escaping should be able to reach a place free from danger from fire.
c. Locks (with or without removable keys) and opening stays (with child-resistant release catches) may be fitted to escape windows.
d. Windows should be capable of remaining open without being held.
fit-out work
Each flat in a block should have alarms as set out in paragraphs 1.1 to 1.4. With effective compartmentation, a communal fire alarm system is not normally needed. In some buildings, detectors in common parts of the building may need to operate smoke control or other fire protection systems but do not usually sound an audible warning.
flat
In student residences that are designed and occupied as a block of flats, separate automatic detection should be provided in each self-contained flat where all of the following apply.
a. A group of up to six students shares the flat.
b. Each flat has its own entrance door.
c. The compartmentation principles for flats in Section 7 have been followed.
Where a total evacuation strategy is adopted, the alarm system should follow the guidance for buildings other than dwellings in Volume 2 of Approved Document B.
These provisions do not apply to the following.
a. The common parts of a sheltered housing development, such as communal lounges.
b. Sheltered accommodation in the 'residential (institutional)' or 'residential (other)' purpose groups (purpose group 2(a) or 2(b)).
In these parts, means of warning should follow the guidance for buildings other than dwellings in Volume 2 of Approved Document B.
A balcony or flat roof intended to form part of an escape route should be provided with guarding etc. in accordance with Approved Document K.
A balcony or flat roof intended to form part of an escape route should be provided with guarding etc. in accordance with Approved Document K.
In mixed use buildings, separate means of escape should be provided from any storeys or parts of storeys used for the ‘residential’ or ‘assembly and recreation’ purpose groups (purpose groups 1, 2 and 5), other than in the case of certain small buildings or buildings in which the residential accommodation is ancillary (see paragraphs 3.76 and 3.77)
Flats may be served by an external stair if the provisions in paragraphs 3.66 to 3.69 are followed.
flight
A stair of acceptable width for everyday use will be sufficient for escape purposes. If it is also a firefighting stair, it should be at least 1100mm wide. The width is the clear width between the walls or balustrades. Any handrails and strings intruding into that width by a maximum of 100mm on each side may be ignored.
floor
Escape route floor finishes should minimise their slipperiness when wet. Finishes include the treads of steps and surfaces of ramps and landings.
flue outlet
A vent to the outside with a minimum free area of 1m2 should be provided from the top storey of the stair.
flueblock chimney
Fire detection and alarm systems sometimes trigger other systems. The interface between systems
must be reliable. Particular care should be taken if the interface is facilitated via another system.
Where any part of BS 7273 applies to the triggering of other systems, the recommendations of that
part of BS 7273 should be followed.
Guidance on the design of smoke control systems that use pressure differentials is available in BS EN 12101-6.
flueless appliance
A room accessed only via an inner room (an inner inner room) is acceptable when all of the following apply.
a. It complies with paragraph 2.11.
b. The access rooms each have a smoke alarm (see Section 1).
c. None of the access rooms is a kitchen.
Two rooms may be served by a single window. A door between the rooms should provide access to the window without passing through the stair enclosure. Both rooms should have their own access to the internal stair.
The approach to rooms containing refuse chutes or for storing refuse should comply with one of the following conditions.
a. Be directly from the open air.
b. Be through a protected lobby with a minimum of 0.2m2 of permanent ventilation.
A room accessed only via an inner room (an inner inner room) is acceptable when all of the following apply.
a. It complies with paragraph 3.7.
b. The access rooms each have a smoke alarm (see Section 1).
c. None of the access rooms is a kitchen.
following edge (of door)
See Diagram 2.1a. All habitable rooms (excluding kitchens) should have either of the following.
a. An opening directly onto a hall leading to a final exit.
b. An emergency escape window or door, as described in paragraph 2.10.
Where a new storey is added through conversion to create a storey above 4.5m, both of the following should apply.
a. The full extent of the escape route should be addressed.
b. Fire resisting doors (minimum E 20) and partitions (minimum REI 30) should be provided, including upgrading the existing doors where necessary.
NOTE: Where the layout is open plan, new partitions should be provided to enclose the escape route (Diagram 2.2).
Where it is undesirable to replace existing doors because of historical or architectural merit, the possibility of retaining, and where necessary upgrading, them should be investigated.
An alternative approach to that described in paragraph 2.21 would be to comply with all of the following.
a. Provide sprinkler protection to the open-plan areas.
b. Provide a fire resisting partition (minimum REI 30) and door (minimum E 20) to separate the ground storey from the upper storeys. The door should allow occupants of the loft room access to a first storey escape window.
c. Separate cooking facilities from the open-plan area with fire resisting construction (minimum REI 30).
All habitable rooms (excluding kitchens) should have either of the following.
a. An opening directly onto a hall leading to a final exit.
b. An emergency escape window or door, as described in paragraph 3.6.
All habitable rooms (excluding kitchens) should have either of the following.
a. An emergency escape window or external door, as described in paragraph 3.6.
b. In multi-storey flats, direct access to a protected internal stairway (minimum REI 30) leading to an exit from the flat.
One of the following approaches should be adopted, observing the inner room restrictions described in paragraphs 3.7 and 3.8.
a. Provide a protected entrance hall (minimum REI 30) serving all habitable rooms that meets the conditions shown in Diagram 3.2.
b. Plan the flat to meet the conditions shown in Diagram 3.3, so that both of the following apply.
i. The travel distance from the flat entrance door to any point in any habitable room is a maximum of 9m.
ii. Cooking facilities are remote from the main entrance door and do not impede the escape route from anywhere in the flat.
c. Provide an alternative exit from the flat complying with paragraph 3.22.
The following paragraphs deal with means of escape from the entrance doors of flats to a final exit.
Except in buildings that comply with Diagram 3.9, the corridor or lobby next to each stair should have a smoke vent. The location of the vent should comply with both of the following.
a. Be as high as practicable.
b. Be positioned so the top edge is at least as high as the top of the door to the stair.
The approach to rooms containing refuse chutes or for storing refuse should comply with one of the following conditions.
a. Be directly from the open air.
b. Be through a protected lobby with a minimum of 0.2m2 of permanent ventilation.
free area
Windows or external doors providing emergency escape should comply with all of the following.
a. Windows should have an unobstructed openable area that complies with all of the following.
i. A minimum area of 0.33m2.
ii. A minimum height of 450mm and a minimum width of 450mm (the route through the window may be at an angle rather than straight through).
iii. The bottom of the openable area is a maximum of 1100mm above the floor.
b. People escaping should be able to reach a place free from danger from fire. Courtyards or inaccessible back gardens should comply with Diagram 2.5.
c. Locks (with or without removable keys) and opening stays (with child-resistant release catches) may be fitted to escape windows.
d. Windows should be capable of remaining open without being held.
A vent to the outside with a minimum free area of 1m2 should be provided from the top storey of the stair.
Access openings to refuse storage chambers should not be sited in the following areas.
a. Next to escape routes or final exits.
b. Near the windows of flats.
Windows or external doors providing emergency escape should comply with all of the following.
a. Windows should have an unobstructed openable area that complies with all of the following.
i. A minimum area of 0.33m2.
ii. A minimum height of 450mm and a minimum width of 450mm (the route through the window may be at an angle rather than straight through).
iii. The bottom of the openable area is a maximum of 1100mm above the floor.
b. People escaping should be able to reach a place free from danger from fire.
c. Locks (with or without removable keys) and opening stays (with child-resistant release catches) may be fitted to escape windows.
d. Windows should be capable of remaining open without being held.
gallery
NOTES:
1. This diagram does not apply where the gallery is provided with one of the following:
i. An alternative escape route
ii. An emergency escape window (where the gallery floor is not more than 4.5m above ground level).
2. Any cooking facilities within a room containing a gallery should comply with one of the following conditions:
i. Be enclosed with fire resisting construction
ii. Be remote from the stair to the gallery and positioned such that they do not prejudice escape from the gallery.
See para 2.15
NOTES:
1. This diagram does not apply where the gallery is provided with one of the following:
i. An alternative escape route
ii. An emergency escape window (where the gallery floor is not more than 4.5m above ground level).
2. Any cooking facilities within a room containing a gallery should comply with one of the following conditions:
i. Be enclosed with fire resisting construction
ii. Be remote from the stair to the gallery and positioned such that they do not prejudice escape from the gallery.
See para 3.13
For flats more than 4.5m above ground level, a balcony outside an alternative exit should be a common balcony meeting the conditions described in paragraph 3.22.
general access stair
Where a storey (or part of a building) is served by a single access stair, that stair may be external provided both of the following conditions are met.
a. The stair serves a floor not more than 6m above the ground level.
b. The stair meets the provisions in paragraph 3.62.
Where a storey (or part of a building) is served by a single access stair, that stair may be external provided both of the following conditions are met.
a. The stair serves a floor not more than 6m above the ground level.
b. The stair meets the provisions in paragraph 3.62.
going
Smoke alarms should be provided in the circulation spaces of the dwelling in accordance with
paragraphs 1.1 to 1.4.
NOTE: This does not apply where inner rooms are provided (see paragraph 2.11 for inner room
requirements).
See paras 2.1 to 2.6
Single storey dwellinghouse(see paragraph 2.1)
Dwellinghouse with one storey more than 4.5m above ground level(see paragraph 2.5)
Dwellinghouse with two or more storeys more than 4.5m above ground level(see paragraph 2.6)
Paragraph 3.27 may be modified using the guidance in clause 7.3 of BS 9991.
Escape route floor finishes should minimise their slipperiness when wet. Finishes include the treads of steps and surfaces of ramps and landings.
Paragraphs 3.6 to 3.23 deal with the means of escape within each flat. Paragraphs 3.25 to 3.89 deal with the means of escape in common areas of the building (including mixed use buildings in paragraphs 3.76 and 3.77). Guidance for live/work units is given in paragraph 3.24.
Flats may be served by an external stair if the provisions in paragraphs 3.66 to 3.69 are followed.
habitable room
Where new habitable rooms are provided, a fire detection and alarm system should be installed
where either of the following applies.
a. The room is provided above or below the ground storey.
b. The room is provided at the ground storey, without a final exit.
Where new habitable rooms are provided, a fire detection and alarm system should be installed
where either of the following applies.
a. The room is provided above or below the ground storey.
b. The room is provided at the ground storey, without a final exit.
Smoke alarms should be provided in the circulation spaces of the dwelling in accordance with
paragraphs 1.1 to 1.4.
NOTE: This does not apply where inner rooms are provided (see paragraph 2.11 for inner room
requirements).
See Diagram 2.1a. All habitable rooms (excluding kitchens) should have either of the following.
a. An opening directly onto a hall leading to a final exit.
b. An emergency escape window or door, as described in paragraph 2.10.
See Diagram 2.1a. All habitable rooms (excluding kitchens) should have either of the following.
a. An opening directly onto a hall leading to a final exit.
b. An emergency escape window or door, as described in paragraph 2.10.
An inner room is permitted when it is one of the following.
a. A kitchen.
b. A laundry or utility room.
c. A dressing room.
d. A bathroom, WC or shower room.
e. Any room on a storey that is a maximum of 4.5m above ground level which is provided with an emergency escape window as described in paragraph 2.10.
f. A gallery that complies with paragraph 2.15.
An inner room is permitted when it is one of the following.
a. A kitchen.
b. A laundry or utility room.
c. A dressing room.
d. A bathroom, WC or shower room.
e. Any room on a storey that is a maximum of 4.5m above ground level which is provided with an emergency escape window as described in paragraph 2.10.
f. A gallery that complies with paragraph 2.15.
A room accessed only via an inner room (an inner inner room) is acceptable when all of the following apply.
a. It complies with paragraph 2.11.
b. The access rooms each have a smoke alarm (see Section 1).
c. None of the access rooms is a kitchen.
A room accessed only via an inner room (an inner inner room) is acceptable when all of the following apply.
a. It complies with paragraph 2.11.
b. The access rooms each have a smoke alarm (see Section 1).
c. None of the access rooms is a kitchen.
See Diagram 2.1b. Where served by only one stair, all habitable rooms (excluding kitchens) should have either of the following.
a. An emergency escape window or external door, as described in paragraph 2.10.
b. Direct access to a protected stairway, as described in paragraph 2.5a.
Two rooms may be served by a single window. A door between the rooms should provide access to the window without passing through the stair enclosure. Both rooms should have their own access to the internal stair.
All habitable rooms (excluding kitchens) should have either of the following.
a. An opening directly onto a hall leading to a final exit.
b. An emergency escape window or door, as described in paragraph 3.6.
All habitable rooms (excluding kitchens) should have either of the following.
a. An opening directly onto a hall leading to a final exit.
b. An emergency escape window or door, as described in paragraph 3.6.
Two rooms may be served by a single escape window. A door between rooms should provide access to the escape window without passing through the stair enclosure. Both rooms should have their own access to the internal stair.
See para 3.18
NOTE: Bathrooms do not need to have fire doorsets provided that the bathroom is separated by fire resisting construction from the adjacent rooms.
See para 3.18
NOTE: Bathrooms do not need to have fire doorsets provided that the bathroom is separated by fire resisting construction from the adjacent rooms.
In addition, escape lighting should be provided to all of the following.
a. Toilet accommodation with a minimum floor area of 8m2.
b. Electricity and generator rooms.
c. Switch room/battery room for emergency lighting system.
d. Emergency control rooms.
An inner room is permitted when it is one of the following.
a. A kitchen.
b. A laundry or utility room.
c. A dressing room.
d. A bathroom, WC or shower room.
e. Any room on a storey that is a maximum of 4.5m above ground level which is provided with an emergency escape window as described in paragraph 3.6.
f. A gallery that complies with paragraph 3.13.
An inner room is permitted when it is one of the following.
a. A kitchen.
b. A laundry or utility room.
c. A dressing room.
d. A bathroom, WC or shower room.
e. Any room on a storey that is a maximum of 4.5m above ground level which is provided with an emergency escape window as described in paragraph 3.6.
f. A gallery that complies with paragraph 3.13.
A room accessed only via an inner room (an inner inner room) is acceptable when all of the following apply.
a. It complies with paragraph 3.7.
b. The access rooms each have a smoke alarm (see Section 1).
c. None of the access rooms is a kitchen.
A room accessed only via an inner room (an inner inner room) is acceptable when all of the following apply.
a. It complies with paragraph 3.7.
b. The access rooms each have a smoke alarm (see Section 1).
c. None of the access rooms is a kitchen.
handrail
A stair of acceptable width for everyday use will be sufficient for escape purposes. If it is also a firefighting stair, it should be at least 1100mm wide. The width is the clear width between the walls or balustrades. Any handrails and strings intruding into that width by a maximum of 100mm on each side may be ignored.
health & safety strategy
Where it is undesirable to replace existing doors because of historical or architectural merit, the possibility of retaining, and where necessary upgrading, them should be investigated.
Refuse storage chambers, refuse chutes and refuse hoppers should be sited and constructed in accordance with BS 5906.
health and safety file
Gas service and installation pipes and meters should not be within a protected stairway, unless installed in accordance with the Pipelines Safety Regulations 1996 and the Gas Safety (Installation and Use) Regulations 1998.
height
A large dwellinghouse of three or more storeys (excluding basement storeys) should be fitted with
a Grade A Category LD2 fire detection and alarm system as described in BS 5839-6.
See paras 2.1 to 2.6
Single storey dwellinghouse(see paragraph 2.1)
Dwellinghouse with one storey more than 4.5m above ground level(see paragraph 2.5)
Dwellinghouse with two or more storeys more than 4.5m above ground level(see paragraph 2.6)
A gallery should comply with one of the following.
a. It should be provided with an alternative exit.
b. It should be provided with an emergency escape window, as described in paragraph 2.10, where the gallery floor is a maximum of 4.5m above ground level.
c. It should meet all the conditions shown in Diagram 2.6.
See para 2.6
Example of alternative exit in para 2.6(a) (see definition in Appendix A)
Where escape from a dwellinghouse is to an enclosed space with exit only possible through other buildings (e.g. a courtyard or back garden), the length of the space should exceed whichever is the greater of the following.
a. The height of the dwellinghouse above ground level (x).
b. Where a rear extension is provided, the height of the extension (y).
See para 2.10
See Diagram 2.1d. In addition to meeting the provisions in paragraph 2.5, the dwellinghouse should comply with either of the following.
a. Provide an alternative escape route from each storey more than 7.5m above ground level. At the first storey above 7.5m, the protected stairway should be separated from the lower storeys by fire resisting construction (minimum REI 30) if the alternative escape route is accessed via either of the following.
i. The protected stairway to an upper storey.
ii. A landing within the protected stairway enclosure to an alternative escape route on the same storey. The protected stairway at or about 7.5m above ground level should be separated from the lower storeys or levels by fire resisting construction (see Diagram 2.4).
b. Provide a sprinkler system throughout, designed and installed in accordance with BS 9251.
No fire resistance required for door
1100mm zone above top landing
1100mm zone above top landing
6m maximum height of stair
Fire resisting window (minimum RE30)
1800mm zone of fire resisting construction at side of stair
Fire doorset (minimum E30)
Ground level or a roof or podium served by an independent stairway
6m maximum height of stair without weather protection
9m zone of fire resisting construction below stair
Ground level or a roof or podium served by an independent stairway
See para 3.68
A gallery should comply with one of the following.
a. It should be provided with an alternative exit.
b. It should be provided with an emergency escape window, as described in paragraph 3.6, where the gallery floor is a maximum of 4.5m above ground level.
c. It should meet the conditions shown in Diagram 3.1.
A multi-storey flat with an independent external entrance at ground level is similar to a dwellinghouse and means of escape should be planned on the basis of Section 2, depending on the height of the top storey above ground level.
For some low rise buildings, the provisions in paragraphs 3.26 and 3.27 may be modified and the use of a single stair, protected in accordance with Diagram 3.9, may be permitted where all of the following apply.
a. The top storey of the building is a maximum of 11m above ground level.
b. No more than three storeys are above the ground storey.
c. The stair does not connect to a covered car park, unless the car park is open sided (as defined in Section 11 of Approved Document B Volume 2).
d. The stair does not serve offices, stores or other ancillary accommodation. If it does, they should be separated from the stair by a protected lobby or protected corridor (minimum REI 30) with a minimum 0.4m2 of permanent ventilation, or be protected from the ingress of smoke by a mechanical smoke control system.
NOTE: For refuse chutes and storage see paragraphs 3.55 to 3.58.
e. Either of the following is provided for the fire and rescue service.
i. A high-level openable vent with a free area of at least 1m2 at each storey.
ii. A single openable vent with a free area of at least 1m2 at the head of the stair, operable remotely at the fire and rescue service access level.
Common corridors should be protected corridors. The wall between each flat and the corridor should be a compartment wall (minimum REI 30 where the top storey is up to 5m above ground level, otherwise REI 60).
Refuse chutes and rooms for storing refuse should meet both of the following conditions.
a. Be separated from other parts of the building by fire resisting construction (minimum REI 30 in buildings with a top storey up to 5m above ground level; otherwise REI 60).
b. Not be situated within a protected stairway or protected lobby.
See paras 3.27 and 3.36
NOTES:
1. The arrangements shown also apply to the top storey.
2. See Diagram 3.9 for small single stair buildings.
3. All doors shown are fire doorsets.
4. Where travel distance is measured to a stair lobby, the lobby must not provide direct access to any storage room, flat or other space containing a potential fire hazard.
5. For further guidance on the fire rating of the fire doorsets from the corridor to the flat and/or stairway refer to Appendix C ,Table C1.
F Flat
Shaded areas indicate zones where ventilation should be provided in accordance with paragraphs 3.50 to 3.53(An external wall vent or smoke shaft located anywhere in the shaded area)
In buildings with a maximum of three storeys above the ground storey, stairs may serve both flats and other occupancies, provided that the stairs are separated from each occupancy by protected lobbies (minimum REI 30) at each storey.
helical stair
See Diagram 2.1b. Where served by only one stair, all habitable rooms (excluding kitchens) should have either of the following.
a. An emergency escape window or external door, as described in paragraph 2.10.
b. Direct access to a protected stairway, as described in paragraph 2.5a.
Dwellinghouses with one internal stair should comply with paragraphs 2.5 and 2.6. In dwellinghouses with more than one stair, the stairs should provide effective alternative means of escape. The stairs should be physically separated by either of the following.
a. Fire resisting construction (minimum REI 30).
b. More than one room.
A building should provide access to more than one common stair if it does not meet the criteria for a single common stair (see paragraph 3.26 and 3.27).
Flats may be served by an external stair if the provisions in paragraphs 3.66 to 3.69 are followed.
Where a storey (or part of a building) is served by a single access stair, that stair may be external provided both of the following conditions are met.
a. The stair serves a floor not more than 6m above the ground level.
b. The stair meets the provisions in paragraph 3.62.
high-usage entrance door
Smoke alarms should be mains operated and conform to BS EN 14604.
Heat alarms should be mains operated and conform to BS 5446-2.
Where a new storey is added through conversion to create a storey above 4.5m, both of the following should apply.
a. The full extent of the escape route should be addressed.
b. Fire resisting doors (minimum E 20) and partitions (minimum REI 30) should be provided, including upgrading the existing doors where necessary.
NOTE: Where the layout is open plan, new partitions should be provided to enclose the escape route (Diagram 2.2).
Where it is undesirable to replace existing doors because of historical or architectural merit, the possibility of retaining, and where necessary upgrading, them should be investigated.
One of the following approaches should be adopted, observing the inner room restrictions described in paragraphs 3.7 and 3.8.
a. Provide a protected entrance hall (minimum REI 30) serving all habitable rooms that meets the conditions shown in Diagram 3.2.
b. Plan the flat to meet the conditions shown in Diagram 3.3, so that both of the following apply.
i. The travel distance from the flat entrance door to any point in any habitable room is a maximum of 9m.
ii. Cooking facilities are remote from the main entrance door and do not impede the escape route from anywhere in the flat.
c. Provide an alternative exit from the flat complying with paragraph 3.22.
The following paragraphs deal with means of escape from the entrance doors of flats to a final exit. They do not apply to flats with a top storey that is a maximum of 4.5m above ground level (designed in accordance with paragraphs 3.16 and 3.17).
Reference should also be made to the following.
a. Requirement B3 regarding compartment walls and protected shafts.
b. Requirement B5 regarding access for the fire and rescue service.
The following paragraphs deal with means of escape from the entrance doors of flats to a final exit.
