Diagram 8.3 Fire resisting ceiling below concealed space

Department for Communities and Local Government, (2019) Diagram 8.3 Fire resisting ceiling below concealed space. [Image]

[img]
Preview
Image
b-volume-1-diagram-8-3-fire-resisting-ceiling-below-concealed-space.jpg

Download (190kB) | Preview
[img] Image
b-volume-1-diagram-8-3-fire-resisting-ceiling-below-concealed-space.svg

Download (4kB)
[img] Text
b-volume-1-diagram-8-3-fire-resisting-ceiling-below-concealed-space.docx
Restricted to Repository staff only

Download (8kB)
[img] Text (Plain text conversion conversion from text to text/plain)
b-volume-1-diagram-8-3-fire-resisting-ceiling-below-concealed-space.txt
Restricted to Repository staff only

Download (456B)

Abstract

NOTE:
The ceiling should meet the following conditions.
a. Provide a minimum fire resistance of EI 30.
b. Be imperforate, except for an opening described in paragraph 5.24.
c. Extend through out the building or compartment.
d. Not be easily demountable.
See para 8.5

Item Type: Image
Additional Information: mml-maui-text-analytics-keywords
Uncontrolled Keywords: compartmentation, suspended ceiling, fire compartment, compartment wall or floor, compartment wall or floor, fire resisting (Fire resistance), principal works, building work, unprotected area, boundary
Subjects: T Technology > TH Building construction > Building standards > fire safety - volume 1: dwellings. 2019 edition - for use in england > Section 8: Cavities – flats
K Law > The Building Regulations 2010 > B3: Internal fire spread (structure)
T Technology > TH Building construction > Building standards
Date Deposited: 14 Mar 2020 15:50
Last Modified: 13 Oct 2021 19:41
URI: https://eprints.buildvoc.co.uk/id/eprint/925