Junction of compartment wall with roof

Department for Communities and Local Government, (2019) Junction of compartment wall with roof. In: Approved Document B: Fire Safety - Volume 1: Dwellings. 2019 ed. Section 5: Internal fire spread – dwellinghouses, 1 (5.12). RIBA Publishing Publication, London, p. 52. ISBN 9781859469156

Full text not available from this repository.

Abstract

To reduce the risk of fire spreading over the roof from one compartment to another, a 1500mm wide zone of the roof, either side of the wall, should have a covering classified as BROOF(t4), on a substrate or deck of a material rated class A2-s3, d2 or better, as set out in Diagram 5.2a.
Thermoplastic rooflights that, because of paragraph 12.7, are regarded as having a BROOF(t4) classification are not suitable for use in that zone.