To limit potential damage to cables in protected circuits, all of the following should apply.
a. Cables should be sufficiently robust.
b. Cable routes should be carefully selected and/or physically protected in areas where cables may be exposed to damage.
c. Methods of cable support should be class A1 rated and offer at least the same integrity as the cable. They should maintain circuit integrity and hold cables in place when exposed to fire.
Except in buildings that comply with Diagram 3.9, the corridor or lobby next to each stair should have a smoke vent. The location of the vent should comply with both of the following.
a. Be as high as practicable.
b. Be positioned so the top edge is at least as high as the top of the door to the stair.
higher risk residential building (hrrb)
All dwellings should have a fire detection and alarm system, minimum Grade D2 Category LD3
standard, in accordance with the relevant recommendations of BS 5839-6.
A higher standard of protection should be considered where occupants of a proposed dwelling
would be at special risk from fire. Further advice on this is also given in BS 5839-6.
hot water storage system package
Fire detection and alarm systems sometimes trigger other systems. The interface between systems
must be reliable. Particular care should be taken if the interface is facilitated via another system.
Where any part of BS 7273 applies to the triggering of other systems, the recommendations of that
part of BS 7273 should be followed.
hot water storage system unit
Fire detection and alarm systems sometimes trigger other systems. The interface between systems
must be reliable. Particular care should be taken if the interface is facilitated via another system.
Where any part of BS 7273 applies to the triggering of other systems, the recommendations of that
part of BS 7273 should be followed.
Smoke and heat alarms should have a standby power supply, such as a battery (rechargeable
or non-rechargeable) or capacitor. More information on power supplies is given in clause 15 of
BS 5839-6.
NOTE: The term ‘fire alarm system’ describes the combination of components for giving an audible
and/or other perceptible warning of fire.
NOTE: In this document, the term ‘fire detection system’ describes any type of automatic sensor
network and associated control and indicating equipment. Sensors may be sensitive to smoke,
heat, gaseous combustion products or radiation. Automatic sprinkler systems can also be used to
operate a fire alarm system.
Refuse storage chambers, refuse chutes and refuse hoppers should be sited and constructed in accordance with BS 5906.
indirect heating
Heat alarms should be mains operated and conform to BS 5446-2.
installation instructions
Fire detection and alarm systems must be properly designed, installed and maintained. A design,
installation and commissioning certificate should be provided for fire detection and alarm systems.
Third party certification schemes for fire protection products and related services are an effective
means of providing assurances of quality, reliability and safety.
Gas service and installation pipes and meters should not be within a protected stairway, unless installed in accordance with the Pipelines Safety Regulations 1996 and the Gas Safety (Installation and Use) Regulations 1998.
intermediate landing
Escape route floor finishes should minimise their slipperiness when wet. Finishes include the treads of steps and surfaces of ramps and landings.
kitchen
An inner room is permitted when it is one of the following.
a. A kitchen.
b. A laundry or utility room.
c. A dressing room.
d. A bathroom, WC or shower room.
e. Any room on a storey that is a maximum of 4.5m above ground level which is provided with an emergency escape window as described in paragraph 2.10.
f. A gallery that complies with paragraph 2.15.
A room accessed only via an inner room (an inner inner room) is acceptable when all of the following apply.
a. It complies with paragraph 2.11.
b. The access rooms each have a smoke alarm (see Section 1).
c. None of the access rooms is a kitchen.
In addition, escape lighting should be provided to all of the following.
a. Toilet accommodation with a minimum floor area of 8m2.
b. Electricity and generator rooms.
c. Switch room/battery room for emergency lighting system.
d. Emergency control rooms.
An inner room is permitted when it is one of the following.
a. A kitchen.
b. A laundry or utility room.
c. A dressing room.
d. A bathroom, WC or shower room.
e. Any room on a storey that is a maximum of 4.5m above ground level which is provided with an emergency escape window as described in paragraph 3.6.
f. A gallery that complies with paragraph 3.13.
A room accessed only via an inner room (an inner inner room) is acceptable when all of the following apply.
a. It complies with paragraph 3.7.
b. The access rooms each have a smoke alarm (see Section 1).
c. None of the access rooms is a kitchen.
landing
Escape route floor finishes should minimise their slipperiness when wet. Finishes include the treads of steps and surfaces of ramps and landings.
leading edge (of door)
See Diagram 2.1a. All habitable rooms (excluding kitchens) should have either of the following.
a. An opening directly onto a hall leading to a final exit.
b. An emergency escape window or door, as described in paragraph 2.10.
Basement storeys containing habitable rooms should have one of the following.
a. An emergency escape window or external door providing escape from the basement (paragraph 2.10).
b. A protected stairway (paragraph 2.5a) leading from the basement to a final exit.
Where it is undesirable to replace existing doors because of historical or architectural merit, the possibility of retaining, and where necessary upgrading, them should be investigated.
Two rooms may be served by a single window. A door between the rooms should provide access to the window without passing through the stair enclosure. Both rooms should have their own access to the internal stair.
All habitable rooms (excluding kitchens) should have either of the following.
a. An opening directly onto a hall leading to a final exit.
b. An emergency escape window or door, as described in paragraph 3.6.
All habitable rooms (excluding kitchens) should have either of the following.
a. An emergency escape window or external door, as described in paragraph 3.6.
b. In multi-storey flats, direct access to a protected internal stairway (minimum REI 30) leading to an exit from the flat.
Any alternative exit from a flat should comply with all of the following.
a. It should be remote from the main entrance door to the flat.
b. It should lead to a final exit, via a common stair if necessary, through one of the following.
i. A door to an access corridor, access lobby or common balcony.
ii. An internal private stair leading to an access corridor, access lobby or common balcony at another level.
iii. A door to a common stair.
iv. A door to an external stair.
v. A door to an escape route over a flat roof.
Any access route leading to a final exit or common stair should comply with the provisions for means of escape in the common parts of a flat (see paragraph 3.25).
Basement storeys containing habitable rooms should have one of the following.
a. An emergency escape window or external door providing escape from the basement (see paragraph 3.6).
b. A protected stairway (minimum REI 30) leading from the basement to a final exit.
level
See para 3.21
NOTE: This only applies where at least one storey is more than 4.5m above ground level.
Alternative exit
Bathroom
ENTRANCE LEVEL
LEVEL(S) ABOVE OR BELOW ENTRANCE LEVEL
liftway
A passenger lift serving any storey more than 4.5m above ground level should be in either of the following.
a. The enclosure to the protected stairway, as described in paragraph 2.5.
b. A fire resisting lift shaft (minimum REI 30).
A protected stairway should not be used for anything else, except a lift well or electricity meters.
light reflectance value (lrv)
All escape routes should have adequate artificial lighting. If the mains electricity power supply fails, escape lighting should illuminate the route (including external escape routes).
All escape routes should have adequate artificial lighting. If the mains electricity power supply fails, escape lighting should illuminate the route (including external escape routes).
Escape lighting should conform to BS 5266-1.
Escape lighting should conform to BS 5266-1.
limiting air permeability
Air circulation systems which circulate air within an individual dwellinghouse with a floor more than
4.5m above ground level should meet the guidance given in paragraph 2.9.
live/work unit
For flats serving as a workplace for both occupants and people who do not live on the premises, provide both of the following.
a. A maximum travel distance of 18m between any part of the working area and either of the following.
i. The flat entrance door.
ii. An alternative means of escape that is not a window.
If the travel distance is over 18m, the assumptions in paragraph 3.2 may not be valid. The design should be considered on a case-by-case basis.
b. Escape lighting to windowless accommodation in accordance with BS 5266-1.
Paragraphs 3.6 to 3.23 deal with the means of escape within each flat. Paragraphs 3.25 to 3.89 deal with the means of escape in common areas of the building (including mixed use buildings in paragraphs 3.76 and 3.77). Guidance for live/work units is given in paragraph 3.24.
live–work units
Where access from any habitable room to the entrance hall or flat entrance is impossible without passing through another room, all of the following conditions should be met (Diagram 3.4).
a. Bedrooms should be separated from living accommodation by fire resisting construction (minimum REI 30) and fire doorsets (minimum E 20).
b. The alternative exit should be in the part of the flat that contains the bedrooms.
For flats serving as a workplace for both occupants and people who do not live on the premises, provide both of the following.
a. A maximum travel distance of 18m between any part of the working area and either of the following.
i. The flat entrance door.
ii. An alternative means of escape that is not a window.
If the travel distance is over 18m, the assumptions in paragraph 3.2 may not be valid. The design should be considered on a case-by-case basis.
b. Escape lighting to windowless accommodation in accordance with BS 5266-1.
Paragraphs 3.6 to 3.23 deal with the means of escape within each flat. Paragraphs 3.25 to 3.89 deal with the means of escape in common areas of the building (including mixed use buildings in paragraphs 3.76 and 3.77). Guidance for live/work units is given in paragraph 3.24.
See para 3.19
NOTE: The bedrooms are not classified as inner rooms because escape is possible in two directions.
Fire doorset
Fire resisting construction (minimum REI 30) between living and bedroom accommodation
Alternative exit
maintenance and operational strategy
Smoke alarms should be mains operated and conform to BS EN 14604.
Heat alarms should be mains operated and conform to BS 5446-2.
material changes of use
Where it is undesirable to replace existing doors because of historical or architectural merit, the possibility of retaining, and where necessary upgrading, them should be investigated.
means of escape
Means of warning and escape
B1.The building shall be designed and constructed so that there are appropriate provisions for the early warning of fire, and appropriate means of escape in case of fire from the building to a place of safety outside the building capable of being safely and effectively used at all material times.
Requirement B1 does not apply to any prison provided under section 33 of the Prison Act 1952
(a) (power to provide prisons, etc.).
(a) 1952 c. 52; section 33 was amended by section 100 of the Criminal Justice and Public Order Act 1994 (c. 33) and by S.I. 1963/597.
In the Secretary of State’s view, requirement B1 is met by achieving all of the following.
a. There are sufficient means for giving early warning of fire to people in the building.
b. All people can escape to a place of safety without external assistance.
c. Escape routes are suitably located, sufficient in number and of adequate capacity.
d. Where necessary, escape routes are sufficiently protected from the effects of fire and smoke.
e. Escape routes are adequately lit and exits are suitably signed.
f. There are appropriate provisions to limit the ingress of smoke to the escape routes, or to
restrict the spread of fire and remove smoke.
g. For buildings containing flats, there are appropriate provisions to support a stay put evacuation
strategy.
The extent to which any of these measures are necessary is dependent on the use of the building,
its size and its height.
Building work and material changes of use subject to requirement B1 include both new and existing
buildings.
Where a flat roof forms part of a means of escape, it should comply with all of the following.
a. It should be part of the same building from which escape is being made.
b. The route across the roof should lead to a storey exit or external escape route.
c. The part of the roof (including its supporting structure) forming the escape route, and any opening within 3m of the escape route, should be of fire resisting construction (minimum REI 30).
Separate guidance applies to means of escape within the flat and within the common parts of the building that lead to a place of safety. Flats at ground level are treated similarly to dwellinghouses. With increasing height, more complex provisions are needed.
NOTES:
1. This diagram does not apply where the gallery is provided with one of the following:
i. An alternative escape route
ii. An emergency escape window (where the gallery floor is not more than 4.5m above ground level).
2. Any cooking facilities within a room containing a gallery should comply with one of the following conditions:
i. Be enclosed with fire resisting construction
ii. Be remote from the stair to the gallery and positioned such that they do not prejudice escape from the gallery.
See para 3.13
Where a flat roof forms part of a means of escape, it should comply with all of the following.
a. It should be part of the same building from which escape is being made.
b. The route across the roof should lead to a storey exit or external escape route.
c. The part of the roof (including its supporting structure) forming the escape route, and any opening within 3m of the escape route, should be of fire resisting construction (minimum REI 30).
A person escaping through the common area, if confronted by the effects of a fire in another flat, should be able to turn away from it and make a safe escape via an alternative route.
Provisions are recommended to support a stay put evacuation strategy for blocks of flats. It is based on the principle that a fire is contained in the flat of origin and common escape routes are maintained relatively free from smoke and heat. It allows occupants, some of whom may require assistance to escape in the event of a fire, in other flats that are not affected to remain.
Sufficient protection to common means of escape is necessary to allow occupants to escape should they choose to do so or are instructed/aided to by the fire service. A higher standard of protection is therefore needed to ensure common escape routes remain available for a longer period than is provided in other buildings.
Where a storey or part of a building has multiple escape routes available, one may be over a flat roof that complies with all of the following.
a. It should be part of the same building from which escape is being made.
b. The route across the roof should lead to a storey exit or external escape route.
c. The part of the roof (including its supporting structure) forming the escape route, and any opening within 3m of the escape route, should be of fire resisting construction (minimum REI 30).
d. The route should be clearly defined and guarded by walls and/or protective barriers to protect against falling.
Escape route travel distances should comply with Table 3.1.
All escape routes should have adequate artificial lighting. If the mains electricity power supply fails, escape lighting should illuminate the route (including external escape routes).
Escape stair lighting should be on a separate circuit from the electricity supply to any other part of the escape route.
In a converted building with a maximum of three storeys, a minimum REI 30 fire resistance could be accepted for elements of structure if the means of escape conform to the provisions of Section 3.
measurement
NOTES:
1. If travel distance is measured to a stair lobby, the lobby must not provide direct access to any storage room, flat or other space containing a fire hazard.
2. In the case of a small single stair building in accordance with Diagram 3.9, this is reduced to 4.5m.
3. Does not apply if all flats on a storey have independent alternative means of escape.
4. Sheltered housing may require reduced maximum travel distances.
Escape route travel distances should comply with Table 3.1.
In buildings with a maximum of three storeys above the ground storey, stairs may serve both flats and other occupancies, provided that the stairs are separated from each occupancy by protected lobbies (minimum REI 30) at each storey.
mixed-use developments
These provisions do not apply to the following.
a. The common parts of a sheltered housing development, such as communal lounges.
b. Sheltered accommodation in the 'residential (institutional)' or 'residential (other)' purpose groups (purpose group 2(a) or 2(b)).
In these parts, means of warning should follow the guidance for buildings other than dwellings in Volume 2 of Approved Document B.
Paragraph 3.27 may be modified using the guidance in clause 7.3 of BS 9991.
non-combustible material
A protected circuit to operate equipment during a fire should achieve all of the following.
a. Cables should achieve PH 30 classification when tested in accordance with BS EN 50200 (incorporating Annex E) or an equivalent standard.
b. It should only pass through parts of the building in which the fire risk is negligible.
c. It should be separate from any circuit provided for another purpose.
non-worsening (of compliance)
Work should comply with Parts K and L of Schedule 1 to the Building Regulations. When complete, the building should comply with other applicable parts of Schedule 1 to at least the same level as before.
nosing
Except in buildings that comply with Diagram 3.9, the corridor or lobby next to each stair should have a smoke vent. The location of the vent should comply with both of the following.
a. Be as high as practicable.
b. Be positioned so the top edge is at least as high as the top of the door to the stair.
notified body
Gas service and installation pipes and meters should not be within a protected stairway, unless installed in accordance with the Pipelines Safety Regulations 1996 and the Gas Safety (Installation and Use) Regulations 1998.
occupiable room
Smoke alarms should be provided in the circulation spaces of the dwelling in accordance with
paragraphs 1.1 to 1.4.
NOTE: This does not apply where inner rooms are provided (see paragraph 2.11 for inner room
requirements).
An inner room is permitted when it is one of the following.
a. A kitchen.
b. A laundry or utility room.
c. A dressing room.
d. A bathroom, WC or shower room.
e. Any room on a storey that is a maximum of 4.5m above ground level which is provided with an emergency escape window as described in paragraph 2.10.
f. A gallery that complies with paragraph 2.15.
A room accessed only via an inner room (an inner inner room) is acceptable when all of the following apply.
a. It complies with paragraph 2.11.
b. The access rooms each have a smoke alarm (see Section 1).
c. None of the access rooms is a kitchen.
See para 3.19
NOTE: The bedrooms are not classified as inner rooms because escape is possible in two directions.
Fire doorset
Fire resisting construction (minimum REI 30) between living and bedroom accommodation
Alternative exit
In addition, escape lighting should be provided to all of the following.
a. Toilet accommodation with a minimum floor area of 8m2.
b. Electricity and generator rooms.
c. Switch room/battery room for emergency lighting system.
d. Emergency control rooms.
An inner room is permitted when it is one of the following.
a. A kitchen.
b. A laundry or utility room.
c. A dressing room.
d. A bathroom, WC or shower room.
e. Any room on a storey that is a maximum of 4.5m above ground level which is provided with an emergency escape window as described in paragraph 3.6.
f. A gallery that complies with paragraph 3.13.
A room accessed only via an inner room (an inner inner room) is acceptable when all of the following apply.
a. It complies with paragraph 3.7.
b. The access rooms each have a smoke alarm (see Section 1).
c. None of the access rooms is a kitchen.
open spatial planning
A large dwellinghouse has more than one storey, and at least one storey exceeds 200m2.
See paras 2.1 to 2.6
Single storey dwellinghouse(see paragraph 2.1)
Dwellinghouse with one storey more than 4.5m above ground level(see paragraph 2.5)
Dwellinghouse with two or more storeys more than 4.5m above ground level(see paragraph 2.6)
See para 3.21
NOTE: This only applies where at least one storey is more than 4.5m above ground level.
Alternative exit
Bathroom
ENTRANCE LEVEL
LEVEL(S) ABOVE OR BELOW ENTRANCE LEVEL
open-flued appliance
Air circulation systems which circulate air within an individual dwellinghouse with a floor more than
4.5m above ground level should meet the guidance given in paragraph 2.9.
outcomes-based system
Fire detection and alarm systems sometimes trigger other systems. The interface between systems
must be reliable. Particular care should be taken if the interface is facilitated via another system.
Where any part of BS 7273 applies to the triggering of other systems, the recommendations of that
part of BS 7273 should be followed.
part b - fire safety
Each flat in a block should have alarms as set out in paragraphs 1.1 to 1.4. With effective compartmentation, a communal fire alarm system is not normally needed. In some buildings, detectors in common parts of the building may need to operate smoke control or other fire protection systems but do not usually sound an audible warning.
Work should comply with Parts K and L of Schedule 1 to the Building Regulations. When complete, the building should comply with other applicable parts of Schedule 1 to at least the same level as before.
The internal arrangement of single storey or multi-storey flats should comply with paragraphs 3.15 to 3.17. Alternatively, the guidance in paragraphs 3.18 to 3.22 may be followed.
A flat accessed via the common parts of the building should also comply with the provisions for small single stair buildings in paragraph 3.28 and Diagram 3.9. A protected entrance hall may be required as a result.
Paragraph 3.27 may be modified using the guidance in clause 7.3 of BS 9991.
Every doorway or other exit providing access to a means of escape, other than exits in ordinary use (e.g. main entrances), should be distinctively and conspicuously marked by an exit sign in accordance with BS ISO 3864-1 and BS 5499-4. For this reason, blocks of flats with a single stair in regular use would not usually require any fire exit signage.
Advice on fire safety signs, including emergency escape signs, is given in the HSE publication Safety Signs and Signals: Guidance on Regulations.
Some buildings may require additional signs to comply with other legislation.
part l - conservation of fuel and power
Guidance on cables for large and complex buildings is given in BS 5839-1, BS 5266-1 and BS 8519.
passive stack ventilation (psv)
All of the following precautions should be taken to avoid the spread of smoke and fire to the protected stairway.
a. Transfer grilles should not be fitted in any wall, door, floor or ceiling of the stair enclosure.
b. Any duct passing through the stair enclosure should be rigid steel. Joints between the ductwork and stair enclosure should be fire-stopped.
c. Ventilation ducts supplying or extracting air directly to or from a protected stairway should not serve other areas as well.
d. Any system of mechanical ventilation which recirculates air and which serves both the stair and other areas should be designed to shut down on the detection of smoke within the system.
e. For ducted warm air heating systems, a room thermostat should be sited in the living room. It should be mounted at a height between 1370mm and 1830mm above the floor. The maximum setting should be 27°C.
NOTE: Ventilation ducts passing through compartment walls should comply with the guidance in Section 9.
For systems circulating air only within an individual flat, take all of the following precautions.
a. Transfer grilles should not be fitted in any wall, door, floor or ceiling of the enclosure.
b. Any duct passing through the enclosure should be rigid steel. Joints between the ductwork and enclosure should be fire-stopped.
c. Ventilation ducts serving the enclosure should not serve any other areas.
d. Any system of mechanical ventilation which recirculates air and which serves both the stair and other areas should be designed to shut down on the detection of smoke within the system.
e. For ducted warm air heating systems, a room thermostat should be sited in the living room. It should be mounted at a height between 1370mm and 1830mm above the floor. The maximum setting should be 27°C.
NOTE: Ventilation ducts passing through compartment walls should comply with the guidance in Section 9.
Access to an external escape stair may be via a flat roof, provided the flat roof meets the requirements of paragraph 3.30.
permanent opening is a ventilation opening
The approach to rooms containing refuse chutes or for storing refuse should comply with one of the following conditions.
a. Be directly from the open air.
b. Be through a protected lobby with a minimum of 0.2m2 of permanent ventilation.
pier
If a loadbearing wall is any of the following, guidance in other sections may also apply.
a. A compartment wall (including a wall common to two buildings): Section 7.
b. Enclosing a place of special fire hazard: Section 7.
c. Protecting a means of escape: Sections 2 and 3.
d. An external wall: Sections 10 and 11.
e. Enclosing a firefighting shaft: Section 15.
pitch
A ramp forming part of an escape route should meet the provisions in Approved Document M. Any sloping floor or tier should have a pitch of not more than 35 degrees to the horizontal.
If a protected stairway projects beyond, is recessed from or is in an internal angle of the adjoining external wall of the building, then the minimum distance between an unprotected area of the building enclosure and an unprotected area of the stair enclosure should be 1800mm.
place of special fire hazard
Where new habitable rooms are provided, a fire detection and alarm system should be installed
where either of the following applies.
a. The room is provided above or below the ground storey.
b. The room is provided at the ground storey, without a final exit.
Smoke alarms should be provided in the circulation spaces of the dwelling in accordance with
paragraphs 1.1 to 1.4.
NOTE: This does not apply where inner rooms are provided (see paragraph 2.11 for inner room
requirements).
An inner room is permitted when it is one of the following.
a. A kitchen.
b. A laundry or utility room.
c. A dressing room.
d. A bathroom, WC or shower room.
e. Any room on a storey that is a maximum of 4.5m above ground level which is provided with an emergency escape window as described in paragraph 2.10.
f. A gallery that complies with paragraph 2.15.
