Fire doorsets C9

Department for Communities and Local Government, (2019) Fire doorsets C9. In: Approved Document B: Fire Safety - Volume 1: Dwellings. 2019 ed. Appendix C: Fire doorsets, 1 (C9). RIBA Publishing Publication, London, 135 - 135. ISBN 9781859469156

Full text not available from this repository.

Abstract

Rolling shutters should be capable of manual opening and closing for firefighting purposes (see Section 15). Rolling shutters across a means of escape should only be released by a heat sensor, such as a fusible link or electric heat detector, in the immediate vicinity of the door. Unless a shutter is also intended to partially descend as part of a boundary to a smoke reservoir, shutters across a means of escape should not be closed by smoke detectors or a fire alarm system.