Provision of firefighting shafts

Department for Communities and Local Government, (2019) Provision of firefighting shafts. In: Approved Document B: Fire Safety - Volume 1: Dwellings. 2019 ed. Section 15: Access to buildings for firefighting personnel – flats, 1 (15.6). RIBA Publishing Publication, London, p. 104. ISBN 9781859469156

[img] Text
810.json

Download (1kB)

Abstract

Firefighting shafts and protected stairways should be positioned such that every part of each storey more than 18m above the fire and rescue service vehicle access level complies with the maximum distances given in paragraph 15.7. Distances should be measured from the fire main outlet on a route suitable for laying a hose.
NOTE: If the internal layout is not known, the distance should be measured at two-thirds of the direct distance.

Item Type: Book Section
Additional Information: mml-maui-text-analytics-keywords
Uncontrolled Keywords: direct distance, firefighting shaft, travel distance, travel distance, protected shaft, should, protected stairway, measurement, principal works, span
Subjects: T Technology > TH Building construction > Building standards > fire safety - volume 1: dwellings. 2019 edition - for use in england > Section 15: Access to buildings for firefighting personnel – flats
K Law > The Building Regulations 2010 > B5: Access and facilities for the fire service
T Technology > TH Building construction > Building standards