A room accessed only via an inner room (an inner inner room) is acceptable when all of the following apply.
a. It complies with paragraph 2.11.
b. The access rooms each have a smoke alarm (see Section 1).
c. None of the access rooms is a kitchen.
Two rooms may be served by a single window. A door between the rooms should provide access to the window without passing through the stair enclosure. Both rooms should have their own access to the internal stair.
Two rooms may be served by a single escape window. A door between rooms should provide access to the escape window without passing through the stair enclosure. Both rooms should have their own access to the internal stair.
In addition, escape lighting should be provided to all of the following.
a. Toilet accommodation with a minimum floor area of 8m2.
b. Electricity and generator rooms.
c. Switch room/battery room for emergency lighting system.
d. Emergency control rooms.
An inner room is permitted when it is one of the following.
a. A kitchen.
b. A laundry or utility room.
c. A dressing room.
d. A bathroom, WC or shower room.
e. Any room on a storey that is a maximum of 4.5m above ground level which is provided with an emergency escape window as described in paragraph 3.6.
f. A gallery that complies with paragraph 3.13.
Except in buildings described in paragraph 3.28, common stairs forming part of the only escape route from a flat should not serve any of the following.
a. Covered car park.
b. Boiler room.
c. Fuel storage space.
d. Other ancillary accommodation of similar fire risk.
A room accessed only via an inner room (an inner inner room) is acceptable when all of the following apply.
a. It complies with paragraph 3.7.
b. The access rooms each have a smoke alarm (see Section 1).
c. None of the access rooms is a kitchen.
plans certificates
Work should comply with Parts K and L of Schedule 1 to the Building Regulations. When complete, the building should comply with other applicable parts of Schedule 1 to at least the same level as before.
Gas service and installation pipes and meters should not be within a protected stairway, unless installed in accordance with the Pipelines Safety Regulations 1996 and the Gas Safety (Installation and Use) Regulations 1998.
plot gradient
See Diagram 2.1d. In addition to meeting the provisions in paragraph 2.5, the dwellinghouse should comply with either of the following.
a. Provide an alternative escape route from each storey more than 7.5m above ground level. At the first storey above 7.5m, the protected stairway should be separated from the lower storeys by fire resisting construction (minimum REI 30) if the alternative escape route is accessed via either of the following.
i. The protected stairway to an upper storey.
ii. A landing within the protected stairway enclosure to an alternative escape route on the same storey. The protected stairway at or about 7.5m above ground level should be separated from the lower storeys or levels by fire resisting construction (see Diagram 2.4).
b. Provide a sprinkler system throughout, designed and installed in accordance with BS 9251.
A multi-storey flat with an independent external entrance at ground level is similar to a dwellinghouse and means of escape should be planned on the basis of Section 2, depending on the height of the top storey above ground level.
When multi-storey flats do not have their own external entrance at ground level, adopt one of the following approaches.
a. Approach 1 – provide at least one alternative exit from each habitable room that is not on the entrance storey of the flat (Diagram 3.5 and paragraph 3.22).
b. Approach 2 – provide at least one alternative exit from each storey that is not the entrance storey of the flat. All habitable rooms should have direct access to a protected landing (Diagram 3.6 and paragraph 3.22).
c. Approach 3 – provide a protected stairway plus a sprinkler system in accordance with Appendix E and provide smoke alarms in accordance with BS 5839-6.
d. Approach 4 – if the vertical distance between the entrance storey of the flat and any of the storeys above or below does not exceed 7.5m, provide all of the following.
i. A protected stairway.
ii. Additional smoke alarms in all habitable rooms.
iii. A heat alarm in any kitchen.
Escape route floor finishes should minimise their slipperiness when wet. Finishes include the treads of steps and surfaces of ramps and landings.
See para 3.21
NOTE: This only applies where at least one storey is more than 4.5m above ground level.
Alternative exit
Bathroom
ENTRANCE LEVEL
LEVEL(S) ABOVE OR BELOW ENTRANCE LEVEL
potential level access shower
A gallery should comply with one of the following.
a. It should be provided with an alternative exit.
b. It should be provided with an emergency escape window, as described in paragraph 2.10, where the gallery floor is a maximum of 4.5m above ground level.
c. It should meet all the conditions shown in Diagram 2.6.
Two rooms may be served by a single window. A door between the rooms should provide access to the window without passing through the stair enclosure. Both rooms should have their own access to the internal stair.
Air circulation systems which circulate air within an individual dwellinghouse with a floor more than
4.5m above ground level should meet the guidance given in paragraph 2.9.
A gallery should comply with one of the following.
a. It should be provided with an alternative exit.
b. It should be provided with an emergency escape window, as described in paragraph 3.6, where the gallery floor is a maximum of 4.5m above ground level.
c. It should meet the conditions shown in Diagram 3.1.
Two rooms may be served by a single escape window. A door between rooms should provide access to the escape window without passing through the stair enclosure. Both rooms should have their own access to the internal stair.
pre-construction information
Refuse storage chambers, refuse chutes and refuse hoppers should be sited and constructed in accordance with BS 5906.
prefabricated appliance chamber
Refuse storage chambers, refuse chutes and refuse hoppers should be sited and constructed in accordance with BS 5906.
prescriptive system
Fire detection and alarm systems sometimes trigger other systems. The interface between systems
must be reliable. Particular care should be taken if the interface is facilitated via another system.
Where any part of BS 7273 applies to the triggering of other systems, the recommendations of that
part of BS 7273 should be followed.
primary thermal store
Heat alarms should be mains operated and conform to BS 5446-2.
principal communal entrance
Each flat in a block should have alarms as set out in paragraphs 1.1 to 1.4. With effective compartmentation, a communal fire alarm system is not normally needed. In some buildings, detectors in common parts of the building may need to operate smoke control or other fire protection systems but do not usually sound an audible warning.
In student residences that are designed and occupied as a block of flats, separate automatic detection should be provided in each self-contained flat where all of the following apply.
a. A group of up to six students shares the flat.
b. Each flat has its own entrance door.
c. The compartmentation principles for flats in Section 7 have been followed.
Where a total evacuation strategy is adopted, the alarm system should follow the guidance for buildings other than dwellings in Volume 2 of Approved Document B.
These provisions do not apply to the following.
a. The common parts of a sheltered housing development, such as communal lounges.
b. Sheltered accommodation in the 'residential (institutional)' or 'residential (other)' purpose groups (purpose group 2(a) or 2(b)).
In these parts, means of warning should follow the guidance for buildings other than dwellings in Volume 2 of Approved Document B.
The internal arrangement of single storey or multi-storey flats should comply with paragraphs 3.15 to 3.17. Alternatively, the guidance in paragraphs 3.18 to 3.22 may be followed.
A flat accessed via the common parts of the building should also comply with the provisions for small single stair buildings in paragraph 3.28 and Diagram 3.9. A protected entrance hall may be required as a result.
One of the following approaches should be adopted, observing the inner room restrictions described in paragraphs 3.7 and 3.8.
a. Provide a protected entrance hall (minimum REI 30) serving all habitable rooms that meets the conditions shown in Diagram 3.2.
b. Plan the flat to meet the conditions shown in Diagram 3.3, so that both of the following apply.
i. The travel distance from the flat entrance door to any point in any habitable room is a maximum of 9m.
ii. Cooking facilities are remote from the main entrance door and do not impede the escape route from anywhere in the flat.
c. Provide an alternative exit from the flat complying with paragraph 3.22.
Where access from any habitable room to the entrance hall or flat entrance is impossible without passing through another room, all of the following conditions should be met (Diagram 3.4).
a. Bedrooms should be separated from living accommodation by fire resisting construction (minimum REI 30) and fire doorsets (minimum E 20).
b. The alternative exit should be in the part of the flat that contains the bedrooms.
The provisions in this section make the following assumptions.
a. Any fire is likely to be in a flat.
b. There is no reliance on external rescue.
c. Simultaneous evacuation of all flats is unlikely to be necessary due to compartmentation.
d. Fires in common parts of the building should not spread beyond the fabric in the immediate vicinity. In some cases, however, communal facilities exist that require additional measures to be taken.
When multi-storey flats do not have their own external entrance at ground level, adopt one of the following approaches.
a. Approach 1 – provide at least one alternative exit from each habitable room that is not on the entrance storey of the flat (Diagram 3.5 and paragraph 3.22).
b. Approach 2 – provide at least one alternative exit from each storey that is not the entrance storey of the flat. All habitable rooms should have direct access to a protected landing (Diagram 3.6 and paragraph 3.22).
c. Approach 3 – provide a protected stairway plus a sprinkler system in accordance with Appendix E and provide smoke alarms in accordance with BS 5839-6.
d. Approach 4 – if the vertical distance between the entrance storey of the flat and any of the storeys above or below does not exceed 7.5m, provide all of the following.
i. A protected stairway.
ii. Additional smoke alarms in all habitable rooms.
iii. A heat alarm in any kitchen.
For flats serving as a workplace for both occupants and people who do not live on the premises, provide both of the following.
a. A maximum travel distance of 18m between any part of the working area and either of the following.
i. The flat entrance door.
ii. An alternative means of escape that is not a window.
If the travel distance is over 18m, the assumptions in paragraph 3.2 may not be valid. The design should be considered on a case-by-case basis.
b. Escape lighting to windowless accommodation in accordance with BS 5266-1.
From the flat entrance door, a single escape route is acceptable in either of the following cases.
a. The flat is on a storey served by a single common stair and both of the following apply.
i. Every flat is separated from the common stair by a protected lobby or common protected corridor (see Diagram 3.7).
ii. The maximum travel distance in Table 3.1, for escape in one direction only, is not exceeded.
b. The flat is in a dead end of a common corridor served by two (or more) common stairs and the maximum travel distance given in Table 3.1, for escape in one direction only, is not exceeded (Diagram 3.8).
See para 3.18
Flat entrance
Kitchen area
Bath
The following paragraphs deal with means of escape from the entrance doors of flats to a final exit.
principal entrance
When multi-storey flats do not have their own external entrance at ground level, adopt one of the following approaches.
a. Approach 1 – provide at least one alternative exit from each habitable room that is not on the entrance storey of the flat (Diagram 3.5 and paragraph 3.22).
b. Approach 2 – provide at least one alternative exit from each storey that is not the entrance storey of the flat. All habitable rooms should have direct access to a protected landing (Diagram 3.6 and paragraph 3.22).
c. Approach 3 – provide a protected stairway plus a sprinkler system in accordance with Appendix E and provide smoke alarms in accordance with BS 5839-6.
d. Approach 4 – if the vertical distance between the entrance storey of the flat and any of the storeys above or below does not exceed 7.5m, provide all of the following.
i. A protected stairway.
ii. Additional smoke alarms in all habitable rooms.
iii. A heat alarm in any kitchen.
See para 3.18
Flat entrance
Kitchen area
Bath
principal private entrance
One of the following approaches should be adopted, observing the inner room restrictions described in paragraphs 3.7 and 3.8.
a. Provide a protected entrance hall (minimum REI 30) serving all habitable rooms that meets the conditions shown in Diagram 3.2.
b. Plan the flat to meet the conditions shown in Diagram 3.3, so that both of the following apply.
i. The travel distance from the flat entrance door to any point in any habitable room is a maximum of 9m.
ii. Cooking facilities are remote from the main entrance door and do not impede the escape route from anywhere in the flat.
c. Provide an alternative exit from the flat complying with paragraph 3.22.
A multi-storey flat with an independent external entrance at ground level is similar to a dwellinghouse and means of escape should be planned on the basis of Section 2, depending on the height of the top storey above ground level.
When multi-storey flats do not have their own external entrance at ground level, adopt one of the following approaches.
a. Approach 1 – provide at least one alternative exit from each habitable room that is not on the entrance storey of the flat (Diagram 3.5 and paragraph 3.22).
b. Approach 2 – provide at least one alternative exit from each storey that is not the entrance storey of the flat. All habitable rooms should have direct access to a protected landing (Diagram 3.6 and paragraph 3.22).
c. Approach 3 – provide a protected stairway plus a sprinkler system in accordance with Appendix E and provide smoke alarms in accordance with BS 5839-6.
d. Approach 4 – if the vertical distance between the entrance storey of the flat and any of the storeys above or below does not exceed 7.5m, provide all of the following.
i. A protected stairway.
ii. Additional smoke alarms in all habitable rooms.
iii. A heat alarm in any kitchen.
For flats serving as a workplace for both occupants and people who do not live on the premises, provide both of the following.
a. A maximum travel distance of 18m between any part of the working area and either of the following.
i. The flat entrance door.
ii. An alternative means of escape that is not a window.
If the travel distance is over 18m, the assumptions in paragraph 3.2 may not be valid. The design should be considered on a case-by-case basis.
b. Escape lighting to windowless accommodation in accordance with BS 5266-1.
The following paragraphs deal with means of escape from the entrance doors of flats to a final exit. They do not apply to flats with a top storey that is a maximum of 4.5m above ground level (designed in accordance with paragraphs 3.16 and 3.17).
Reference should also be made to the following.
a. Requirement B3 regarding compartment walls and protected shafts.
b. Requirement B5 regarding access for the fire and rescue service.
See para 3.18
Flat entrance
Kitchen area
Bath
The following paragraphs deal with means of escape from the entrance doors of flats to a final exit.
principal storey
A large dwellinghouse has more than one storey, and at least one storey exceeds 200m2.
A large dwellinghouse of two storeys (excluding basement storeys) should be fitted with a Grade A
Category LD3 fire detection and alarm system, as described in BS 5839-6.
A large dwellinghouse of three or more storeys (excluding basement storeys) should be fitted with
a Grade A Category LD2 fire detection and alarm system as described in BS 5839-6.
Where new habitable rooms are provided, a fire detection and alarm system should be installed
where either of the following applies.
a. The room is provided above or below the ground storey.
b. The room is provided at the ground storey, without a final exit.
Smoke alarms should be provided in the circulation spaces of the dwelling in accordance with
paragraphs 1.1 to 1.4.
NOTE: This does not apply where inner rooms are provided (see paragraph 2.11 for inner room
requirements).
See paras 2.1 to 2.6
Single storey dwellinghouse(see paragraph 2.1)
Dwellinghouse with one storey more than 4.5m above ground level(see paragraph 2.5)
Dwellinghouse with two or more storeys more than 4.5m above ground level(see paragraph 2.6)
Where a new storey is added through conversion to create a storey above 4.5m, both of the following should apply.
a. The full extent of the escape route should be addressed.
b. Fire resisting doors (minimum E 20) and partitions (minimum REI 30) should be provided, including upgrading the existing doors where necessary.
NOTE: Where the layout is open plan, new partitions should be provided to enclose the escape route (Diagram 2.2).
An alternative approach to that described in paragraph 2.21 would be to comply with all of the following.
a. Provide sprinkler protection to the open-plan areas.
b. Provide a fire resisting partition (minimum REI 30) and door (minimum E 20) to separate the ground storey from the upper storeys. The door should allow occupants of the loft room access to a first storey escape window.
c. Separate cooking facilities from the open-plan area with fire resisting construction (minimum REI 30).
Where escape from a dwellinghouse is to an enclosed space with exit only possible through other buildings (e.g. a courtyard or back garden), the length of the space should exceed whichever is the greater of the following.
a. The height of the dwellinghouse above ground level (x).
b. Where a rear extension is provided, the height of the extension (y).
See para 2.10
See Diagram 2.1d. In addition to meeting the provisions in paragraph 2.5, the dwellinghouse should comply with either of the following.
a. Provide an alternative escape route from each storey more than 7.5m above ground level. At the first storey above 7.5m, the protected stairway should be separated from the lower storeys by fire resisting construction (minimum REI 30) if the alternative escape route is accessed via either of the following.
i. The protected stairway to an upper storey.
ii. A landing within the protected stairway enclosure to an alternative escape route on the same storey. The protected stairway at or about 7.5m above ground level should be separated from the lower storeys or levels by fire resisting construction (see Diagram 2.4).
b. Provide a sprinkler system throughout, designed and installed in accordance with BS 9251.
The internal arrangement of single storey or multi-storey flats should comply with paragraphs 3.15 to 3.17. Alternatively, the guidance in paragraphs 3.18 to 3.22 may be followed.
A flat accessed via the common parts of the building should also comply with the provisions for small single stair buildings in paragraph 3.28 and Diagram 3.9. A protected entrance hall may be required as a result.
Where access from any habitable room to the entrance hall or flat entrance is impossible without passing through another room, all of the following conditions should be met (Diagram 3.4).
a. Bedrooms should be separated from living accommodation by fire resisting construction (minimum REI 30) and fire doorsets (minimum E 20).
b. The alternative exit should be in the part of the flat that contains the bedrooms.
A multi-storey flat with an independent external entrance at ground level is similar to a dwellinghouse and means of escape should be planned on the basis of Section 2, depending on the height of the top storey above ground level.
When multi-storey flats do not have their own external entrance at ground level, adopt one of the following approaches.
a. Approach 1 – provide at least one alternative exit from each habitable room that is not on the entrance storey of the flat (Diagram 3.5 and paragraph 3.22).
b. Approach 2 – provide at least one alternative exit from each storey that is not the entrance storey of the flat. All habitable rooms should have direct access to a protected landing (Diagram 3.6 and paragraph 3.22).
c. Approach 3 – provide a protected stairway plus a sprinkler system in accordance with Appendix E and provide smoke alarms in accordance with BS 5839-6.
d. Approach 4 – if the vertical distance between the entrance storey of the flat and any of the storeys above or below does not exceed 7.5m, provide all of the following.
i. A protected stairway.
ii. Additional smoke alarms in all habitable rooms.
iii. A heat alarm in any kitchen.
For some low rise buildings, the provisions in paragraphs 3.26 and 3.27 may be modified and the use of a single stair, protected in accordance with Diagram 3.9, may be permitted where all of the following apply.
a. The top storey of the building is a maximum of 11m above ground level.
b. No more than three storeys are above the ground storey.
c. The stair does not connect to a covered car park, unless the car park is open sided (as defined in Section 11 of Approved Document B Volume 2).
d. The stair does not serve offices, stores or other ancillary accommodation. If it does, they should be separated from the stair by a protected lobby or protected corridor (minimum REI 30) with a minimum 0.4m2 of permanent ventilation, or be protected from the ingress of smoke by a mechanical smoke control system.
NOTE: For refuse chutes and storage see paragraphs 3.55 to 3.58.
e. Either of the following is provided for the fire and rescue service.
i. A high-level openable vent with a free area of at least 1m2 at each storey.
ii. A single openable vent with a free area of at least 1m2 at the head of the stair, operable remotely at the fire and rescue service access level.
Common corridors should be protected corridors. The wall between each flat and the corridor should be a compartment wall (minimum REI 30 where the top storey is up to 5m above ground level, otherwise REI 60).
Ancillary accommodation should not be located in, or entered from, a protected lobby or protected corridor forming the only common escape route on that storey.
See para 3.21
NOTE: This only applies where at least one storey is more than 4.5m above ground level.
Alternative exit
Bathroom
ENTRANCE LEVEL
LEVEL(S) ABOVE OR BELOW ENTRANCE LEVEL
Smoke vents should comply with one of the following.
a. They should be located on an external wall with minimum free area of 1.5m2.
b. They should discharge into a vertical smoke shaft, closed at the base, that meets all of the following criteria.
i. The shaft should conform to the following conditions.
• Have a minimum cross-sectional area of 1.5m2 (minimum dimension 0.85m in any direction).
• Open at roof level, minimum 0.5m above any surrounding structures within 2m of it horizontally.
• Extend a minimum of 2.5m above the ceiling of the highest storey served by the shaft.
ii. The free area of all the following vents should be a minimum of 1m2 in the following places.
• From the corridor or lobby into the shaft.
• At the opening at the head of the shaft.
• At all internal locations within the shaft (e.g. safety grilles).
iii. The smoke shaft should be constructed from a class A1 material. All vents should either be a fire doorset (see Appendix C, Table C1, item 2.e for minimum fire resistance) or fitted with a smoke control damper achieving the same period of fire resistance and designed to operate as described below. The shaft should be vertical from base to head, with a maximum of 4m at a maximum inclined angle of 30 degrees.
iv. If smoke is detected in the common corridor or lobby, both of the following should occur.
• Simultaneous opening of vents on the storey where the fire is located, at the top of the smoke shaft and to the stair.
• Vents from the corridors or lobbies on all other storeys should remain closed, even if smoke is subsequently detected on storeys other than where the fire is located.
A vent to the outside with a minimum free area of 1m2 should be provided from the top storey of the stair.
In single stair buildings, smoke vents on the storey where the fire is initiated, and the vent at the head of the stair, should be activated by smoke detectors in the common parts.
In buildings with more than one stair, smoke vents may be activated manually. The control system should open the vent at the head of the stair before, or at the same time as, the vent on the storey where the fire is located. Smoke detection is not required for ventilation purposes in this instance.
Where a storey (or part of a building) is served by a single access stair, that stair may be external provided both of the following conditions are met.
a. The stair serves a floor not more than 6m above the ground level.
b. The stair meets the provisions in paragraph 3.62.
Where more than one escape route is available from a storey (or part of a building), then some of the escape routes from that storey or part of the building may be by way of an external stair provided all of the following conditions are met:
a. There is a at least one internal escape stair from every part of each storey (excluding plant areas).
b. The stair serves a floor not more than 6m above either the ground level or a roof podium which is itself served by an independent protected stairway.
c. The stair meets the provisions in paragraph 3.68.
If a building does not meet the criteria of paragraph 3.28, an escape stair forming part of the only escape route from an upper storey should not continue down to serve a basement storey. The basement storey should be served by a separate escape stair.
Where multiple escape stairs serve the upper storeys, only one needs to end at ground level. Other stairs may connect with the basement storeys if there is a protected lobby or a protected corridor between the stairs and accommodation at each basement level.
In buildings with a maximum of three storeys above the ground storey, stairs may serve both flats and other occupancies, provided that the stairs are separated from each occupancy by protected lobbies (minimum REI 30) at each storey.
In buildings with more than three storeys above the ground storey, stairs may serve the flats and other occupancies if all of the following apply.
a. The flat is ancillary to the main use of the building.
b. The flat has an independent alternative escape route.
c. The stair is separated from occupancies on lower storeys by a protected lobby (minimum REI 30) at each of those storeys.
d. The stair enclosure has at least the same standard of fire resistance as the structural elements of the building (see Appendix B, Table B4); if the stair is a firefighting stair, it should comply with the provisions in Section 15 (see also paragraph 3.60).
e. Any automatic fire detection and alarm system fitted in the main part of the building also covers all flats.
f. Any security measures in any parts of the building do not prevent escape at all material times.
a. SMALL SINGLE STAIR BUILDING
*If smoke control is provided in the lobby, the travel distance can be increased to 7.5m maximum(see Diagram 3.7, example b).
b. SMALL SINGLE STAIR BUILDING WITH NO MORE THAN TWO FLATS PER STOREY
The door between stair and lobby should be free from security fastenings.
If the flats have protected entrance halls, the lobby between the common stair and flat entrance is not essential.
NOTES:
1. The arrangements shown also apply to the top storey.
2. If the travel distance across the lobby in diagram (a) exceeds 4.5m, Diagram 3.7 applies.
3. Where,in Diagram (b), the lobby between the common stair and the dwelling is omitted in smal lsingle stair buildings, an automatic opening vent with a free area of at least 1m2 is required at the top of the stair,which is operated automatically on detection of smoke at any storey in the stair.
4. For further guidance on the fire rating of the fire doorsets from the corridor to the flat and/or stairway refer to Appendix C, Table C1.
Fire resisting construction
Openable vent at high level for fire service use (1.0m2 minimum free area); see paragraph 3.28eSee para 3.28
Diagram 3.9
principal works
The fire detection and alarm systems in flats should connect to a central monitoring point or alarm
receiving centre. The systems should alert the warden or supervisor and identify the individual flat
where a fire has been detected.
A gallery should comply with one of the following.
a. It should be provided with an alternative exit.
b. It should be provided with an emergency escape window, as described in paragraph 2.10, where the gallery floor is a maximum of 4.5m above ground level.
c. It should meet all the conditions shown in Diagram 2.6.
Any external escape stair should meet all of the following conditions (Diagram 2.7).
a. Doors to the stair should be fire resisting (minimum E 30), except for a single exit door from the building to the top landing of a downward-leading external stair.
b. Fire resisting construction (minimum RE 30) is required for the building envelope within the following zones, measured from the flights and landings of the external stair.
i. 1800mm horizontally.
ii. 9m vertically below.
iii. 1100mm above the top landing of the stair (except where the stair leads from basement to ground level).
c. Fire resisting construction (minimum RE 30) should be provided for any part of the building (including doors) within 1800mm of the escape route from the foot of the stair to a place of safety. This does not apply if there are alternative escape routes from the foot of the external escape stair.
d. Stairs more than 6m in height should be protected from adverse weather. Protection should prevent the build-up of snow or ice but does not require full enclosure.
e. Glazing in areas of fire resisting construction should be fixed shut and fire resisting (in terms of integrity, but not insulation) (minimum E 30).
Where an existing window would be an escape window in a new dwellinghouse, and is big enough to be used for escape purposes, then the replacement should comply with one of the following.
a. The replacement window should be sized to provide at least the same potential for escape.
b. If the existing window was larger than required for escape purposes, the opening can be reduced to the minimum described in paragraph 2.10.
Where a new storey is added through conversion to create a storey above 4.5m, both of the following should apply.
a. The full extent of the escape route should be addressed.
b. Fire resisting doors (minimum E 20) and partitions (minimum REI 30) should be provided, including upgrading the existing doors where necessary.
NOTE: Where the layout is open plan, new partitions should be provided to enclose the escape route (Diagram 2.2).
All of the following precautions should be taken to avoid the spread of smoke and fire to the protected stairway.
a. Transfer grilles should not be fitted in any wall, door, floor or ceiling of the stair enclosure.
b. Any duct passing through the stair enclosure should be rigid steel. Joints between the ductwork and stair enclosure should be fire-stopped.
c. Ventilation ducts supplying or extracting air directly to or from a protected stairway should not serve other areas as well.
d. Any system of mechanical ventilation which recirculates air and which serves both the stair and other areas should be designed to shut down on the detection of smoke within the system.
e. For ducted warm air heating systems, a room thermostat should be sited in the living room. It should be mounted at a height between 1370mm and 1830mm above the floor. The maximum setting should be 27°C.
NOTE: Ventilation ducts passing through compartment walls should comply with the guidance in Section 9.
A gallery should comply with one of the following.
a. It should be provided with an alternative exit.
b. It should be provided with an emergency escape window, as described in paragraph 3.6, where the gallery floor is a maximum of 4.5m above ground level.
c. It should meet the conditions shown in Diagram 3.1.
The provisions in this section make the following assumptions.
a. Any fire is likely to be in a flat.
b. There is no reliance on external rescue.
c. Simultaneous evacuation of all flats is unlikely to be necessary due to compartmentation.
d. Fires in common parts of the building should not spread beyond the fabric in the immediate vicinity. In some cases, however, communal facilities exist that require additional measures to be taken.
For systems circulating air only within an individual flat, take all of the following precautions.
a. Transfer grilles should not be fitted in any wall, door, floor or ceiling of the enclosure.
b. Any duct passing through the enclosure should be rigid steel. Joints between the ductwork and enclosure should be fire-stopped.
c. Ventilation ducts serving the enclosure should not serve any other areas.
d. Any system of mechanical ventilation which recirculates air and which serves both the stair and other areas should be designed to shut down on the detection of smoke within the system.
e. For ducted warm air heating systems, a room thermostat should be sited in the living room. It should be mounted at a height between 1370mm and 1830mm above the floor. The maximum setting should be 27°C.
NOTE: Ventilation ducts passing through compartment walls should comply with the guidance in Section 9.
For flats serving as a workplace for both occupants and people who do not live on the premises, provide both of the following.
a. A maximum travel distance of 18m between any part of the working area and either of the following.
i. The flat entrance door.
ii. An alternative means of escape that is not a window.
If the travel distance is over 18m, the assumptions in paragraph 3.2 may not be valid. The design should be considered on a case-by-case basis.
b. Escape lighting to windowless accommodation in accordance with BS 5266-1.
For some low rise buildings, the provisions in paragraphs 3.26 and 3.27 may be modified and the use of a single stair, protected in accordance with Diagram 3.9, may be permitted where all of the following apply.
a. The top storey of the building is a maximum of 11m above ground level.
b. No more than three storeys are above the ground storey.
c. The stair does not connect to a covered car park, unless the car park is open sided (as defined in Section 11 of Approved Document B Volume 2).
d. The stair does not serve offices, stores or other ancillary accommodation. If it does, they should be separated from the stair by a protected lobby or protected corridor (minimum REI 30) with a minimum 0.4m2 of permanent ventilation, or be protected from the ingress of smoke by a mechanical smoke control system.
NOTE: For refuse chutes and storage see paragraphs 3.55 to 3.58.
e. Either of the following is provided for the fire and rescue service.
i. A high-level openable vent with a free area of at least 1m2 at each storey.
ii. A single openable vent with a free area of at least 1m2 at the head of the stair, operable remotely at the fire and rescue service access level.
A ramp forming part of an escape route should meet the provisions in Approved Document M. Any sloping floor or tier should have a pitch of not more than 35 degrees to the horizontal.
To limit potential damage to cables in protected circuits, all of the following should apply.
a. Cables should be sufficiently robust.
b. Cable routes should be carefully selected and/or physically protected in areas where cables may be exposed to damage.
c. Methods of cable support should be class A1 rated and offer at least the same integrity as the cable. They should maintain circuit integrity and hold cables in place when exposed to fire.
A protected circuit to operate equipment during a fire should achieve all of the following.
a. Cables should achieve PH 30 classification when tested in accordance with BS EN 50200 (incorporating Annex E) or an equivalent standard.
b. It should only pass through parts of the building in which the fire risk is negligible.
c. It should be separate from any circuit provided for another purpose.
Except in buildings that comply with Diagram 3.9, the corridor or lobby next to each stair should have a smoke vent. The location of the vent should comply with both of the following.
a. Be as high as practicable.
b. Be positioned so the top edge is at least as high as the top of the door to the stair.
Smoke vents should comply with one of the following.
a. They should be located on an external wall with minimum free area of 1.5m2.
b. They should discharge into a vertical smoke shaft, closed at the base, that meets all of the following criteria.
i. The shaft should conform to the following conditions.
• Have a minimum cross-sectional area of 1.5m2 (minimum dimension 0.85m in any direction).
• Open at roof level, minimum 0.5m above any surrounding structures within 2m of it horizontally.
• Extend a minimum of 2.5m above the ceiling of the highest storey served by the shaft.
ii. The free area of all the following vents should be a minimum of 1m2 in the following places.
• From the corridor or lobby into the shaft.
• At the opening at the head of the shaft.
• At all internal locations within the shaft (e.g. safety grilles).
iii. The smoke shaft should be constructed from a class A1 material. All vents should either be a fire doorset (see Appendix C, Table C1, item 2.e for minimum fire resistance) or fitted with a smoke control damper achieving the same period of fire resistance and designed to operate as described below. The shaft should be vertical from base to head, with a maximum of 4m at a maximum inclined angle of 30 degrees.
iv. If smoke is detected in the common corridor or lobby, both of the following should occur.
• Simultaneous opening of vents on the storey where the fire is located, at the top of the smoke shaft and to the stair.
• Vents from the corridors or lobbies on all other storeys should remain closed, even if smoke is subsequently detected on storeys other than where the fire is located.
A vent to the outside with a minimum free area of 1m2 should be provided from the top storey of the stair.
In single stair buildings, smoke vents on the storey where the fire is initiated, and the vent at the head of the stair, should be activated by smoke detectors in the common parts.
In buildings with more than one stair, smoke vents may be activated manually. The control system should open the vent at the head of the stair before, or at the same time as, the vent on the storey where the fire is located. Smoke detection is not required for ventilation purposes in this instance.
Any external escape stair should meet all of the following conditions (Diagram 3.11).
a. Doors to the stair should be fire resisting (minimum E 30) and be fitted with a self-closing device, except for a single exit door from the building to the top landing of a downward-leading external stair, provided it is the only door onto the landing.
b. Fire resisting construction (minimum RE 30) is required for the building envelope within the following zones, measured from the flights and landings of the external stair.
i. 1800mm above and horizontally.
ii. 9m vertically below.
iii. 1100mm above the top landing of the stair (except where the stair leads from basement to ground level).
c. Fire resisting construction (minimum RE 30) should be provided for any part of the building (including doors) within 1800mm of the escape route from the foot of the stair to a place of safety. This does not apply if there are alternative escape routes from the foot of the external escape stair.
d. Glazing in areas of fire resisting construction should be fixed shut and fire resisting (in terms of integrity but not insulation) (minimum E 30).
e. Stairs more than 6m in height above ground level (e.g. where they are provided above a podium) should be protected from adverse weather. Protection should prevent the build-up of snow or ice but does not require full enclosure.
In buildings with more than three storeys above the ground storey, stairs may serve the flats and other occupancies if all of the following apply.
a. The flat is ancillary to the main use of the building.
b. The flat has an independent alternative escape route.
c. The stair is separated from occupancies on lower storeys by a protected lobby (minimum REI 30) at each of those storeys.
d. The stair enclosure has at least the same standard of fire resistance as the structural elements of the building (see Appendix B, Table B4); if the stair is a firefighting stair, it should comply with the provisions in Section 15 (see also paragraph 3.60).
e. Any automatic fire detection and alarm system fitted in the main part of the building also covers all flats.
f. Any security measures in any parts of the building do not prevent escape at all material times.
private (area facilities or entrances)
See para 3.18
Flat entrance
Kitchen area
Bath
private stair
Any external escape stair should meet all of the following conditions (Diagram 2.7).
a. Doors to the stair should be fire resisting (minimum E 30), except for a single exit door from the building to the top landing of a downward-leading external stair.
b. Fire resisting construction (minimum RE 30) is required for the building envelope within the following zones, measured from the flights and landings of the external stair.
i. 1800mm horizontally.
ii. 9m vertically below.
iii. 1100mm above the top landing of the stair (except where the stair leads from basement to ground level).
c. Fire resisting construction (minimum RE 30) should be provided for any part of the building (including doors) within 1800mm of the escape route from the foot of the stair to a place of safety. This does not apply if there are alternative escape routes from the foot of the external escape stair.
d. Stairs more than 6m in height should be protected from adverse weather. Protection should prevent the build-up of snow or ice but does not require full enclosure.
e. Glazing in areas of fire resisting construction should be fixed shut and fire resisting (in terms of integrity, but not insulation) (minimum E 30).
See Diagram 2.1b. Where served by only one stair, all habitable rooms (excluding kitchens) should have either of the following.
a. An emergency escape window or external door, as described in paragraph 2.10.
b. Direct access to a protected stairway, as described in paragraph 2.5a.
Dwellinghouses with one internal stair should comply with paragraphs 2.5 and 2.6. In dwellinghouses with more than one stair, the stairs should provide effective alternative means of escape. The stairs should be physically separated by either of the following.
a. Fire resisting construction (minimum REI 30).
b. More than one room.
No fire resistance required for door
1100mm zone above top landing
1100mm zone above top landing
6m maximum height of stair
Fire resisting window (minimum RE30)
1800mm zone of fire resisting construction at side of stair
Fire doorset (minimum E30)
Ground level or a roof or podium served by an independent stairway
6m maximum height of stair without weather protection
9m zone of fire resisting construction below stair
Ground level or a roof or podium served by an independent stairway
See para 3.68
From the flat entrance door, a single escape route is acceptable in either of the following cases.
a. The flat is on a storey served by a single common stair and both of the following apply.
i. Every flat is separated from the common stair by a protected lobby or common protected corridor (see Diagram 3.7).
ii. The maximum travel distance in Table 3.1, for escape in one direction only, is not exceeded.
b. The flat is in a dead end of a common corridor served by two (or more) common stairs and the maximum travel distance given in Table 3.1, for escape in one direction only, is not exceeded (Diagram 3.8).
An escape route should not pass through one stair enclosure to reach another. It may pass through a protected lobby (minimum REI 30) of one stair to reach another.
A building should provide access to more than one common stair if it does not meet the criteria for a single common stair (see paragraph 3.26 and 3.27).
See para 3.21
NOTE: This only applies where at least one storey is more than 4.5m above ground level.
Fire doorset
Fire resisting stair enclosure(minimum REI 30)
Alternative exit
A stair of acceptable width for everyday use will be sufficient for escape purposes. If it is also a firefighting stair, it should be at least 1100mm wide. The width is the clear width between the walls or balustrades. Any handrails and strings intruding into that width by a maximum of 100mm on each side may be ignored.
Section 7 provides guidance on avoiding the spread of fire between storeys. For a stair that is also a firefighting stair, guidance in Section 15 should be followed.
Flats may be served by an external stair if the provisions in paragraphs 3.66 to 3.69 are followed.
Where a storey (or part of a building) is served by a single access stair, that stair may be external provided both of the following conditions are met.
a. The stair serves a floor not more than 6m above the ground level.
b. The stair meets the provisions in paragraph 3.62.
Any external escape stair should meet all of the following conditions (Diagram 3.11).
a. Doors to the stair should be fire resisting (minimum E 30) and be fitted with a self-closing device, except for a single exit door from the building to the top landing of a downward-leading external stair, provided it is the only door onto the landing.
b. Fire resisting construction (minimum RE 30) is required for the building envelope within the following zones, measured from the flights and landings of the external stair.
i. 1800mm above and horizontally.
ii. 9m vertically below.
iii. 1100mm above the top landing of the stair (except where the stair leads from basement to ground level).
c. Fire resisting construction (minimum RE 30) should be provided for any part of the building (including doors) within 1800mm of the escape route from the foot of the stair to a place of safety. This does not apply if there are alternative escape routes from the foot of the external escape stair.
d. Glazing in areas of fire resisting construction should be fixed shut and fire resisting (in terms of integrity but not insulation) (minimum E 30).
e. Stairs more than 6m in height above ground level (e.g. where they are provided above a podium) should be protected from adverse weather. Protection should prevent the build-up of snow or ice but does not require full enclosure.
If a building does not meet the criteria of paragraph 3.28, an escape stair forming part of the only escape route from an upper storey should not continue down to serve a basement storey. The basement storey should be served by a separate escape stair.
Where multiple escape stairs serve the upper storeys, only one needs to end at ground level. Other stairs may connect with the basement storeys if there is a protected lobby or a protected corridor between the stairs and accommodation at each basement level.
a. SMALL SINGLE STAIR BUILDING
*If smoke control is provided in the lobby, the travel distance can be increased to 7.5m maximum(see Diagram 3.7, example b).
b. SMALL SINGLE STAIR BUILDING WITH NO MORE THAN TWO FLATS PER STOREY
The door between stair and lobby should be free from security fastenings.
If the flats have protected entrance halls, the lobby between the common stair and flat entrance is not essential.
NOTES:
1. The arrangements shown also apply to the top storey.
2. If the travel distance across the lobby in diagram (a) exceeds 4.5m, Diagram 3.7 applies.
3. Where,in Diagram (b), the lobby between the common stair and the dwelling is omitted in smal lsingle stair buildings, an automatic opening vent with a free area of at least 1m2 is required at the top of the stair,which is operated automatically on detection of smoke at any storey in the stair.
4. For further guidance on the fire rating of the fire doorsets from the corridor to the flat and/or stairway refer to Appendix C, Table C1.
Fire resisting construction
Openable vent at high level for fire service use (1.0m2 minimum free area); see paragraph 3.28eSee para 3.28
Diagram 3.9
project budget
Paragraph 3.27 may be modified using the guidance in clause 7.3 of BS 9991.
protected circuit
See para 2.5
Alternative cavity barrier arrangements in roof space over protected stairway in a house with a storey more than 4.5m above ground level
Where a storey or part of a building has multiple escape routes available, one may be over a flat roof that complies with all of the following.
d. The route should be clearly defined and guarded by walls and/or protective barriers to protect against falling.
Ancillary accommodation should not be located in, or entered from, a protected lobby or protected corridor forming the only common escape route on that storey.
Escape stair lighting should be on a separate circuit from the electricity supply to any other part of the escape route.
To limit potential damage to cables in protected circuits, all of the following should apply.
a. Cables should be sufficiently robust.
b. Cable routes should be carefully selected and/or physically protected in areas where cables may be exposed to damage.
c. Methods of cable support should be class A1 rated and offer at least the same integrity as the cable. They should maintain circuit integrity and hold cables in place when exposed to fire.
A protected circuit to operate equipment during a fire should achieve all of the following.
a. Cables should achieve PH 30 classification when tested in accordance with BS EN 50200 (incorporating Annex E) or an equivalent standard.
b. It should only pass through parts of the building in which the fire risk is negligible.
c. It should be separate from any circuit provided for another purpose.
A protected stairway should not be used for anything else, except a lift well or electricity meters.
Every protected stairway should lead to a final exit, either directly or via a protected exit passageway. Any protected exit corridor or stair should have the same standard of fire resistance and lobby protection as the stair it serves.
protected corridor/lobby
See para 2.5
Fire resisting construction minimum REI 30
Fd Fire doorset minimum E 20
See para 2.5
Alternative cavity barrier arrangements in roof space over protected stairway in a house with a storey more than 4.5m above ground level
Fire resisting window(minimum RE30)
No fire resistance required for door
1100mm zone above top landing
6m max. height without weather protection
1800mm zone of fire resisting construction at side of stairway
Fire doorset(minimum E30)
See para 2.17
Configurations of stairs and external wall
Fire resisting construction
Fire resisting construction of adjacent building enclosure of protected stairway
Non-fire resisting construction
See para 3.63
No fire resistance required for door
1100mm zone above top landing
1100mm zone above top landing
6m maximum height of stair
Fire resisting window (minimum RE30)
1800mm zone of fire resisting construction at side of stair
Fire doorset (minimum E30)
Ground level or a roof or podium served by an independent stairway
6m maximum height of stair without weather protection
9m zone of fire resisting construction below stair
Ground level or a roof or podium served by an independent stairway
See para 3.68
Common corridors should be protected corridors. The wall between each flat and the corridor should be a compartment wall (minimum REI 30 where the top storey is up to 5m above ground level, otherwise REI 60).
Divide a common corridor connecting two or more storey exits with a fire doorset fitted with a self-closing device (minimum E 30 Sa). See Diagram 3.8. Associated screens should be fire resisting. Site doors so that smoke does not affect access to more than one stair.
A fire doorset (minimum E 30 Sa) fitted with a self-closing device (and fire resisting screen, where required) should separate the dead-end portion of a common corridor from the rest of the corridor (Diagrams 3.7a, 3.8b and 3.8c).
Ancillary accommodation should not be located in, or entered from, a protected lobby or protected corridor forming the only common escape route on that storey.
Despite the provisions described, it is probable that some smoke will get into the common corridor or lobby from a fire in a flat.
There should therefore be some means of ventilating the common corridors/lobbies to control smoke and so protect the common stairs. This means of ventilation offers additional protection to that provided by the fire doors to the stair, as well as some protection to the corridors/lobbies.
Ventilation can be natural (paragraphs 3.50 to 3.53) or mechanical (paragraph 3.54).
Refuse chutes and rooms for storing refuse should meet both of the following conditions.
a. Be separated from other parts of the building by fire resisting construction (minimum REI 30 in buildings with a top storey up to 5m above ground level; otherwise REI 60).
b. Not be situated within a protected stairway or protected lobby.
The approach to rooms containing refuse chutes or for storing refuse should comply with one of the following conditions.
a. Be directly from the open air.
b. Be through a protected lobby with a minimum of 0.2m2 of permanent ventilation.
Every common stair should be a protected stairway, within a fire resisting enclosure (minimum REI 30).
See paras 3.27 and 3.36
NOTES:
1. The arrangements shown also apply to the top storey.
2. See Diagram 3.9 for small single stair buildings.
3. All doors shown are fire doorsets.
4. Where travel distance is measured to a stair lobby, the lobby must not provide direct access to any storage room, flat or other space containing a potential fire hazard.
5. For further guidance on the fire rating of the fire doorsets from the corridor to the flat and/or stairway refer to Appendix C ,Table C1.
F Flat
Shaded areas indicate zones where ventilation should be provided in accordance with paragraphs 3.50 to 3.53(An external wall vent or smoke shaft located anywhere in the shaded area)
Where multiple escape stairs serve the upper storeys, only one needs to end at ground level. Other stairs may connect with the basement storeys if there is a protected lobby or a protected corridor between the stairs and accommodation at each basement level.
Where a common stair is not part of the only escape route from a flat, it may also serve ancillary accommodation from which it is separated by a protected lobby or protected corridor (minimum REI 30).
Where a stair serves an enclosed car park or place of special fire hazard, the lobby or corridor should have a minimum 0.4m2 of permanent ventilation or be protected from the ingress of smoke by a mechanical smoke control system.
NOTE: For refuse chutes and storage see paragraphs 3.55 to 3.58.
a. CORRIDOR ACCESS WITHOUT DEAD ENDS
b. CORRIDOR ACCESS WITH DEAD ENDS
The central door may be omitted if maximum travel distance is not more than 15m.
1. The arrangements shown also apply to the top storey.
2. For further guidance on the fire rating of the fire doorsets from the corridor to the flat and/or stairway refer to Appendix C ,Table C1.
Fire doorset provided in accordance with paragraphs 3.50 to 3.53(An external wall vent or smoke shaft located anywhere in the shaded area)
See paras 3.27 and 3.36
Every protected stairway should lead to a final exit, either directly or via a protected exit passageway. Any protected exit corridor or stair should have the same standard of fire resistance and lobby protection as the stair it serves.
a. SMALL SINGLE STAIR BUILDING
*If smoke control is provided in the lobby, the travel distance can be increased to 7.5m maximum(see Diagram 3.7, example b).
b. SMALL SINGLE STAIR BUILDING WITH NO MORE THAN TWO FLATS PER STOREY
The door between stair and lobby should be free from security fastenings.
If the flats have protected entrance halls, the lobby between the common stair and flat entrance is not essential.
NOTES:
1. The arrangements shown also apply to the top storey.
2. If the travel distance across the lobby in diagram (a) exceeds 4.5m, Diagram 3.7 applies.
3. Where,in Diagram (b), the lobby between the common stair and the dwelling is omitted in smal lsingle stair buildings, an automatic opening vent with a free area of at least 1m2 is required at the top of the stair,which is operated automatically on detection of smoke at any storey in the stair.
4. For further guidance on the fire rating of the fire doorsets from the corridor to the flat and/or stairway refer to Appendix C, Table C1.
Fire resisting construction
Openable vent at high level for fire service use (1.0m2 minimum free area); see paragraph 3.28eSee para 3.28
Diagram 3.9
protected entrance hall/landing
See para 2.5
Alternative cavity barrier arrangements in roof space over protected stairway in a house with a storey more than 4.5m above ground level
Fire resisting window(minimum RE30)
No fire resistance required for door
1100mm zone above top landing
6m max. height without weather protection
1800mm zone of fire resisting construction at side of stairway
Fire doorset(minimum E30)
See para 2.17
Configurations of stairs and external wall
Fire resisting construction
Fire resisting construction of adjacent building enclosure of protected stairway
Non-fire resisting construction
See para 3.63
The internal arrangement of single storey or multi-storey flats should comply with paragraphs 3.15 to 3.17. Alternatively, the guidance in paragraphs 3.18 to 3.22 may be followed.
A flat accessed via the common parts of the building should also comply with the provisions for small single stair buildings in paragraph 3.28 and Diagram 3.9. A protected entrance hall may be required as a result.
Where access from any habitable room to the entrance hall or flat entrance is impossible without passing through another room, all of the following conditions should be met (Diagram 3.4).
a. Bedrooms should be separated from living accommodation by fire resisting construction (minimum REI 30) and fire doorsets (minimum E 20).
b. The alternative exit should be in the part of the flat that contains the bedrooms.
See para 3.18
Flat entrance
Kitchen area
Bath
protected shaft
A passenger lift serving any storey more than 4.5m above ground level should be in either of the following.
a. The enclosure to the protected stairway, as described in paragraph 2.5.
b. A fire resisting lift shaft (minimum REI 30).
Configurations of stairs and external wall
Fire resisting construction
Fire resisting construction of adjacent building enclosure of protected stairway
Non-fire resisting construction
See para 3.63
The following paragraphs deal with means of escape from the entrance doors of flats to a final exit. They do not apply to flats with a top storey that is a maximum of 4.5m above ground level (designed in accordance with paragraphs 3.16 and 3.17).
Reference should also be made to the following.
a. Requirement B3 regarding compartment walls and protected shafts.
b. Requirement B5 regarding access for the fire and rescue service.
An escape route should not pass through one stair enclosure to reach another. It may pass through a protected lobby (minimum REI 30) of one stair to reach another.
Smoke vents should comply with one of the following.
a. They should be located on an external wall with minimum free area of 1.5m2.
b. They should discharge into a vertical smoke shaft, closed at the base, that meets all of the following criteria.
i. The shaft should conform to the following conditions.
• Have a minimum cross-sectional area of 1.5m2 (minimum dimension 0.85m in any direction).
• Open at roof level, minimum 0.5m above any surrounding structures within 2m of it horizontally.
• Extend a minimum of 2.5m above the ceiling of the highest storey served by the shaft.
ii. The free area of all the following vents should be a minimum of 1m2 in the following places.
• From the corridor or lobby into the shaft.
• At the opening at the head of the shaft.
• At all internal locations within the shaft (e.g. safety grilles).
iii. The smoke shaft should be constructed from a class A1 material. All vents should either be a fire doorset (see Appendix C, Table C1, item 2.e for minimum fire resistance) or fitted with a smoke control damper achieving the same period of fire resistance and designed to operate as described below. The shaft should be vertical from base to head, with a maximum of 4m at a maximum inclined angle of 30 degrees.
iv. If smoke is detected in the common corridor or lobby, both of the following should occur.
• Simultaneous opening of vents on the storey where the fire is located, at the top of the smoke shaft and to the stair.
• Vents from the corridors or lobbies on all other storeys should remain closed, even if smoke is subsequently detected on storeys other than where the fire is located.
protected stairway
Where new habitable rooms are provided, a fire detection and alarm system should be installed
where either of the following applies.
a. The room is provided above or below the ground storey.
b. The room is provided at the ground storey, without a final exit.
See Diagram 2.1a. All habitable rooms (excluding kitchens) should have either of the following.
a. An opening directly onto a hall leading to a final exit.
b. An emergency escape window or door, as described in paragraph 2.10.
Basement storeys containing habitable rooms should have one of the following.
a. An emergency escape window or external door providing escape from the basement (paragraph 2.10).
b. A protected stairway (paragraph 2.5a) leading from the basement to a final exit.
Any external escape stair should meet all of the following conditions (Diagram 2.7).
a. Doors to the stair should be fire resisting (minimum E 30), except for a single exit door from the building to the top landing of a downward-leading external stair.
b. Fire resisting construction (minimum RE 30) is required for the building envelope within the following zones, measured from the flights and landings of the external stair.
i. 1800mm horizontally.
ii. 9m vertically below.
iii. 1100mm above the top landing of the stair (except where the stair leads from basement to ground level).
c. Fire resisting construction (minimum RE 30) should be provided for any part of the building (including doors) within 1800mm of the escape route from the foot of the stair to a place of safety. This does not apply if there are alternative escape routes from the foot of the external escape stair.
d. Stairs more than 6m in height should be protected from adverse weather. Protection should prevent the build-up of snow or ice but does not require full enclosure.
e. Glazing in areas of fire resisting construction should be fixed shut and fire resisting (in terms of integrity, but not insulation) (minimum E 30).
See para 2.5
Fire resisting construction minimum REI 30
Fd Fire doorset minimum E 20
See para 2.5
Alternative cavity barrier arrangements in roof space over protected stairway in a house with a storey more than 4.5m above ground level
Dwellinghouses with one internal stair should comply with paragraphs 2.5 and 2.6. In dwellinghouses with more than one stair, the stairs should provide effective alternative means of escape. The stairs should be physically separated by either of the following.
a. Fire resisting construction (minimum REI 30).
b. More than one room.
See Diagram 2.1c. The dwellinghouse should have either of the following. Cavity barriers or a fire resisting ceiling (minimum EI 30) should be provided above a protected stairway enclosure (Diagram 2.3). b. Alternative escape route – a top storey separated from lower storeys by fire resisting construction (minimum REI 30) and with an alternative escape route leading to its own final exit.
a. Protected stairway – a stair separated by fire resisting construction (minimum REI 30) at all storeys, that complies with one of the following.
i. Extends to a final exit (Diagram 2.2a).
ii. Gives access to a minimum of two ground level final exits that are separated from each other by fire resisting construction (minimum REI 30) and fire doorsets (minimum E 20) (Diagram 2.2b).
NOTES:
1. This diagram does not apply where the gallery is provided with one of the following:
i. An alternative escape route
ii. An emergency escape window (where the gallery floor is not more than 4.5m above ground level).
2. Any cooking facilities within a room containing a gallery should comply with one of the following conditions:
i. Be enclosed with fire resisting construction
ii. Be remote from the stair to the gallery and positioned such that they do not prejudice escape from the gallery.
See para 2.15
All of the following precautions should be taken to avoid the spread of smoke and fire to the protected stairway.
a. Transfer grilles should not be fitted in any wall, door, floor or ceiling of the stair enclosure.
b. Any duct passing through the stair enclosure should be rigid steel. Joints between the ductwork and stair enclosure should be fire-stopped.
c. Ventilation ducts supplying or extracting air directly to or from a protected stairway should not serve other areas as well.
d. Any system of mechanical ventilation which recirculates air and which serves both the stair and other areas should be designed to shut down on the detection of smoke within the system.
e. For ducted warm air heating systems, a room thermostat should be sited in the living room. It should be mounted at a height between 1370mm and 1830mm above the floor. The maximum setting should be 27°C.
NOTE: Ventilation ducts passing through compartment walls should comply with the guidance in Section 9.
Configurations of stairs and external wall
Fire resisting construction
Fire resisting construction of adjacent building enclosure of protected stairway
Non-fire resisting construction
See para 3.63
No fire resistance required for door
1100mm zone above top landing
1100mm zone above top landing
6m maximum height of stair
Fire resisting window (minimum RE30)
1800mm zone of fire resisting construction at side of stair
Fire doorset (minimum E30)
Ground level or a roof or podium served by an independent stairway
6m maximum height of stair without weather protection
9m zone of fire resisting construction below stair
Ground level or a roof or podium served by an independent stairway
See para 3.68
All habitable rooms (excluding kitchens) should have either of the following.
a. An opening directly onto a hall leading to a final exit.
b. An emergency escape window or door, as described in paragraph 3.6.
All habitable rooms (excluding kitchens) should have either of the following.
a. An emergency escape window or external door, as described in paragraph 3.6.
b. In multi-storey flats, direct access to a protected internal stairway (minimum REI 30) leading to an exit from the flat.
Any alternative exit from a flat should comply with all of the following.
a. It should be remote from the main entrance door to the flat.
b. It should lead to a final exit, via a common stair if necessary, through one of the following.
i. A door to an access corridor, access lobby or common balcony.
ii. An internal private stair leading to an access corridor, access lobby or common balcony at another level.
iii. A door to a common stair.
iv. A door to an external stair.
v. A door to an escape route over a flat roof.
Any access route leading to a final exit or common stair should comply with the provisions for means of escape in the common parts of a flat (see paragraph 3.25).
The following paragraphs deal with means of escape from the entrance doors of flats to a final exit. They do not apply to flats with a top storey that is a maximum of 4.5m above ground level (designed in accordance with paragraphs 3.16 and 3.17).
Reference should also be made to the following.
a. Requirement B3 regarding compartment walls and protected shafts.
b. Requirement B5 regarding access for the fire and rescue service.
The following paragraphs deal with means of escape from the entrance doors of flats to a final exit.
Divide a common corridor connecting two or more storey exits with a fire doorset fitted with a self-closing device (minimum E 30 Sa). See Diagram 3.8. Associated screens should be fire resisting. Site doors so that smoke does not affect access to more than one stair.
See para 3.19
NOTE: The bedrooms are not classified as inner rooms because escape is possible in two directions.
Fire doorset
Fire resisting construction (minimum REI 30) between living and bedroom accommodation
Alternative exit
Every doorway or other exit providing access to a means of escape, other than exits in ordinary use (e.g. main entrances), should be distinctively and conspicuously marked by an exit sign in accordance with BS ISO 3864-1 and BS 5499-4. For this reason, blocks of flats with a single stair in regular use would not usually require any fire exit signage.
Advice on fire safety signs, including emergency escape signs, is given in the HSE publication Safety Signs and Signals: Guidance on Regulations.
Some buildings may require additional signs to comply with other legislation.
Access openings to refuse storage chambers should not be sited in the following areas.
a. Next to escape routes or final exits.
b. Near the windows of flats.
See para 3.21
NOTE: This only applies where at least one storey is more than 4.5m above ground level.
Fire doorset
Fire resisting stair enclosure(minimum REI 30)
Alternative exit
Every common stair should be a protected stairway, within a fire resisting enclosure (minimum REI 30).
Any external escape stair should meet all of the following conditions (Diagram 3.11).
a. Doors to the stair should be fire resisting (minimum E 30) and be fitted with a self-closing device, except for a single exit door from the building to the top landing of a downward-leading external stair, provided it is the only door onto the landing.
b. Fire resisting construction (minimum RE 30) is required for the building envelope within the following zones, measured from the flights and landings of the external stair.
i. 1800mm above and horizontally.
ii. 9m vertically below.
iii. 1100mm above the top landing of the stair (except where the stair leads from basement to ground level).
c. Fire resisting construction (minimum RE 30) should be provided for any part of the building (including doors) within 1800mm of the escape route from the foot of the stair to a place of safety. This does not apply if there are alternative escape routes from the foot of the external escape stair.
d. Glazing in areas of fire resisting construction should be fixed shut and fire resisting (in terms of integrity but not insulation) (minimum E 30).
e. Stairs more than 6m in height above ground level (e.g. where they are provided above a podium) should be protected from adverse weather. Protection should prevent the build-up of snow or ice but does not require full enclosure.
The construction separating two adjacent protected stairways (or exit passageways leading to different final exits) should be imperforate.
Where a stair serves an enclosed car park or place of special fire hazard, the lobby or corridor should have a minimum 0.4m2 of permanent ventilation or be protected from the ingress of smoke by a mechanical smoke control system.
NOTE: For refuse chutes and storage see paragraphs 3.55 to 3.58.
Every protected stairway should lead to a final exit, either directly or via a protected exit passageway. Any protected exit corridor or stair should have the same standard of fire resistance and lobby protection as the stair it serves.
Basement storeys containing habitable rooms should have one of the following.
a. An emergency escape window or external door providing escape from the basement (see paragraph 3.6).
b. A protected stairway (minimum REI 30) leading from the basement to a final exit.
a. SMALL SINGLE STAIR BUILDING
*If smoke control is provided in the lobby, the travel distance can be increased to 7.5m maximum(see Diagram 3.7, example b).
b. SMALL SINGLE STAIR BUILDING WITH NO MORE THAN TWO FLATS PER STOREY
The door between stair and lobby should be free from security fastenings.
If the flats have protected entrance halls, the lobby between the common stair and flat entrance is not essential.
NOTES:
1. The arrangements shown also apply to the top storey.
2. If the travel distance across the lobby in diagram (a) exceeds 4.5m, Diagram 3.7 applies.
3. Where,in Diagram (b), the lobby between the common stair and the dwelling is omitted in smal lsingle stair buildings, an automatic opening vent with a free area of at least 1m2 is required at the top of the stair,which is operated automatically on detection of smoke at any storey in the stair.
4. For further guidance on the fire rating of the fire doorsets from the corridor to the flat and/or stairway refer to Appendix C, Table C1.
Fire resisting construction
Openable vent at high level for fire service use (1.0m2 minimum free area); see paragraph 3.28eSee para 3.28
Diagram 3.9
proven
Refuse storage chambers, refuse chutes and refuse hoppers should be sited and constructed in accordance with BS 5906.
purpose group
These provisions do not apply to the following.
a. The common parts of a sheltered housing development, such as communal lounges.
b. Sheltered accommodation in the 'residential (institutional)' or 'residential (other)' purpose groups (purpose group 2(a) or 2(b)).
In these parts, means of warning should follow the guidance for buildings other than dwellings in Volume 2 of Approved Document B.
Escape route travel distances should comply with Table 3.1.
A protected circuit to operate equipment during a fire should achieve all of the following.
a. Cables should achieve PH 30 classification when tested in accordance with BS EN 50200 (incorporating Annex E) or an equivalent standard.
b. It should only pass through parts of the building in which the fire risk is negligible.
c. It should be separate from any circuit provided for another purpose.
In mixed use buildings, separate means of escape should be provided from any storeys or parts of storeys used for the ‘residential’ or ‘assembly and recreation’ purpose groups (purpose groups 1, 2 and 5), other than in the case of certain small buildings or buildings in which the residential accommodation is ancillary (see paragraphs 3.76 and 3.77)
purpose-provided ventilation
Despite the provisions described, it is probable that some smoke will get into the common corridor or lobby from a fire in a flat.
There should therefore be some means of ventilating the common corridors/lobbies to control smoke and so protect the common stairs. This means of ventilation offers additional protection to that provided by the fire doors to the stair, as well as some protection to the corridors/lobbies.
Ventilation can be natural (paragraphs 3.50 to 3.53) or mechanical (paragraph 3.54).
The approach to rooms containing refuse chutes or for storing refuse should comply with one of the following conditions.
a. Be directly from the open air.
b. Be through a protected lobby with a minimum of 0.2m2 of permanent ventilation.
Where a stair serves an enclosed car park or place of special fire hazard, the lobby or corridor should have a minimum 0.4m2 of permanent ventilation or be protected from the ingress of smoke by a mechanical smoke control system.
NOTE: For refuse chutes and storage see paragraphs 3.55 to 3.58.
ramped
Escape route floor finishes should minimise their slipperiness when wet. Finishes include the treads of steps and surfaces of ramps and landings.
regulation 7 - materials and workmanship
In the Secretary of State’s view, requirement B1 is met by achieving all of the following.
a. There are sufficient means for giving early warning of fire to people in the building.
b. All people can escape to a place of safety without external assistance.
c. Escape routes are suitably located, sufficient in number and of adequate capacity.
d. Where necessary, escape routes are sufficiently protected from the effects of fire and smoke.
e. Escape routes are adequately lit and exits are suitably signed.
f. There are appropriate provisions to limit the ingress of smoke to the escape routes, or to
restrict the spread of fire and remove smoke.
g. For buildings containing flats, there are appropriate provisions to support a stay put evacuation
strategy.
The extent to which any of these measures are necessary is dependent on the use of the building,
its size and its height.
Building work and material changes of use subject to requirement B1 include both new and existing
buildings.
resistance to the passage of sound 2003 edition incorporating 2004 2010 2013 and 2015 amendments
Guidance on cables for large and complex buildings is given in BS 5839-1, BS 5266-1 and BS 8519.
rise
For some low rise buildings, the provisions in paragraphs 3.26 and 3.27 may be modified and the use of a single stair, protected in accordance with Diagram 3.9, may be permitted where all of the following apply.
a. The top storey of the building is a maximum of 11m above ground level.
b. No more than three storeys are above the ground storey.
c. The stair does not connect to a covered car park, unless the car park is open sided (as defined in Section 11 of Approved Document B Volume 2).
d. The stair does not serve offices, stores or other ancillary accommodation. If it does, they should be separated from the stair by a protected lobby or protected corridor (minimum REI 30) with a minimum 0.4m2 of permanent ventilation, or be protected from the ingress of smoke by a mechanical smoke control system.
NOTE: For refuse chutes and storage see paragraphs 3.55 to 3.58.
e. Either of the following is provided for the fire and rescue service.
i. A high-level openable vent with a free area of at least 1m2 at each storey.
ii. A single openable vent with a free area of at least 1m2 at the head of the stair, operable remotely at the fire and rescue service access level.
Escape route floor finishes should minimise their slipperiness when wet. Finishes include the treads of steps and surfaces of ramps and landings.
Paragraphs 3.6 to 3.23 deal with the means of escape within each flat. Paragraphs 3.25 to 3.89 deal with the means of escape in common areas of the building (including mixed use buildings in paragraphs 3.76 and 3.77). Guidance for live/work units is given in paragraph 3.24.
roof
Access to an external escape stair may be via a flat roof, provided the flat roof meets the requirements of paragraph 3.30.
rooflight
Escape lighting should conform to BS 5266-1.
room
Smoke alarms should be provided in the circulation spaces of the dwelling in accordance with
paragraphs 1.1 to 1.4.
NOTE: This does not apply where inner rooms are provided (see paragraph 2.11 for inner room
requirements).
room for residential purposes
These provisions do not apply to the following.
a. The common parts of a sheltered housing development, such as communal lounges.
b. Sheltered accommodation in the 'residential (institutional)' or 'residential (other)' purpose groups (purpose group 2(a) or 2(b)).
In these parts, means of warning should follow the guidance for buildings other than dwellings in Volume 2 of Approved Document B.
Smoke alarms should be provided in the circulation spaces of the dwelling in accordance with
paragraphs 1.1 to 1.4.
NOTE: This does not apply where inner rooms are provided (see paragraph 2.11 for inner room
requirements).
An inner room is permitted when it is one of the following.
a. A kitchen.
b. A laundry or utility room.
c. A dressing room.
d. A bathroom, WC or shower room.
e. Any room on a storey that is a maximum of 4.5m above ground level which is provided with an emergency escape window as described in paragraph 2.10.
f. A gallery that complies with paragraph 2.15.
A room accessed only via an inner room (an inner inner room) is acceptable when all of the following apply.
a. It complies with paragraph 2.11.
b. The access rooms each have a smoke alarm (see Section 1).
c. None of the access rooms is a kitchen.
In addition, escape lighting should be provided to all of the following.
a. Toilet accommodation with a minimum floor area of 8m2.
b. Electricity and generator rooms.
c. Switch room/battery room for emergency lighting system.
d. Emergency control rooms.
In mixed use buildings, separate means of escape should be provided from any storeys or parts of storeys used for the ‘residential’ or ‘assembly and recreation’ purpose groups (purpose groups 1, 2 and 5), other than in the case of certain small buildings or buildings in which the residential accommodation is ancillary (see paragraphs 3.76 and 3.77)
An inner room is permitted when it is one of the following.
a. A kitchen.
b. A laundry or utility room.
c. A dressing room.
d. A bathroom, WC or shower room.
e. Any room on a storey that is a maximum of 4.5m above ground level which is provided with an emergency escape window as described in paragraph 3.6.
f. A gallery that complies with paragraph 3.13.
A room accessed only via an inner room (an inner inner room) is acceptable when all of the following apply.
a. It complies with paragraph 3.7.
b. The access rooms each have a smoke alarm (see Section 1).
c. None of the access rooms is a kitchen.
room-sealed appliance
Air circulation systems which circulate air within an individual dwellinghouse with a floor more than
4.5m above ground level should meet the guidance given in paragraph 2.9.
All of the following precautions should be taken to avoid the spread of smoke and fire to the protected stairway.
a. Transfer grilles should not be fitted in any wall, door, floor or ceiling of the stair enclosure.
b. Any duct passing through the stair enclosure should be rigid steel. Joints between the ductwork and stair enclosure should be fire-stopped.
c. Ventilation ducts supplying or extracting air directly to or from a protected stairway should not serve other areas as well.
d. Any system of mechanical ventilation which recirculates air and which serves both the stair and other areas should be designed to shut down on the detection of smoke within the system.
e. For ducted warm air heating systems, a room thermostat should be sited in the living room. It should be mounted at a height between 1370mm and 1830mm above the floor. The maximum setting should be 27°C.
NOTE: Ventilation ducts passing through compartment walls should comply with the guidance in Section 9.
For systems circulating air only within an individual flat, take all of the following precautions.
a. Transfer grilles should not be fitted in any wall, door, floor or ceiling of the enclosure.
b. Any duct passing through the enclosure should be rigid steel. Joints between the ductwork and enclosure should be fire-stopped.
c. Ventilation ducts serving the enclosure should not serve any other areas.
d. Any system of mechanical ventilation which recirculates air and which serves both the stair and other areas should be designed to shut down on the detection of smoke within the system.
e. For ducted warm air heating systems, a room thermostat should be sited in the living room. It should be mounted at a height between 1370mm and 1830mm above the floor. The maximum setting should be 27°C.
NOTE: Ventilation ducts passing through compartment walls should comply with the guidance in Section 9.
A vent to the outside with a minimum free area of 1m2 should be provided from the top storey of the stair.
In single stair buildings, smoke vents on the storey where the fire is initiated, and the vent at the head of the stair, should be activated by smoke detectors in the common parts.
In buildings with more than one stair, smoke vents may be activated manually. The control system should open the vent at the head of the stair before, or at the same time as, the vent on the storey where the fire is located. Smoke detection is not required for ventilation purposes in this instance.
The approach to rooms containing refuse chutes or for storing refuse should comply with one of the following conditions.
a. Be directly from the open air.
b. Be through a protected lobby with a minimum of 0.2m2 of permanent ventilation.
sanitary accommodation
Air circulation systems which circulate air within an individual dwellinghouse with a floor more than
4.5m above ground level should meet the guidance given in paragraph 2.9.
sanitation hot water safety and water efficiency 2015 edition with 2016 amendments
A balcony or flat roof intended to form part of an escape route should be provided with guarding etc. in accordance with Approved Document K.
A balcony or flat roof intended to form part of an escape route should be provided with guarding etc. in accordance with Approved Document K.
schedule
Work should comply with Parts K and L of Schedule 1 to the Building Regulations. When complete, the building should comply with other applicable parts of Schedule 1 to at least the same level as before.
section
Means of warning and escape
B1.The building shall be designed and constructed so that there are appropriate provisions for the early warning of fire, and appropriate means of escape in case of fire from the building to a place of safety outside the building capable of being safely and effectively used at all material times.
Requirement B1 does not apply to any prison provided under section 33 of the Prison Act 1952
(a) (power to provide prisons, etc.).
(a) 1952 c. 52; section 33 was amended by section 100 of the Criminal Justice and Public Order Act 1994 (c. 33) and by S.I. 1963/597.
If windows are replaced, it may be necessary to provide cavity barriers around the opening in accordance with Section 5.
Section 7 provides guidance on avoiding the spread of fire between storeys. For a stair that is also a firefighting stair, guidance in Section 15 should be followed.
If a loadbearing wall is any of the following, guidance in other sections may also apply.
a. A compartment wall (including a wall common to two buildings): Section 7.
b. Enclosing a place of special fire hazard: Section 7.
c. Protecting a means of escape: Sections 2 and 3.
d. An external wall: Sections 10 and 11.
e. Enclosing a firefighting shaft: Section 15.
In a converted building with a maximum of three storeys, a minimum REI 30 fire resistance could be accepted for elements of structure if the means of escape conform to the provisions of Section 3.
secure window
Windows or external doors providing emergency escape should comply with all of the following.
a. Windows should have an unobstructed openable area that complies with all of the following.
i. A minimum area of 0.33m2.
ii. A minimum height of 450mm and a minimum width of 450mm (the route through the window may be at an angle rather than straight through).
iii. The bottom of the openable area is a maximum of 1100mm above the floor.
b. People escaping should be able to reach a place free from danger from fire. Courtyards or inaccessible back gardens should comply with Diagram 2.5.
c. Locks (with or without removable keys) and opening stays (with child-resistant release catches) may be fitted to escape windows.
d. Windows should be capable of remaining open without being held.
Where an existing window would be an escape window in a new dwellinghouse, and is big enough to be used for escape purposes, then the replacement should comply with one of the following.
a. The replacement window should be sized to provide at least the same potential for escape.
b. If the existing window was larger than required for escape purposes, the opening can be reduced to the minimum described in paragraph 2.10.
If windows are replaced, it may be necessary to provide cavity barriers around the opening in accordance with Section 5.
Windows or external doors providing emergency escape should comply with all of the following.
a. Windows should have an unobstructed openable area that complies with all of the following.
i. A minimum area of 0.33m2.
ii. A minimum height of 450mm and a minimum width of 450mm (the route through the window may be at an angle rather than straight through).
iii. The bottom of the openable area is a maximum of 1100mm above the floor.
b. People escaping should be able to reach a place free from danger from fire.
c. Locks (with or without removable keys) and opening stays (with child-resistant release catches) may be fitted to escape windows.
d. Windows should be capable of remaining open without being held.
self-closing device
Divide a common corridor connecting two or more storey exits with a fire doorset fitted with a self-closing device (minimum E 30 Sa). See Diagram 3.8. Associated screens should be fire resisting. Site doors so that smoke does not affect access to more than one stair.
Escape routes should have a minimum clear headroom of 2m. The only projections allowed below this height are door frames.
separated part
Fire detection and alarm systems sometimes trigger other systems. The interface between systems
must be reliable. Particular care should be taken if the interface is facilitated via another system.
Where any part of BS 7273 applies to the triggering of other systems, the recommendations of that
part of BS 7273 should be followed.
Work should comply with Parts K and L of Schedule 1 to the Building Regulations. When complete, the building should comply with other applicable parts of Schedule 1 to at least the same level as before.
Separate guidance applies to means of escape within the flat and within the common parts of the building that lead to a place of safety. Flats at ground level are treated similarly to dwellinghouses. With increasing height, more complex provisions are needed.
In mixed use buildings, separate means of escape should be provided from any storeys or parts of storeys used for the ‘residential’ or ‘assembly and recreation’ purpose groups (purpose groups 1, 2 and 5), other than in the case of certain small buildings or buildings in which the residential accommodation is ancillary (see paragraphs 3.76 and 3.77)
Refuse chutes and rooms for storing refuse should meet both of the following conditions.
a. Be separated from other parts of the building by fire resisting construction (minimum REI 30 in buildings with a top storey up to 5m above ground level; otherwise REI 60).
b. Not be situated within a protected stairway or protected lobby.
With some configurations of external wall, a fire in one part of a building could subject the external wall of a protected stairway to heat (for example, where the two are adjacent at an internal angle in the façade, as shown in Diagram 3.10).
In buildings with more than three storeys above the ground storey, stairs may serve the flats and other occupancies if all of the following apply.
a. The flat is ancillary to the main use of the building.
b. The flat has an independent alternative escape route.
c. The stair is separated from occupancies on lower storeys by a protected lobby (minimum REI 30) at each of those storeys.
d. The stair enclosure has at least the same standard of fire resistance as the structural elements of the building (see Appendix B, Table B4); if the stair is a firefighting stair, it should comply with the provisions in Section 15 (see also paragraph 3.60).
e. Any automatic fire detection and alarm system fitted in the main part of the building also covers all flats.
f. Any security measures in any parts of the building do not prevent escape at all material times.
separating floor
In mixed use buildings, separate means of escape should be provided from any storeys or parts of storeys used for the ‘residential’ or ‘assembly and recreation’ purpose groups (purpose groups 1, 2 and 5), other than in the case of certain small buildings or buildings in which the residential accommodation is ancillary (see paragraphs 3.76 and 3.77)
separating wall
In mixed use buildings, separate means of escape should be provided from any storeys or parts of storeys used for the ‘residential’ or ‘assembly and recreation’ purpose groups (purpose groups 1, 2 and 5), other than in the case of certain small buildings or buildings in which the residential accommodation is ancillary (see paragraphs 3.76 and 3.77)
sheltered housing
These provisions do not apply to the following.
a. The common parts of a sheltered housing development, such as communal lounges.
b. Sheltered accommodation in the 'residential (institutional)' or 'residential (other)' purpose groups (purpose group 2(a) or 2(b)).
In these parts, means of warning should follow the guidance for buildings other than dwellings in Volume 2 of Approved Document B.
should
Smoke alarms should be mains operated and conform to BS EN 14604.
Heat alarms should be mains operated and conform to BS 5446-2.
Windows or external doors providing emergency escape should comply with all of the following.
a. Windows should have an unobstructed openable area that complies with all of the following.
i. A minimum area of 0.33m2.
ii. A minimum height of 450mm and a minimum width of 450mm (the route through the window may be at an angle rather than straight through).
iii. The bottom of the openable area is a maximum of 1100mm above the floor.
b. People escaping should be able to reach a place free from danger from fire. Courtyards or inaccessible back gardens should comply with Diagram 2.5.
c. Locks (with or without removable keys) and opening stays (with child-resistant release catches) may be fitted to escape windows.
d. Windows should be capable of remaining open without being held.
A gallery should comply with one of the following.
a. It should be provided with an alternative exit.
b. It should be provided with an emergency escape window, as described in paragraph 2.10, where the gallery floor is a maximum of 4.5m above ground level.
c. It should meet all the conditions shown in Diagram 2.6.
Work should comply with Parts K and L of Schedule 1 to the Building Regulations. When complete, the building should comply with other applicable parts of Schedule 1 to at least the same level as before.
Where a new storey is added through conversion to create a storey above 4.5m, both of the following should apply.
a. The full extent of the escape route should be addressed.
b. Fire resisting doors (minimum E 20) and partitions (minimum REI 30) should be provided, including upgrading the existing doors where necessary.
NOTE: Where the layout is open plan, new partitions should be provided to enclose the escape route (Diagram 2.2).
All of the following precautions should be taken to avoid the spread of smoke and fire to the protected stairway.
a. Transfer grilles should not be fitted in any wall, door, floor or ceiling of the stair enclosure.
b. Any duct passing through the stair enclosure should be rigid steel. Joints between the ductwork and stair enclosure should be fire-stopped.
c. Ventilation ducts supplying or extracting air directly to or from a protected stairway should not serve other areas as well.
d. Any system of mechanical ventilation which recirculates air and which serves both the stair and other areas should be designed to shut down on the detection of smoke within the system.
e. For ducted warm air heating systems, a room thermostat should be sited in the living room. It should be mounted at a height between 1370mm and 1830mm above the floor. The maximum setting should be 27°C.
NOTE: Ventilation ducts passing through compartment walls should comply with the guidance in Section 9.
A gallery should comply with one of the following.
a. It should be provided with an alternative exit.
b. It should be provided with an emergency escape window, as described in paragraph 3.6, where the gallery floor is a maximum of 4.5m above ground level.
c. It should meet the conditions shown in Diagram 3.1.
For systems circulating air only within an individual flat, take all of the following precautions.
a. Transfer grilles should not be fitted in any wall, door, floor or ceiling of the enclosure.
b. Any duct passing through the enclosure should be rigid steel. Joints between the ductwork and enclosure should be fire-stopped.
c. Ventilation ducts serving the enclosure should not serve any other areas.
d. Any system of mechanical ventilation which recirculates air and which serves both the stair and other areas should be designed to shut down on the detection of smoke within the system.
e. For ducted warm air heating systems, a room thermostat should be sited in the living room. It should be mounted at a height between 1370mm and 1830mm above the floor. The maximum setting should be 27°C.
NOTE: Ventilation ducts passing through compartment walls should comply with the guidance in Section 9.
Escape route travel distances should comply with Table 3.1.
A ramp forming part of an escape route should meet the provisions in Approved Document M. Any sloping floor or tier should have a pitch of not more than 35 degrees to the horizontal.
Escape lighting should conform to BS 5266-1.
To limit potential damage to cables in protected circuits, all of the following should apply.
a. Cables should be sufficiently robust.
b. Cable routes should be carefully selected and/or physically protected in areas where cables may be exposed to damage.
c. Methods of cable support should be class A1 rated and offer at least the same integrity as the cable. They should maintain circuit integrity and hold cables in place when exposed to fire.
A protected circuit to operate equipment during a fire should achieve all of the following.
a. Cables should achieve PH 30 classification when tested in accordance with BS EN 50200 (incorporating Annex E) or an equivalent standard.
b. It should only pass through parts of the building in which the fire risk is negligible.
c. It should be separate from any circuit provided for another purpose.
Except in buildings that comply with Diagram 3.9, the corridor or lobby next to each stair should have a smoke vent. The location of the vent should comply with both of the following.
a. Be as high as practicable.
b. Be positioned so the top edge is at least as high as the top of the door to the stair.
Refuse storage chambers, refuse chutes and refuse hoppers should be sited and constructed in accordance with BS 5906.
A protected stairway should not be used for anything else, except a lift well or electricity meters.
In single stair buildings, electricity meters should be in securely locked cupboards. Cupboards should be separated from the escape route by fire resisting construction.
simple payback
A protected circuit to operate equipment during a fire should achieve all of the following.
a. Cables should achieve PH 30 classification when tested in accordance with BS EN 50200 (incorporating Annex E) or an equivalent standard.
b. It should only pass through parts of the building in which the fire risk is negligible.
c. It should be separate from any circuit provided for another purpose.
single storey
A large dwellinghouse has more than one storey, and at least one storey exceeds 200m2.
A large dwellinghouse of two storeys (excluding basement storeys) should be fitted with a Grade A
Category LD3 fire detection and alarm system, as described in BS 5839-6.
A large dwellinghouse of three or more storeys (excluding basement storeys) should be fitted with
a Grade A Category LD2 fire detection and alarm system as described in BS 5839-6.
Where new habitable rooms are provided, a fire detection and alarm system should be installed
where either of the following applies.
a. The room is provided above or below the ground storey.
b. The room is provided at the ground storey, without a final exit.
See paras 2.1 to 2.6
Single storey dwellinghouse(see paragraph 2.1)
Dwellinghouse with one storey more than 4.5m above ground level(see paragraph 2.5)
Dwellinghouse with two or more storeys more than 4.5m above ground level(see paragraph 2.6)
An alternative approach to that described in paragraph 2.21 would be to comply with all of the following.
a. Provide sprinkler protection to the open-plan areas.
b. Provide a fire resisting partition (minimum REI 30) and door (minimum E 20) to separate the ground storey from the upper storeys. The door should allow occupants of the loft room access to a first storey escape window.
c. Separate cooking facilities from the open-plan area with fire resisting construction (minimum REI 30).
See para 2.6
Example of alternative exit in para 2.6(a) (see definition in Appendix A)
Where escape from a dwellinghouse is to an enclosed space with exit only possible through other buildings (e.g. a courtyard or back garden), the length of the space should exceed whichever is the greater of the following.
a. The height of the dwellinghouse above ground level (x).
b. Where a rear extension is provided, the height of the extension (y).
See para 2.10
See Diagram 2.1d. In addition to meeting the provisions in paragraph 2.5, the dwellinghouse should comply with either of the following.
a. Provide an alternative escape route from each storey more than 7.5m above ground level. At the first storey above 7.5m, the protected stairway should be separated from the lower storeys by fire resisting construction (minimum REI 30) if the alternative escape route is accessed via either of the following.
i. The protected stairway to an upper storey.
ii. A landing within the protected stairway enclosure to an alternative escape route on the same storey. The protected stairway at or about 7.5m above ground level should be separated from the lower storeys or levels by fire resisting construction (see Diagram 2.4).
b. Provide a sprinkler system throughout, designed and installed in accordance with BS 9251.
NOTES:
1. If travel distance is measured to a stair lobby, the lobby must not provide direct access to any storage room, flat or other space containing a fire hazard.
2. In the case of a small single stair building in accordance with Diagram 3.9, this is reduced to 4.5m.
3. Does not apply if all flats on a storey have independent alternative means of escape.
4. Sheltered housing may require reduced maximum travel distances.
The internal arrangement of single storey or multi-storey flats should comply with paragraphs 3.15 to 3.17. Alternatively, the guidance in paragraphs 3.18 to 3.22 may be followed.
A flat accessed via the common parts of the building should also comply with the provisions for small single stair buildings in paragraph 3.28 and Diagram 3.9. A protected entrance hall may be required as a result.
A multi-storey flat with an independent external entrance at ground level is similar to a dwellinghouse and means of escape should be planned on the basis of Section 2, depending on the height of the top storey above ground level.
When multi-storey flats do not have their own external entrance at ground level, adopt one of the following approaches.
a. Approach 1 – provide at least one alternative exit from each habitable room that is not on the entrance storey of the flat (Diagram 3.5 and paragraph 3.22).
b. Approach 2 – provide at least one alternative exit from each storey that is not the entrance storey of the flat. All habitable rooms should have direct access to a protected landing (Diagram 3.6 and paragraph 3.22).
c. Approach 3 – provide a protected stairway plus a sprinkler system in accordance with Appendix E and provide smoke alarms in accordance with BS 5839-6.
d. Approach 4 – if the vertical distance between the entrance storey of the flat and any of the storeys above or below does not exceed 7.5m, provide all of the following.
i. A protected stairway.
ii. Additional smoke alarms in all habitable rooms.
iii. A heat alarm in any kitchen.
For some low rise buildings, the provisions in paragraphs 3.26 and 3.27 may be modified and the use of a single stair, protected in accordance with Diagram 3.9, may be permitted where all of the following apply.
a. The top storey of the building is a maximum of 11m above ground level.
b. No more than three storeys are above the ground storey.
c. The stair does not connect to a covered car park, unless the car park is open sided (as defined in Section 11 of Approved Document B Volume 2).
d. The stair does not serve offices, stores or other ancillary accommodation. If it does, they should be separated from the stair by a protected lobby or protected corridor (minimum REI 30) with a minimum 0.4m2 of permanent ventilation, or be protected from the ingress of smoke by a mechanical smoke control system.
NOTE: For refuse chutes and storage see paragraphs 3.55 to 3.58.
e. Either of the following is provided for the fire and rescue service.
i. A high-level openable vent with a free area of at least 1m2 at each storey.
ii. A single openable vent with a free area of at least 1m2 at the head of the stair, operable remotely at the fire and rescue service access level.
Ancillary accommodation should not be located in, or entered from, a protected lobby or protected corridor forming the only common escape route on that storey.
In mixed use buildings, separate means of escape should be provided from any storeys or parts of storeys used for the ‘residential’ or ‘assembly and recreation’ purpose groups (purpose groups 1, 2 and 5), other than in the case of certain small buildings or buildings in which the residential accommodation is ancillary (see paragraphs 3.76 and 3.77)
Refuse chutes and rooms for storing refuse should meet both of the following conditions.
a. Be separated from other parts of the building by fire resisting construction (minimum REI 30 in buildings with a top storey up to 5m above ground level; otherwise REI 60).
b. Not be situated within a protected stairway or protected lobby.
See para 3.21
NOTE: This only applies where at least one storey is more than 4.5m above ground level.
Fire doorset
Fire resisting stair enclosure(minimum REI 30)
Alternative exit
Where more than one escape route is available from a storey (or part of a building), then some of the escape routes from that storey or part of the building may be by way of an external stair provided all of the following conditions are met:
a. There is a at least one internal escape stair from every part of each storey (excluding plant areas).
b. The stair serves a floor not more than 6m above either the ground level or a roof podium which is itself served by an independent protected stairway.
c. The stair meets the provisions in paragraph 3.68.
If a building does not meet the criteria of paragraph 3.28, an escape stair forming part of the only escape route from an upper storey should not continue down to serve a basement storey. The basement storey should be served by a separate escape stair.
Where multiple escape stairs serve the upper storeys, only one needs to end at ground level. Other stairs may connect with the basement storeys if there is a protected lobby or a protected corridor between the stairs and accommodation at each basement level.
In buildings with a maximum of three storeys above the ground storey, stairs may serve both flats and other occupancies, provided that the stairs are separated from each occupancy by protected lobbies (minimum REI 30) at each storey.
site preparation and resistance to contaminants and moisture 2004 edition incorporating 2010 and 2013 amendments
Guidance on cables for large and complex buildings is given in BS 5839-1, BS 5266-1 and BS 8519.
Refuse storage chambers, refuse chutes and refuse hoppers should be sited and constructed in accordance with BS 5906.
specialist process lighting
All escape routes should have adequate artificial lighting. If the mains electricity power supply fails, escape lighting should illuminate the route (including external escape routes).
Escape lighting should conform to BS 5266-1.
specified attachment
With some configurations of external wall, a fire in one part of a building could subject the external wall of a protected stairway to heat (for example, where the two are adjacent at an internal angle in the façade, as shown in Diagram 3.10).
spiral stair
See Diagram 2.1b. Where served by only one stair, all habitable rooms (excluding kitchens) should have either of the following.
a. An emergency escape window or external door, as described in paragraph 2.10.
b. Direct access to a protected stairway, as described in paragraph 2.5a.
Dwellinghouses with one internal stair should comply with paragraphs 2.5 and 2.6. In dwellinghouses with more than one stair, the stairs should provide effective alternative means of escape. The stairs should be physically separated by either of the following.
a. Fire resisting construction (minimum REI 30).
b. More than one room.
A building should provide access to more than one common stair if it does not meet the criteria for a single common stair (see paragraph 3.26 and 3.27).
Flats may be served by an external stair if the provisions in paragraphs 3.66 to 3.69 are followed.
Where a storey (or part of a building) is served by a single access stair, that stair may be external provided both of the following conditions are met.
a. The stair serves a floor not more than 6m above the ground level.
b. The stair meets the provisions in paragraph 3.62.
stack effect
Guidance on the design of smoke control systems that use pressure differentials is available in BS EN 12101-6.
stair width
A stair of acceptable width for everyday use will be sufficient for escape purposes. If it is also a firefighting stair, it should be at least 1100mm wide. The width is the clear width between the walls or balustrades. Any handrails and strings intruding into that width by a maximum of 100mm on each side may be ignored.
step-free
Escape route floor finishes should minimise their slipperiness when wet. Finishes include the treads of steps and surfaces of ramps and landings.
storey
NOTES:
1. This diagram does not apply where the gallery is provided with one of the following:
i. An alternative escape route
ii. An emergency escape window (where the gallery floor is not more than 4.5m above ground level).
2. Any cooking facilities within a room containing a gallery should comply with one of the following conditions:
i. Be enclosed with fire resisting construction
ii. Be remote from the stair to the gallery and positioned such that they do not prejudice escape from the gallery.
See para 2.15
NOTES:
1. This diagram does not apply where the gallery is provided with one of the following:
i. An alternative escape route
ii. An emergency escape window (where the gallery floor is not more than 4.5m above ground level).
2. Any cooking facilities within a room containing a gallery should comply with one of the following conditions:
i. Be enclosed with fire resisting construction
ii. Be remote from the stair to the gallery and positioned such that they do not prejudice escape from the gallery.
See para 3.13
When multi-storey flats do not have their own external entrance at ground level, adopt one of the following approaches.
a. Approach 1 – provide at least one alternative exit from each habitable room that is not on the entrance storey of the flat (Diagram 3.5 and paragraph 3.22).
b. Approach 2 – provide at least one alternative exit from each storey that is not the entrance storey of the flat. All habitable rooms should have direct access to a protected landing (Diagram 3.6 and paragraph 3.22).
c. Approach 3 – provide a protected stairway plus a sprinkler system in accordance with Appendix E and provide smoke alarms in accordance with BS 5839-6.
d. Approach 4 – if the vertical distance between the entrance storey of the flat and any of the storeys above or below does not exceed 7.5m, provide all of the following.
i. A protected stairway.
ii. Additional smoke alarms in all habitable rooms.
iii. A heat alarm in any kitchen.
In mixed use buildings, separate means of escape should be provided from any storeys or parts of storeys used for the ‘residential’ or ‘assembly and recreation’ purpose groups (purpose groups 1, 2 and 5), other than in the case of certain small buildings or buildings in which the residential accommodation is ancillary (see paragraphs 3.76 and 3.77)
storey exit
See Diagram 2.1a. All habitable rooms (excluding kitchens) should have either of the following.
a. An opening directly onto a hall leading to a final exit.
b. An emergency escape window or door, as described in paragraph 2.10.
Where a flat roof forms part of a means of escape, it should comply with all of the following.
a. It should be part of the same building from which escape is being made.
b. The route across the roof should lead to a storey exit or external escape route.
c. The part of the roof (including its supporting structure) forming the escape route, and any opening within 3m of the escape route, should be of fire resisting construction (minimum REI 30).
Basement storeys containing habitable rooms should have one of the following.
a. An emergency escape window or external door providing escape from the basement (paragraph 2.10).
b. A protected stairway (paragraph 2.5a) leading from the basement to a final exit.
See Diagram 2.1b. Where served by only one stair, all habitable rooms (excluding kitchens) should have either of the following.
a. An emergency escape window or external door, as described in paragraph 2.10.
b. Direct access to a protected stairway, as described in paragraph 2.5a.
See para 2.5
Fire resisting construction minimum REI 30
Fd Fire doorset minimum E 20
See para 2.5
Alternative cavity barrier arrangements in roof space over protected stairway in a house with a storey more than 4.5m above ground level
See Diagram 2.1c. The dwellinghouse should have either of the following. Cavity barriers or a fire resisting ceiling (minimum EI 30) should be provided above a protected stairway enclosure (Diagram 2.3). b. Alternative escape route – a top storey separated from lower storeys by fire resisting construction (minimum REI 30) and with an alternative escape route leading to its own final exit.
a. Protected stairway – a stair separated by fire resisting construction (minimum REI 30) at all storeys, that complies with one of the following.
i. Extends to a final exit (Diagram 2.2a).
ii. Gives access to a minimum of two ground level final exits that are separated from each other by fire resisting construction (minimum REI 30) and fire doorsets (minimum E 20) (Diagram 2.2b).
See Diagram 2.1d. In addition to meeting the provisions in paragraph 2.5, the dwellinghouse should comply with either of the following.
a. Provide an alternative escape route from each storey more than 7.5m above ground level. At the first storey above 7.5m, the protected stairway should be separated from the lower storeys by fire resisting construction (minimum REI 30) if the alternative escape route is accessed via either of the following.
i. The protected stairway to an upper storey.
ii. A landing within the protected stairway enclosure to an alternative escape route on the same storey. The protected stairway at or about 7.5m above ground level should be separated from the lower storeys or levels by fire resisting construction (see Diagram 2.4).
b. Provide a sprinkler system throughout, designed and installed in accordance with BS 9251.
Where a flat roof forms part of a means of escape, it should comply with all of the following.
a. It should be part of the same building from which escape is being made.
b. The route across the roof should lead to a storey exit or external escape route.
c. The part of the roof (including its supporting structure) forming the escape route, and any opening within 3m of the escape route, should be of fire resisting construction (minimum REI 30).
All habitable rooms (excluding kitchens) should have either of the following.
a. An opening directly onto a hall leading to a final exit.
b. An emergency escape window or door, as described in paragraph 3.6.
All habitable rooms (excluding kitchens) should have either of the following.
a. An emergency escape window or external door, as described in paragraph 3.6.
b. In multi-storey flats, direct access to a protected internal stairway (minimum REI 30) leading to an exit from the flat.
Any alternative exit from a flat should comply with all of the following.
a. It should be remote from the main entrance door to the flat.
b. It should lead to a final exit, via a common stair if necessary, through one of the following.
i. A door to an access corridor, access lobby or common balcony.
ii. An internal private stair leading to an access corridor, access lobby or common balcony at another level.
iii. A door to a common stair.
iv. A door to an external stair.
v. A door to an escape route over a flat roof.
Any access route leading to a final exit or common stair should comply with the provisions for means of escape in the common parts of a flat (see paragraph 3.25).
Where a storey or part of a building has multiple escape routes available, one may be over a flat roof that complies with all of the following.
a. It should be part of the same building from which escape is being made.
b. The route across the roof should lead to a storey exit or external escape route.
c. The part of the roof (including its supporting structure) forming the escape route, and any opening within 3m of the escape route, should be of fire resisting construction (minimum REI 30).
d. The route should be clearly defined and guarded by walls and/or protective barriers to protect against falling.
Where a storey or part of a building has multiple escape routes available, one may be over a flat roof that complies with all of the following.
d. The route should be clearly defined and guarded by walls and/or protective barriers to protect against falling.
The following paragraphs deal with means of escape from the entrance doors of flats to a final exit.
Ancillary accommodation should not be located in, or entered from, a protected lobby or protected corridor forming the only common escape route on that storey.
Every doorway or other exit providing access to a means of escape, other than exits in ordinary use (e.g. main entrances), should be distinctively and conspicuously marked by an exit sign in accordance with BS ISO 3864-1 and BS 5499-4. For this reason, blocks of flats with a single stair in regular use would not usually require any fire exit signage.
Advice on fire safety signs, including emergency escape signs, is given in the HSE publication Safety Signs and Signals: Guidance on Regulations.
Some buildings may require additional signs to comply with other legislation.
Access openings to refuse storage chambers should not be sited in the following areas.
a. Next to escape routes or final exits.
b. Near the windows of flats.
The construction separating two adjacent protected stairways (or exit passageways leading to different final exits) should be imperforate.
Where a common stair is not part of the only escape route from a flat, it may also serve ancillary accommodation from which it is separated by a protected lobby or protected corridor (minimum REI 30).
Every protected stairway should lead to a final exit, either directly or via a protected exit passageway. Any protected exit corridor or stair should have the same standard of fire resistance and lobby protection as the stair it serves.
Basement storeys containing habitable rooms should have one of the following.
a. An emergency escape window or external door providing escape from the basement (see paragraph 3.6).
b. A protected stairway (minimum REI 30) leading from the basement to a final exit.
structure 2004 edition incorporating 20042010 and 2013 amendments
Guidance on cables for large and complex buildings is given in BS 5839-1, BS 5266-1 and BS 8519.
suitable tread nosings
Smoke alarms should be mains operated and conform to BS EN 14604.
Heat alarms should be mains operated and conform to BS 5446-2.
surface water activity
Guidance on the design of smoke control systems that use pressure differentials is available in BS EN 12101-6.
suspended ceiling
See para 2.5
Alternative cavity barrier arrangements in roof space over protected stairway in a house with a storey more than 4.5m above ground level
Fire resisting window(minimum RE30)
No fire resistance required for door
1100mm zone above top landing
6m max. height without weather protection
1800mm zone of fire resisting construction at side of stairway
Fire doorset(minimum E30)
See para 2.17
tapered tread
Paragraph 3.27 may be modified using the guidance in clause 7.3 of BS 9991.
the management regulations
Gas service and installation pipes and meters should not be within a protected stairway, unless installed in accordance with the Pipelines Safety Regulations 1996 and the Gas Safety (Installation and Use) Regulations 1998.
total useful floor area
Windows or external doors providing emergency escape should comply with all of the following.
a. Windows should have an unobstructed openable area that complies with all of the following.
i. A minimum area of 0.33m2.
ii. A minimum height of 450mm and a minimum width of 450mm (the route through the window may be at an angle rather than straight through).
iii. The bottom of the openable area is a maximum of 1100mm above the floor.
b. People escaping should be able to reach a place free from danger from fire. Courtyards or inaccessible back gardens should comply with Diagram 2.5.
c. Locks (with or without removable keys) and opening stays (with child-resistant release catches) may be fitted to escape windows.
d. Windows should be capable of remaining open without being held.
Windows or external doors providing emergency escape should comply with all of the following.
a. Windows should have an unobstructed openable area that complies with all of the following.
i. A minimum area of 0.33m2.
ii. A minimum height of 450mm and a minimum width of 450mm (the route through the window may be at an angle rather than straight through).
iii. The bottom of the openable area is a maximum of 1100mm above the floor.
b. People escaping should be able to reach a place free from danger from fire. Courtyards or inaccessible back gardens should comply with Diagram 2.5.
c. Locks (with or without removable keys) and opening stays (with child-resistant release catches) may be fitted to escape windows.
d. Windows should be capable of remaining open without being held.
A gallery should comply with one of the following.
a. It should be provided with an alternative exit.
b. It should be provided with an emergency escape window, as described in paragraph 2.10, where the gallery floor is a maximum of 4.5m above ground level.
c. It should meet all the conditions shown in Diagram 2.6.
An alternative approach to that described in paragraph 2.21 would be to comply with all of the following.
a. Provide sprinkler protection to the open-plan areas.
b. Provide a fire resisting partition (minimum REI 30) and door (minimum E 20) to separate the ground storey from the upper storeys. The door should allow occupants of the loft room access to a first storey escape window.
c. Separate cooking facilities from the open-plan area with fire resisting construction (minimum REI 30).
NOTES:
1. This diagram does not apply where the gallery is provided with one of the following:
i. An alternative escape route
ii. An emergency escape window (where the gallery floor is not more than 4.5m above ground level).
2. Any cooking facilities within a room containing a gallery should comply with one of the following conditions:
i. Be enclosed with fire resisting construction
ii. Be remote from the stair to the gallery and positioned such that they do not prejudice escape from the gallery.
See para 2.15
NOTES:
1. This diagram does not apply where the gallery is provided with one of the following:
i. An alternative escape route
ii. An emergency escape window (where the gallery floor is not more than 4.5m above ground level).
2. Any cooking facilities within a room containing a gallery should comply with one of the following conditions:
i. Be enclosed with fire resisting construction
ii. Be remote from the stair to the gallery and positioned such that they do not prejudice escape from the gallery.
See para 2.15
All of the following precautions should be taken to avoid the spread of smoke and fire to the protected stairway.
a. Transfer grilles should not be fitted in any wall, door, floor or ceiling of the stair enclosure.
b. Any duct passing through the stair enclosure should be rigid steel. Joints between the ductwork and stair enclosure should be fire-stopped.
c. Ventilation ducts supplying or extracting air directly to or from a protected stairway should not serve other areas as well.
d. Any system of mechanical ventilation which recirculates air and which serves both the stair and other areas should be designed to shut down on the detection of smoke within the system.
e. For ducted warm air heating systems, a room thermostat should be sited in the living room. It should be mounted at a height between 1370mm and 1830mm above the floor. The maximum setting should be 27°C.
NOTE: Ventilation ducts passing through compartment walls should comply with the guidance in Section 9.
All of the following precautions should be taken to avoid the spread of smoke and fire to the protected stairway.
a. Transfer grilles should not be fitted in any wall, door, floor or ceiling of the stair enclosure.
b. Any duct passing through the stair enclosure should be rigid steel. Joints between the ductwork and stair enclosure should be fire-stopped.
c. Ventilation ducts supplying or extracting air directly to or from a protected stairway should not serve other areas as well.
d. Any system of mechanical ventilation which recirculates air and which serves both the stair and other areas should be designed to shut down on the detection of smoke within the system.
e. For ducted warm air heating systems, a room thermostat should be sited in the living room. It should be mounted at a height between 1370mm and 1830mm above the floor. The maximum setting should be 27°C.
NOTE: Ventilation ducts passing through compartment walls should comply with the guidance in Section 9.
NOTES:
1. This diagram does not apply where the gallery is provided with one of the following:
i. An alternative escape route
ii. An emergency escape window (where the gallery floor is not more than 4.5m above ground level).
2. Any cooking facilities within a room containing a gallery should comply with one of the following conditions:
i. Be enclosed with fire resisting construction
ii. Be remote from the stair to the gallery and positioned such that they do not prejudice escape from the gallery.
See para 3.13
NOTES:
1. This diagram does not apply where the gallery is provided with one of the following:
i. An alternative escape route
ii. An emergency escape window (where the gallery floor is not more than 4.5m above ground level).
2. Any cooking facilities within a room containing a gallery should comply with one of the following conditions:
i. Be enclosed with fire resisting construction
ii. Be remote from the stair to the gallery and positioned such that they do not prejudice escape from the gallery.
See para 3.13
A gallery should comply with one of the following.
a. It should be provided with an alternative exit.
b. It should be provided with an emergency escape window, as described in paragraph 3.6, where the gallery floor is a maximum of 4.5m above ground level.
c. It should meet the conditions shown in Diagram 3.1.
For systems circulating air only within an individual flat, take all of the following precautions.
a. Transfer grilles should not be fitted in any wall, door, floor or ceiling of the enclosure.
b. Any duct passing through the enclosure should be rigid steel. Joints between the ductwork and enclosure should be fire-stopped.
c. Ventilation ducts serving the enclosure should not serve any other areas.
d. Any system of mechanical ventilation which recirculates air and which serves both the stair and other areas should be designed to shut down on the detection of smoke within the system.
e. For ducted warm air heating systems, a room thermostat should be sited in the living room. It should be mounted at a height between 1370mm and 1830mm above the floor. The maximum setting should be 27°C.
NOTE: Ventilation ducts passing through compartment walls should comply with the guidance in Section 9.
Paragraph 3.27 may be modified using the guidance in clause 7.3 of BS 9991.
A ramp forming part of an escape route should meet the provisions in Approved Document M. Any sloping floor or tier should have a pitch of not more than 35 degrees to the horizontal.
To limit potential damage to cables in protected circuits, all of the following should apply.
a. Cables should be sufficiently robust.
b. Cable routes should be carefully selected and/or physically protected in areas where cables may be exposed to damage.
c. Methods of cable support should be class A1 rated and offer at least the same integrity as the cable. They should maintain circuit integrity and hold cables in place when exposed to fire.
A vent to the outside with a minimum free area of 1m2 should be provided from the top storey of the stair.
Access openings to refuse storage chambers should not be sited in the following areas.
a. Next to escape routes or final exits.
b. Near the windows of flats.
Windows or external doors providing emergency escape should comply with all of the following.
a. Windows should have an unobstructed openable area that complies with all of the following.
i. A minimum area of 0.33m2.
ii. A minimum height of 450mm and a minimum width of 450mm (the route through the window may be at an angle rather than straight through).
iii. The bottom of the openable area is a maximum of 1100mm above the floor.
b. People escaping should be able to reach a place free from danger from fire.
c. Locks (with or without removable keys) and opening stays (with child-resistant release catches) may be fitted to escape windows.
d. Windows should be capable of remaining open without being held.
Windows or external doors providing emergency escape should comply with all of the following.
a. Windows should have an unobstructed openable area that complies with all of the following.
i. A minimum area of 0.33m2.
ii. A minimum height of 450mm and a minimum width of 450mm (the route through the window may be at an angle rather than straight through).
iii. The bottom of the openable area is a maximum of 1100mm above the floor.
b. People escaping should be able to reach a place free from danger from fire.
c. Locks (with or without removable keys) and opening stays (with child-resistant release catches) may be fitted to escape windows.
d. Windows should be capable of remaining open without being held.
If a protected stairway projects beyond, is recessed from or is in an internal angle of the adjoining external wall of the building, then the minimum distance between an unprotected area of the building enclosure and an unprotected area of the stair enclosure should be 1800mm.
If a protected stairway projects beyond, is recessed from or is in an internal angle of the adjoining external wall of the building, then the minimum distance between an unprotected area of the building enclosure and an unprotected area of the stair enclosure should be 1800mm.
See paras 3.27 and 3.36
NOTES:
1. The arrangements shown also apply to the top storey.
2. See Diagram 3.9 for small single stair buildings.
3. All doors shown are fire doorsets.
4. Where travel distance is measured to a stair lobby, the lobby must not provide direct access to any storage room, flat or other space containing a potential fire hazard.
5. For further guidance on the fire rating of the fire doorsets from the corridor to the flat and/or stairway refer to Appendix C ,Table C1.
F Flat
Shaded areas indicate zones where ventilation should be provided in accordance with paragraphs 3.50 to 3.53(An external wall vent or smoke shaft located anywhere in the shaded area)
travel distance
An alternative approach to that described in paragraph 2.21 would be to comply with all of the following.
a. Provide sprinkler protection to the open-plan areas.
b. Provide a fire resisting partition (minimum REI 30) and door (minimum E 20) to separate the ground storey from the upper storeys. The door should allow occupants of the loft room access to a first storey escape window.
c. Separate cooking facilities from the open-plan area with fire resisting construction (minimum REI 30).
An alternative approach to that described in paragraph 2.21 would be to comply with all of the following.
a. Provide sprinkler protection to the open-plan areas.
b. Provide a fire resisting partition (minimum REI 30) and door (minimum E 20) to separate the ground storey from the upper storeys. The door should allow occupants of the loft room access to a first storey escape window.
c. Separate cooking facilities from the open-plan area with fire resisting construction (minimum REI 30).
NOTES:
1. If travel distance is measured to a stair lobby, the lobby must not provide direct access to any storage room, flat or other space containing a fire hazard.
2. In the case of a small single stair building in accordance with Diagram 3.9, this is reduced to 4.5m.
3. Does not apply if all flats on a storey have independent alternative means of escape.
4. Sheltered housing may require reduced maximum travel distances.
NOTES:
1. If travel distance is measured to a stair lobby, the lobby must not provide direct access to any storage room, flat or other space containing a fire hazard.
2. In the case of a small single stair building in accordance with Diagram 3.9, this is reduced to 4.5m.
3. Does not apply if all flats on a storey have independent alternative means of escape.
4. Sheltered housing may require reduced maximum travel distances.
One of the following approaches should be adopted, observing the inner room restrictions described in paragraphs 3.7 and 3.8.
a. Provide a protected entrance hall (minimum REI 30) serving all habitable rooms that meets the conditions shown in Diagram 3.2.
b. Plan the flat to meet the conditions shown in Diagram 3.3, so that both of the following apply.
i. The travel distance from the flat entrance door to any point in any habitable room is a maximum of 9m.
ii. Cooking facilities are remote from the main entrance door and do not impede the escape route from anywhere in the flat.
c. Provide an alternative exit from the flat complying with paragraph 3.22.
One of the following approaches should be adopted, observing the inner room restrictions described in paragraphs 3.7 and 3.8.
a. Provide a protected entrance hall (minimum REI 30) serving all habitable rooms that meets the conditions shown in Diagram 3.2.
b. Plan the flat to meet the conditions shown in Diagram 3.3, so that both of the following apply.
i. The travel distance from the flat entrance door to any point in any habitable room is a maximum of 9m.
ii. Cooking facilities are remote from the main entrance door and do not impede the escape route from anywhere in the flat.
c. Provide an alternative exit from the flat complying with paragraph 3.22.
For flats serving as a workplace for both occupants and people who do not live on the premises, provide both of the following.
a. A maximum travel distance of 18m between any part of the working area and either of the following.
i. The flat entrance door.
ii. An alternative means of escape that is not a window.
If the travel distance is over 18m, the assumptions in paragraph 3.2 may not be valid. The design should be considered on a case-by-case basis.
b. Escape lighting to windowless accommodation in accordance with BS 5266-1.
For flats serving as a workplace for both occupants and people who do not live on the premises, provide both of the following.
a. A maximum travel distance of 18m between any part of the working area and either of the following.
i. The flat entrance door.
ii. An alternative means of escape that is not a window.
If the travel distance is over 18m, the assumptions in paragraph 3.2 may not be valid. The design should be considered on a case-by-case basis.
b. Escape lighting to windowless accommodation in accordance with BS 5266-1.
From the flat entrance door, a single escape route is acceptable in either of the following cases.
a. The flat is on a storey served by a single common stair and both of the following apply.
i. Every flat is separated from the common stair by a protected lobby or common protected corridor (see Diagram 3.7).
ii. The maximum travel distance in Table 3.1, for escape in one direction only, is not exceeded.
b. The flat is in a dead end of a common corridor served by two (or more) common stairs and the maximum travel distance given in Table 3.1, for escape in one direction only, is not exceeded (Diagram 3.8).
From the flat entrance door, a single escape route is acceptable in either of the following cases.
a. The flat is on a storey served by a single common stair and both of the following apply.
i. Every flat is separated from the common stair by a protected lobby or common protected corridor (see Diagram 3.7).
ii. The maximum travel distance in Table 3.1, for escape in one direction only, is not exceeded.
b. The flat is in a dead end of a common corridor served by two (or more) common stairs and the maximum travel distance given in Table 3.1, for escape in one direction only, is not exceeded (Diagram 3.8).
Escape route travel distances should comply with Table 3.1.
Escape route travel distances should comply with Table 3.1.
If a protected stairway projects beyond, is recessed from or is in an internal angle of the adjoining external wall of the building, then the minimum distance between an unprotected area of the building enclosure and an unprotected area of the stair enclosure should be 1800mm.
If a protected stairway projects beyond, is recessed from or is in an internal angle of the adjoining external wall of the building, then the minimum distance between an unprotected area of the building enclosure and an unprotected area of the stair enclosure should be 1800mm.
See paras 3.27 and 3.36
NOTES:
1. The arrangements shown also apply to the top storey.
2. See Diagram 3.9 for small single stair buildings.
3. All doors shown are fire doorsets.
4. Where travel distance is measured to a stair lobby, the lobby must not provide direct access to any storage room, flat or other space containing a potential fire hazard.
5. For further guidance on the fire rating of the fire doorsets from the corridor to the flat and/or stairway refer to Appendix C ,Table C1.
F Flat
Shaded areas indicate zones where ventilation should be provided in accordance with paragraphs 3.50 to 3.53(An external wall vent or smoke shaft located anywhere in the shaded area)
See paras 3.27 and 3.36
NOTES:
1. The arrangements shown also apply to the top storey.
2. See Diagram 3.9 for small single stair buildings.
3. All doors shown are fire doorsets.
4. Where travel distance is measured to a stair lobby, the lobby must not provide direct access to any storage room, flat or other space containing a potential fire hazard.
5. For further guidance on the fire rating of the fire doorsets from the corridor to the flat and/or stairway refer to Appendix C ,Table C1.
F Flat
Shaded areas indicate zones where ventilation should be provided in accordance with paragraphs 3.50 to 3.53(An external wall vent or smoke shaft located anywhere in the shaded area)
a. CORRIDOR ACCESS WITHOUT DEAD ENDS
b. CORRIDOR ACCESS WITH DEAD ENDS
The central door may be omitted if maximum travel distance is not more than 15m.
1. The arrangements shown also apply to the top storey.
2. For further guidance on the fire rating of the fire doorsets from the corridor to the flat and/or stairway refer to Appendix C ,Table C1.
Fire doorset provided in accordance with paragraphs 3.50 to 3.53(An external wall vent or smoke shaft located anywhere in the shaded area)
See paras 3.27 and 3.36
a. CORRIDOR ACCESS WITHOUT DEAD ENDS
b. CORRIDOR ACCESS WITH DEAD ENDS
The central door may be omitted if maximum travel distance is not more than 15m.
1. The arrangements shown also apply to the top storey.
2. For further guidance on the fire rating of the fire doorsets from the corridor to the flat and/or stairway refer to Appendix C ,Table C1.
Fire doorset provided in accordance with paragraphs 3.50 to 3.53(An external wall vent or smoke shaft located anywhere in the shaded area)
See paras 3.27 and 3.36
a. SMALL SINGLE STAIR BUILDING
*If smoke control is provided in the lobby, the travel distance can be increased to 7.5m maximum(see Diagram 3.7, example b).
b. SMALL SINGLE STAIR BUILDING WITH NO MORE THAN TWO FLATS PER STOREY
The door between stair and lobby should be free from security fastenings.
If the flats have protected entrance halls, the lobby between the common stair and flat entrance is not essential.
NOTES:
1. The arrangements shown also apply to the top storey.
2. If the travel distance across the lobby in diagram (a) exceeds 4.5m, Diagram 3.7 applies.
3. Where,in Diagram (b), the lobby between the common stair and the dwelling is omitted in smal lsingle stair buildings, an automatic opening vent with a free area of at least 1m2 is required at the top of the stair,which is operated automatically on detection of smoke at any storey in the stair.
4. For further guidance on the fire rating of the fire doorsets from the corridor to the flat and/or stairway refer to Appendix C, Table C1.
Fire resisting construction
Openable vent at high level for fire service use (1.0m2 minimum free area); see paragraph 3.28eSee para 3.28
Diagram 3.9
a. SMALL SINGLE STAIR BUILDING
*If smoke control is provided in the lobby, the travel distance can be increased to 7.5m maximum(see Diagram 3.7, example b).
b. SMALL SINGLE STAIR BUILDING WITH NO MORE THAN TWO FLATS PER STOREY
The door between stair and lobby should be free from security fastenings.
If the flats have protected entrance halls, the lobby between the common stair and flat entrance is not essential.
NOTES:
1. The arrangements shown also apply to the top storey.
2. If the travel distance across the lobby in diagram (a) exceeds 4.5m, Diagram 3.7 applies.
3. Where,in Diagram (b), the lobby between the common stair and the dwelling is omitted in smal lsingle stair buildings, an automatic opening vent with a free area of at least 1m2 is required at the top of the stair,which is operated automatically on detection of smoke at any storey in the stair.
4. For further guidance on the fire rating of the fire doorsets from the corridor to the flat and/or stairway refer to Appendix C, Table C1.
Fire resisting construction
Openable vent at high level for fire service use (1.0m2 minimum free area); see paragraph 3.28eSee para 3.28
Diagram 3.9
unprotected area
Any external escape stair should meet all of the following conditions (Diagram 2.7).
a. Doors to the stair should be fire resisting (minimum E 30), except for a single exit door from the building to the top landing of a downward-leading external stair.
b. Fire resisting construction (minimum RE 30) is required for the building envelope within the following zones, measured from the flights and landings of the external stair.
i. 1800mm horizontally.
ii. 9m vertically below.
iii. 1100mm above the top landing of the stair (except where the stair leads from basement to ground level).
c. Fire resisting construction (minimum RE 30) should be provided for any part of the building (including doors) within 1800mm of the escape route from the foot of the stair to a place of safety. This does not apply if there are alternative escape routes from the foot of the external escape stair.
d. Stairs more than 6m in height should be protected from adverse weather. Protection should prevent the build-up of snow or ice but does not require full enclosure.
e. Glazing in areas of fire resisting construction should be fixed shut and fire resisting (in terms of integrity, but not insulation) (minimum E 30).
Windows or external doors providing emergency escape should comply with all of the following.
a. Windows should have an unobstructed openable area that complies with all of the following.
i. A minimum area of 0.33m2.
ii. A minimum height of 450mm and a minimum width of 450mm (the route through the window may be at an angle rather than straight through).
iii. The bottom of the openable area is a maximum of 1100mm above the floor.
b. People escaping should be able to reach a place free from danger from fire.
c. Locks (with or without removable keys) and opening stays (with child-resistant release catches) may be fitted to escape windows.
d. Windows should be capable of remaining open without being held.
With some configurations of external wall, a fire in one part of a building could subject the external wall of a protected stairway to heat (for example, where the two are adjacent at an internal angle in the façade, as shown in Diagram 3.10).
If a protected stairway projects beyond, is recessed from or is in an internal angle of the adjoining external wall of the building, then the minimum distance between an unprotected area of the building enclosure and an unprotected area of the stair enclosure should be 1800mm.
Flats may be served by an external stair if the provisions in paragraphs 3.66 to 3.69 are followed.
Any external escape stair should meet all of the following conditions (Diagram 3.11).
a. Doors to the stair should be fire resisting (minimum E 30) and be fitted with a self-closing device, except for a single exit door from the building to the top landing of a downward-leading external stair, provided it is the only door onto the landing.
b. Fire resisting construction (minimum RE 30) is required for the building envelope within the following zones, measured from the flights and landings of the external stair.
i. 1800mm above and horizontally.
ii. 9m vertically below.
iii. 1100mm above the top landing of the stair (except where the stair leads from basement to ground level).
c. Fire resisting construction (minimum RE 30) should be provided for any part of the building (including doors) within 1800mm of the escape route from the foot of the stair to a place of safety. This does not apply if there are alternative escape routes from the foot of the external escape stair.
d. Glazing in areas of fire resisting construction should be fixed shut and fire resisting (in terms of integrity but not insulation) (minimum E 30).
e. Stairs more than 6m in height above ground level (e.g. where they are provided above a podium) should be protected from adverse weather. Protection should prevent the build-up of snow or ice but does not require full enclosure.
If a loadbearing wall is any of the following, guidance in other sections may also apply.
a. A compartment wall (including a wall common to two buildings): Section 7.
b. Enclosing a place of special fire hazard: Section 7.
c. Protecting a means of escape: Sections 2 and 3.
d. An external wall: Sections 10 and 11.
e. Enclosing a firefighting shaft: Section 15.
utility room
An inner room is permitted when it is one of the following.
a. A kitchen.
b. A laundry or utility room.
c. A dressing room.
d. A bathroom, WC or shower room.
e. Any room on a storey that is a maximum of 4.5m above ground level which is provided with an emergency escape window as described in paragraph 2.10.
f. A gallery that complies with paragraph 2.15.
A room accessed only via an inner room (an inner inner room) is acceptable when all of the following apply.
a. It complies with paragraph 2.11.
b. The access rooms each have a smoke alarm (see Section 1).
c. None of the access rooms is a kitchen.
An inner room is permitted when it is one of the following.
a. A kitchen.
b. A laundry or utility room.
c. A dressing room.
d. A bathroom, WC or shower room.
e. Any room on a storey that is a maximum of 4.5m above ground level which is provided with an emergency escape window as described in paragraph 3.6.
f. A gallery that complies with paragraph 3.13.
A room accessed only via an inner room (an inner inner room) is acceptable when all of the following apply.
a. It complies with paragraph 3.7.
b. The access rooms each have a smoke alarm (see Section 1).
c. None of the access rooms is a kitchen.
utility stair
Any external escape stair should meet all of the following conditions (Diagram 2.7).
a. Doors to the stair should be fire resisting (minimum E 30), except for a single exit door from the building to the top landing of a downward-leading external stair.
b. Fire resisting construction (minimum RE 30) is required for the building envelope within the following zones, measured from the flights and landings of the external stair.
i. 1800mm horizontally.
ii. 9m vertically below.
iii. 1100mm above the top landing of the stair (except where the stair leads from basement to ground level).
c. Fire resisting construction (minimum RE 30) should be provided for any part of the building (including doors) within 1800mm of the escape route from the foot of the stair to a place of safety. This does not apply if there are alternative escape routes from the foot of the external escape stair.
d. Stairs more than 6m in height should be protected from adverse weather. Protection should prevent the build-up of snow or ice but does not require full enclosure.
e. Glazing in areas of fire resisting construction should be fixed shut and fire resisting (in terms of integrity, but not insulation) (minimum E 30).
Where an existing window would be an escape window in a new dwellinghouse, and is big enough to be used for escape purposes, then the replacement should comply with one of the following.
a. The replacement window should be sized to provide at least the same potential for escape.
b. If the existing window was larger than required for escape purposes, the opening can be reduced to the minimum described in paragraph 2.10.
Dwellinghouses with one internal stair should comply with paragraphs 2.5 and 2.6. In dwellinghouses with more than one stair, the stairs should provide effective alternative means of escape. The stairs should be physically separated by either of the following.
a. Fire resisting construction (minimum REI 30).
b. More than one room.
Two rooms may be served by a single escape window. A door between rooms should provide access to the escape window without passing through the stair enclosure. Both rooms should have their own access to the internal stair.
Two rooms may be served by a single escape window. A door between rooms should provide access to the escape window without passing through the stair enclosure. Both rooms should have their own access to the internal stair.
An escape route should not pass through one stair enclosure to reach another. It may pass through a protected lobby (minimum REI 30) of one stair to reach another.
An escape route should not pass through one stair enclosure to reach another. It may pass through a protected lobby (minimum REI 30) of one stair to reach another.
Escape stair lighting should be on a separate circuit from the electricity supply to any other part of the escape route.
A building should provide access to more than one common stair if it does not meet the criteria for a single common stair (see paragraph 3.26 and 3.27).
A building should provide access to more than one common stair if it does not meet the criteria for a single common stair (see paragraph 3.26 and 3.27).
A stair of acceptable width for everyday use will be sufficient for escape purposes. If it is also a firefighting stair, it should be at least 1100mm wide. The width is the clear width between the walls or balustrades. Any handrails and strings intruding into that width by a maximum of 100mm on each side may be ignored.
A stair of acceptable width for everyday use will be sufficient for escape purposes. If it is also a firefighting stair, it should be at least 1100mm wide. The width is the clear width between the walls or balustrades. Any handrails and strings intruding into that width by a maximum of 100mm on each side may be ignored.
Section 7 provides guidance on avoiding the spread of fire between storeys. For a stair that is also a firefighting stair, guidance in Section 15 should be followed.
Where a storey (or part of a building) is served by a single access stair, that stair may be external provided both of the following conditions are met.
a. The stair serves a floor not more than 6m above the ground level.
b. The stair meets the provisions in paragraph 3.62.
Where a storey (or part of a building) is served by a single access stair, that stair may be external provided both of the following conditions are met.
a. The stair serves a floor not more than 6m above the ground level.
b. The stair meets the provisions in paragraph 3.62.
Where multiple escape stairs serve the upper storeys, only one needs to end at ground level. Other stairs may connect with the basement storeys if there is a protected lobby or a protected corridor between the stairs and accommodation at each basement level.
Where multiple escape stairs serve the upper storeys, only one needs to end at ground level. Other stairs may connect with the basement storeys if there is a protected lobby or a protected corridor between the stairs and accommodation at each basement level.
vented (open) hot water storage system
Except in buildings that comply with Diagram 3.9, the corridor or lobby next to each stair should have a smoke vent. The location of the vent should comply with both of the following.
a. Be as high as practicable.
b. Be positioned so the top edge is at least as high as the top of the door to the stair.
A vent to the outside with a minimum free area of 1m2 should be provided from the top storey of the stair.
In single stair buildings, smoke vents on the storey where the fire is initiated, and the vent at the head of the stair, should be activated by smoke detectors in the common parts.
In buildings with more than one stair, smoke vents may be activated manually. The control system should open the vent at the head of the stair before, or at the same time as, the vent on the storey where the fire is located. Smoke detection is not required for ventilation purposes in this instance.
ventilation
Despite the provisions described, it is probable that some smoke will get into the common corridor or lobby from a fire in a flat.
There should therefore be some means of ventilating the common corridors/lobbies to control smoke and so protect the common stairs. This means of ventilation offers additional protection to that provided by the fire doors to the stair, as well as some protection to the corridors/lobbies.
Ventilation can be natural (paragraphs 3.50 to 3.53) or mechanical (paragraph 3.54).
ventilation opening
See Diagram 2.1a. All habitable rooms (excluding kitchens) should have either of the following.
a. An opening directly onto a hall leading to a final exit.
b. An emergency escape window or door, as described in paragraph 2.10.
Windows or external doors providing emergency escape should comply with all of the following.
a. Windows should have an unobstructed openable area that complies with all of the following.
i. A minimum area of 0.33m2.
ii. A minimum height of 450mm and a minimum width of 450mm (the route through the window may be at an angle rather than straight through).
iii. The bottom of the openable area is a maximum of 1100mm above the floor.
b. People escaping should be able to reach a place free from danger from fire. Courtyards or inaccessible back gardens should comply with Diagram 2.5.
c. Locks (with or without removable keys) and opening stays (with child-resistant release catches) may be fitted to escape windows.
d. Windows should be capable of remaining open without being held.
If windows are replaced, it may be necessary to provide cavity barriers around the opening in accordance with Section 5.
All habitable rooms (excluding kitchens) should have either of the following.
a. An opening directly onto a hall leading to a final exit.
b. An emergency escape window or door, as described in paragraph 3.6.
The approach to rooms containing refuse chutes or for storing refuse should comply with one of the following conditions.
a. Be directly from the open air.
b. Be through a protected lobby with a minimum of 0.2m2 of permanent ventilation.
Windows or external doors providing emergency escape should comply with all of the following.
a. Windows should have an unobstructed openable area that complies with all of the following.
i. A minimum area of 0.33m2.
ii. A minimum height of 450mm and a minimum width of 450mm (the route through the window may be at an angle rather than straight through).
iii. The bottom of the openable area is a maximum of 1100mm above the floor.
b. People escaping should be able to reach a place free from danger from fire.
c. Locks (with or without removable keys) and opening stays (with child-resistant release catches) may be fitted to escape windows.
d. Windows should be capable of remaining open without being held.
vomitory exits
Where new habitable rooms are provided, a fire detection and alarm system should be installed
where either of the following applies.
a. The room is provided above or below the ground storey.
b. The room is provided at the ground storey, without a final exit.
See para 2.5
Fire resisting construction minimum REI 30
Fd Fire doorset minimum E 20
Every doorway or other exit providing access to a means of escape, other than exits in ordinary use (e.g. main entrances), should be distinctively and conspicuously marked by an exit sign in accordance with BS ISO 3864-1 and BS 5499-4. For this reason, blocks of flats with a single stair in regular use would not usually require any fire exit signage.
Advice on fire safety signs, including emergency escape signs, is given in the HSE publication Safety Signs and Signals: Guidance on Regulations.
Some buildings may require additional signs to comply with other legislation.
The construction separating two adjacent protected stairways (or exit passageways leading to different final exits) should be imperforate.
Every protected stairway should lead to a final exit, either directly or via a protected exit passageway. Any protected exit corridor or stair should have the same standard of fire resistance and lobby protection as the stair it serves.
wall
With some configurations of external wall, a fire in one part of a building could subject the external wall of a protected stairway to heat (for example, where the two are adjacent at an internal angle in the façade, as shown in Diagram 3.10).
wet room
An inner room is permitted when it is one of the following.
a. A kitchen.
b. A laundry or utility room.
c. A dressing room.
d. A bathroom, WC or shower room.
e. Any room on a storey that is a maximum of 4.5m above ground level which is provided with an emergency escape window as described in paragraph 2.10.
f. A gallery that complies with paragraph 2.15.
A room accessed only via an inner room (an inner inner room) is acceptable when all of the following apply.
a. It complies with paragraph 2.11.
b. The access rooms each have a smoke alarm (see Section 1).
c. None of the access rooms is a kitchen.
Two rooms may be served by a single window. A door between the rooms should provide access to the window without passing through the stair enclosure. Both rooms should have their own access to the internal stair.
In addition, escape lighting should be provided to all of the following.
a. Toilet accommodation with a minimum floor area of 8m2.
b. Electricity and generator rooms.
c. Switch room/battery room for emergency lighting system.
d. Emergency control rooms.
An inner room is permitted when it is one of the following.
a. A kitchen.
b. A laundry or utility room.
c. A dressing room.
d. A bathroom, WC or shower room.
e. Any room on a storey that is a maximum of 4.5m above ground level which is provided with an emergency escape window as described in paragraph 3.6.
f. A gallery that complies with paragraph 3.13.
A room accessed only via an inner room (an inner inner room) is acceptable when all of the following apply.
a. It complies with paragraph 3.7.
b. The access rooms each have a smoke alarm (see Section 1).
c. None of the access rooms is a kitchen.
wheelchair accessible
All dwellings should have a fire detection and alarm system, minimum Grade D2 Category LD3
standard, in accordance with the relevant recommendations of BS 5839-6.
A higher standard of protection should be considered where occupants of a proposed dwelling
would be at special risk from fire. Further advice on this is also given in BS 5839-6.
wheelchair adaptable
All dwellings should have a fire detection and alarm system, minimum Grade D2 Category LD3
standard, in accordance with the relevant recommendations of BS 5839-6.
A higher standard of protection should be considered where occupants of a proposed dwelling
would be at special risk from fire. Further advice on this is also given in BS 5839-6.
whole building ventilation
Despite the provisions described, it is probable that some smoke will get into the common corridor or lobby from a fire in a flat.
There should therefore be some means of ventilating the common corridors/lobbies to control smoke and so protect the common stairs. This means of ventilation offers additional protection to that provided by the fire doors to the stair, as well as some protection to the corridors/lobbies.
Ventilation can be natural (paragraphs 3.50 to 3.53) or mechanical (paragraph 3.54).
window
See Diagram 2.1a. All habitable rooms (excluding kitchens) should have either of the following.
a. An opening directly onto a hall leading to a final exit.
b. An emergency escape window or door, as described in paragraph 2.10.
Windows or external doors providing emergency escape should comply with all of the following.
a. Windows should have an unobstructed openable area that complies with all of the following.
i. A minimum area of 0.33m2.
ii. A minimum height of 450mm and a minimum width of 450mm (the route through the window may be at an angle rather than straight through).
iii. The bottom of the openable area is a maximum of 1100mm above the floor.
b. People escaping should be able to reach a place free from danger from fire. Courtyards or inaccessible back gardens should comply with Diagram 2.5.
c. Locks (with or without removable keys) and opening stays (with child-resistant release catches) may be fitted to escape windows.
d. Windows should be capable of remaining open without being held.
Where an existing window would be an escape window in a new dwellinghouse, and is big enough to be used for escape purposes, then the replacement should comply with one of the following.
a. The replacement window should be sized to provide at least the same potential for escape.
b. If the existing window was larger than required for escape purposes, the opening can be reduced to the minimum described in paragraph 2.10.
If windows are replaced, it may be necessary to provide cavity barriers around the opening in accordance with Section 5.
Two rooms may be served by a single window. A door between the rooms should provide access to the window without passing through the stair enclosure. Both rooms should have their own access to the internal stair.
All habitable rooms (excluding kitchens) should have either of the following.
a. An opening directly onto a hall leading to a final exit.
b. An emergency escape window or door, as described in paragraph 3.6.
Two rooms may be served by a single escape window. A door between rooms should provide access to the escape window without passing through the stair enclosure. Both rooms should have their own access to the internal stair.
Access openings to refuse storage chambers should not be sited in the following areas.
a. Next to escape routes or final exits.
b. Near the windows of flats.
Windows or external doors providing emergency escape should comply with all of the following.
a. Windows should have an unobstructed openable area that complies with all of the following.
i. A minimum area of 0.33m2.
ii. A minimum height of 450mm and a minimum width of 450mm (the route through the window may be at an angle rather than straight through).
iii. The bottom of the openable area is a maximum of 1100mm above the floor.
b. People escaping should be able to reach a place free from danger from fire.
c. Locks (with or without removable keys) and opening stays (with child-resistant release catches) may be fitted to escape windows.
d. Windows should be capable of remaining open without being held.
workplace regulations
Gas service and installation pipes and meters should not be within a protected stairway, unless installed in accordance with the Pipelines Safety Regulations 1996 and the Gas Safety (Installation and Use) Regulations 1998.